SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SPLIT-TYPE, AIR CONDITIONERS
No. OC328
NOTE:
• This manual describes only
service data of the indoor
units.
INDOOR UNIT
REMOTE CONTROLLER
CONTENTS
1. REFERENCE MANUAL ······································2
2. SAFETY PRECAUTION···································3
3. PART NAMES AND FUNCTIONS ···················7
4. SPECIFICATIONS············································9
5. NOISE CRITERION CURVES························13
6. OUTLINES AND DIMENSIONS ·····················15
7.
WIRING DIAGRAM
············································19
8.
REFRIGERANT SYSTEM DIAGRAM
··················20
9. TROUBLESHOOTING ···································21
10. DISASSEMBLY PROCEDURE ······················33
11. PARTS LIST ···················································38
ON/OFF
TEMP.
Indoor unit
[Model names] [Service Ref.]
PCA-RP50GA PCA-RP50GA
PCA-RP60GA PCA-RP60GA
PCA-RP71GA PCA-RP71GA
PCA-RP100GA PCA-RP100GA
PCA-RP125GA PCA-RP125GA
PCA-RP140GA PCA-RP140GA
Model name
indication
PCH-P50GAH PCH-P50GAH
PCH-P60GAH PCH-P60GAH
PCH-P71GAH PCH-P71GAH
PCH-P100GAH PCH-P100GAH
PCH-P125GAH PCH-P125GAH
PCH-P140GAH PCH-P140GAH
May 2005
OC328--1.qxp 05.5.17 9:30 AM Page 1
Vista de pagina 0
1 2 3 4 5 6 ... 47 48

Indice de contenidos

Pagina 1 - SERVICE MANUAL

SERVICE MANUALSPLIT-TYPE, HEAT PUMP AIR CONDITIONERSSPLIT-TYPE, AIR CONDITIONERSNo. OC328NOTE:• This manual describes onlyservice data of the indoorun

Pagina 2 - REFERENCE MANUAL

10kWAAkWK/min(CFM)Pa(mmAq)dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)Service Ref.ModePower supply(phase, cycle, voltage)InputRunning currentStarting current

Pagina 3 - SAFETY PRECAUTION

11kWAAkWK/min(CFM)Pa(mmAq)kWdBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)Service Ref.ModePower supply(phase, cycle, voltage)Input w1Running current w1Starting

Pagina 4 - [3] Service tools

12Cooling0.150.691.48Heating0.15<2.48>0.69<10.78>1.48<10.78>Single phase, 50Hz, 230VMunsell 0.70Y 8.59/0.97Plate fin coilSirocco fan

Pagina 5 - [1] Cautions for service

13NOISE CRITERION CURVES590807060504030201063 125 250 500 1000 2000 4000 8000APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISENC-60NC-50NC-40NC-30NC-2

Pagina 6 - Gravimeter

141m1munitabout 1.4mMICROPHONEceiling90807060504030201063 125 250 500 1000 2000 4000 8000APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISENC-60NC-50NC

Pagina 7 - PART NAMES AND FUNCTIONS

15INDOOR UNITPCA-RP50GAPCH-P50GAH1802101571585182 liquid201 gas241 (Drainage)Air intake918161 90254680506 56Electrical box2267062717

Pagina 8 - FUNCTION

16PCA-RP60GAPCA-RP71GAPCH-P60GAHPCH-P71GAH161 90254680506 561240 (suspension bolt pitch)140150320 80177061290121421018081 761310Air outlet1228Air inta

Pagina 9 - SPECIFICATIONS

17161 90254680506 561228Air intake121427020781 961310Air outlet1240 (suspension bolt pitch)140150320 80187068718219824516217(3/8F liquid)(5/8F, 3/4F g

Pagina 10

18161 90254680506 561535Air intake152427020781 961620Air outlet1547(suspension bolt pitch)140150320 80187068718219824516217(3/8F liquid)(5/8F, 3/4F ga

