Job Name: Location:
Engineer Name: Contractor:
System No.: Date:
Model: PURY-P288TSKMU-A
(Consists of Two PURY-P144TKMU-A and One CMY-R100XLCBK Twinning Kit)
OUTDOOR VRF HEAT RECOVERY SYSTEM FEATURES
• 3-phase, 208/230V
• Modular variable refrigerant flow (VRF) systems;
smaller capacity units can be piped together to form a
single, large-capacity two-pipe system
• Required Twinning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static
pressure; factory set to 0"WG
• Connects to CITY MULTI indoor units; controlled via
CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets
• Operating Temperature Range
Cooling (Outdoor): 23° ~ 115°F (-5° ~ +46°C) DB
Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
PURY-P144TKMU-A
PURY-P144TKMU-A
OPTIONAL PARTS
Twinning Kit*.………………………………...….CMY-R100XLCBK
Branch Joint (T-Branch: 72,000 Btu/h).…………CMY-Y102SS-G2
Branch Joint (T-Branch: 73,000-144,000 Btu/h).………CMY-Y102LS-G2
Branch Joint (T-Branch: 145,000-234,000 Btu/h).………CMY-Y202S-G2
Joint Adapter (Port Connector > 54,000 Btu/h).………….CMY-R160C-J
Main BC Controller.…….……………………………CMB-1016NU-HA
Sub BC Controller.……………….CMB-P104/108NU-GB/1016NU-HB
* Twinning Kit is necessary to combine the refrigerant ows of the
modules and is sold separately.
Specifications System Module 1 Module 2
Unit Type PURY-P288TSKMU-A PURY-P144TKMU-A PURY-P144TKMU-A
Nominal Cooling Capacity Btu/h 288,000 144,000 144,000
Nominal Heating Capacity Btu/h 320,000 160,000 160,000
External Dimensions (H x W x D) In. / mm Refer to Module Data
65 x 68-29/32 x 29-5/23 /
1,650 x 1,750 x 740
65 x
1,650 x 1,750 x 740
Net Weight Lbs. / kg 1,430 / 648 715 / 324
Electrical Power Requirements Voltage, Phase, Hertz
Refer to Module Data** 208 / 230V, 3-phase, 60Hz
Cooling Power Input kW 24.57
Refer to System Data
Heating Power Input kW 27.62
Cooling Current (208/230V) R.L.A. 75.7 / 68.5
Refer to System Data
Heating Current (208/230V) R.L.A. 85.1 / 77.0
Minimum Circuit Ampacity
(MCA)**
A Refer to Module Data** 53 / 48** 53/ 48**
Maximum Breaker Size**
A Refer to Module Data** 60** 60**
Maximum Overcurrent Protection** A Refer to Module Data** 87 / 80** 87 / 80**
Piping Diameter
Refer to System Data
From Twinning Kit to Indoor Units
(Brazed) (In. / mm)
Liquid (High Pressure) 1-1/8 / 28.58
Gas (Low Pressure) 1-3/8 / 34.93
From Modules to Twinning Kit
(Brazed) (In. / mm)
Liquid (High Pressure)
Refer to Module Data
7/8 / 22.2 7/8 / 22.2
Gas (Low Pressure) 1-1/8 / 28.58 1-1/8 / 28.58
Indoor Unit
Total Capacity 50 to 150% of ODUs
Refer to System Data
Model / Quantity
P06 ~ P96 / 2 to 50
(Max. No. Connectable
Branches: 48)
Sound Pressure Levels dB(A) 64.0 61.0 61.0
Fan
Refer to Module Data
Type x Quantity Propeller Fan x 2 Propeller Fan x 2
Airflow Rate CFM 11,300 11,300
Direct-drive Inverter Motor Output kW 0.92 + 0.92 0.92 + 0.92
Compressor Operating Range 7 to 100% Refer to System Data
Compressor Type x Quantity
Refer to Module Data
Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1
Compressor Motor Output kW 9.5 9.5
Compressor Crankcase Heater kW - -
Refrigerant
Refer to Module Data
R410A
Lubricant MEL32
High-pressure Protection Device
Refer to Module Data
601 psi / 4.15 MPa 601 psi / 4.15 MPa
Compressor / Fan Protection Device Overheat Protectio
n / Thermal Switch Overheat Protection / Thermal Switch
Inverter Protection Device Overheat / Overcurrent Protection Overheat / Overcurrent Protection
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;
≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.
68-29/32 x 29-5/23 /
715 / 324
Vista de pagina 0
1 2 3 4

Indice de contenidos

Pagina 1 - PURY-P288TSKMU-A

Job Name: Location:Engineer Name: Contractor:System No.: Date:Model: PURY-P288TSKMU-A(Consists of Two PURY-P144TKMU-A and One CMY-R100XLCBK Twinn

Pagina 2 - PURY-P240,264,288TSKMU-A(-BS)

Module : PURY-P288TSKMU-A – DIMENSIONSIntakeairIntakeairIntakeairDischarge airOutdoor unit 1Outdoor unit 2Front viewLeft viewNote 1.Connect the pipes

Pagina 3 - PURY-P144TKMU-A – DIMENSIONS

Module : PURY-P144TKMU-A – DIMENSIONS(1-25/32)(1)(1)(1-1/8)(7/8)(3/4)(1-1/8) (1-1/8)(1-1/8)(5-17/32)(3-1/16)(5-29/32)(3-23/32)(2-1/16)(1-11/32)(1-3/8

Pagina 4 - CMY-R100XLCBK

Mitsubishi Electric Sales Canada Inc.www.MitsubishiElectric.caSpecifications are subject to change without notice.SB_PURY-P288TSKMU-A_201206 Mitsubish