Pagina 11

19PCA-RP50GA PCA-RP60GA PCA-RP71GAPCA-RP100GA PCA-RP125GA PCA-RP140GAPCH-P50GAH PCH-P60GAH PCH-P71GAHPCH-P100GAH PCH-P125GAH PCH-P140GAHX4 X1FAN(WHT)1

Pagina 12

21REFERENCE MANUALService Ref.PUHZ-RP35/50/60/71/100/125/140VHAPUHZ-RP100/125/140YHAPUHZ-RP71/100/125/140VHA-APUHZ-RP200/250YHAPUHZ-RP200/250YHA-APU(H

Pagina 13 - NOISE CRITERION CURVES5

20PCA-RP50GA PCA-RP60GA PCA-RP71GAPCA-RP100GA PCA-RP125GA PCA-RP140GAPCH-P50GAH PCH-P60GAH PCH-P71GAHPCH-P100GAH PCH-P125GAH PCH-P140GAHUnit : mmPipe

Pagina 14 - BAND CENTER FREQUENCIES, Hz

219 TROUBLESHOOTING<Error code display by self-diagnosis and actions to be taken for service (summary)>Present and past error codes are logged a

Pagina 15 - OUTLINES AND DIMENSIONS

229-2. SELF-DIAGNOSIS ACTION TABLENote: Refer to the manual of outdoor unit for the details of display such as F, U, and other E.Error CodeMeaning of

Pagina 16

23Error CodeMeaning of error code and detection method CauseCountermeasureP6Freezing/overheating protection isworking1 Freezing protection (Cooling mo

Pagina 17

24Error CodeMeaning of error code and detection method CauseCountermeasureP9Abnormality of pipe temperature ther-mistor / Condenser-Evaporator (TH5)1

Pagina 18

25E61 Contact failure, short circuit or,mis-wiring (converse wiring) ofindoor/outdoor unit connectingwire2 Defective transmitting receivingcircuit of

Pagina 19 - WIRING DIAGRAM

26(For the separate indoor/outdoor unit power sup-ply system)1 Power supply of 220~240V AC is not supplied toindoor unit.2 The connectors of the optio

Pagina 20 - REFRIGERANT SYSTEM DIAGRAM

27Note: Refer to the manual of outdoor unit for the detail of remote controller.(3)Upward/downward vane performance failure1 The vane is not downward

Pagina 21 - 9 TROUBLESHOOTING

289-4. When wired remote controller or indoor unit micro computer troubles1. If there is not any other wrong when trouble occurs, emergency operation

Pagina 22

299-5. HOW TO CHECK THE PARTSPCH-P50 / 60 / 71 / 100 / 125 / 140GAHPCA-RP50 / 60 / 71 / 100 / 125 / 140GA112233RedWhiteBlackRelay connectorProtector13

Pagina 23

3SAFETY PRECAUTION2[2] Refrigerant recharging(1) Refrigerant recharging process1Direct charging from the cylinder.·R407C cylinder are available on th

Pagina 24

3001020304050-20 -10 0 10 20 30 40 50< Thermistor for lower temperature >Temperature (:)Resistance (k")<Thermistor Characteristic graph&

Pagina 25

319-6-2. Indoor controller boardPCA-RP50GA PCA-RP60GA PCA-RP71GA PCA-RP100GA PCA-RP125GA PCA-RP140GAPCH-P50GAH PCH-P60GAH PCH-P71GAH PCH-P100GAH P

Pagina 26

32SW1Setting by the dip switch and jumper wireFunctionsJumper wireModelsettingsCapacitysettingsPair numbersetting withwireless remotecontrollerFor ser

Pagina 27

33DISASSEMBLY PROCEDURE101. Removing the air intake grille (1) Slide the intake grille holding 2 knobs backward to openthe intake grill.(2) When the

Pagina 28

34Figure 3OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS3. Removing the fan motor (1) Remove the intake grille. (See the figure 1)(2) Disconnect the fa

Pagina 29 - Drain-up

35OPERATING PROCEDURE PHOTOS6. Removing the vane motor (1) Remove the air intake grille. (See the figure 1)(2) Remove the left side panel. (See the f

Pagina 30 - 9-6.TEST POINT DIAGRAM

36OPERATING PROCEDURE PHOTOS9. Removing the drain pan(1) Remove the air intake grille. (See the figure 1)(2) Remove the beam.(3) Remove the side pane

Pagina 31

37OPERATING PROCEDURE PHOTOS13. Removing the heat exchanger. (1) Remove the air intake grille. (See the figure 1)(2) Remove the beam.(3) Remove the s

Pagina 32 - Service board

38PARTS LIST11No.Parts No. Parts Name SpecificationsPCH- PCA-P50GAH RP50GAWiringDiagramSymbolRecom-mendedQ'tyUnitAmountQ'ty / set12345678910

Pagina 33 - DISASSEMBLY PROCEDURE

39No. Parts No. Parts Name SpecificationsPCH- PCA-P60GAHRP60GAWiringDiagramSymbolRecom-mendedQ'tyUnitAmountQ'ty / set Price12345678910111213

Pagina 34 - Figure 3

4[3] Service toolsUse the below service tools as exclusive tools for R407C refrigerant.No. Tool name Specifications1 Gauge manifold ·Only for R407C.·U

Pagina 35 - OPERATING PROCEDURE PHOTOS

40No. Parts No. Parts Name SpecificationsPCA-PCH-WiringDiagramSymbolRecom-mendedQ'tyUnitAmountQ'ty / set Price123456789101112131415161718192

Pagina 36

41No.Parts No. Parts Name SpecificationsWiringDiagramSymbolRecom-mendedQ'tyUnitAmountQ'ty / set Price123456789101112131415161718192021222324

Pagina 37

42STRUCTURAL PARTPCA-RP50GAPCH-P50GAH1234515678911121013161719182021222324252614No.Parts No. Parts Name SpecificationsPCA-RP50GAPCH-P50GAHWiringDiagra

Pagina 38 - PARTS LIST

43STRUCTURAL PARTPCA-RP60GAPCA-RP71GAPCA-RP100GAPCH-P60GAHPCH-P71GAHPCH-P100GAH321456 7 8 9 10 11 12 13141516171819202122232425No.Parts No. Parts Name

Pagina 39 - PCH-P71GAH, PCA-RP71GA

4427911122120191817161514131026 25 24232272134568No.Parts No.Parts NameSpecificationsWiringDiagramSymbolRecom-mendedQ'tyUnitAmountPrice1234567891

Pagina 40 - PCA-RP100GA

45No.Parts No. Parts Name Specifications60/71 100WiringDiagramSymbolRecom-mendedQ'tyUnitAmountPCA-RPGAPrice1234567891050Remarks(Drawing No.)125/1

Pagina 41

46No.Parts No. Parts NameSpecificationsWiringDiagramSymbolRecom-mendedQ'tyUnit(BG00N015G32)AmountQ'ty / setGAHPrice123456789101112CAPACITORC

Pagina 42 - PCH-P50GAH

47OC328--2.qxp 05.5.17 9:28 AM Page 47

Pagina 43

HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANCCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.Dis

Pagina 44

5Cautions for units utilising refrigerant R410ACAUTIONS RELATED TO NEW REFRIGERANTUse new refrigerant pipes.Make sure that the inside and outside of r

Pagina 45

6GravimeterUnit[3] Service toolsUse the below service tools as exclusive tools for R410A refrigerant.No. Specifications1 Gauge manifold ·Only for R410

Pagina 46 - PCH-P71GAH, PCH-P140GAH

7PART NAMES AND FUNCTIONS3● Remote controllerOnce the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.●

Pagina 47

8● DisplayFor purposes of this explanation,all parts of the display are shownas lit. During actual operation, onlythe relevant items will be lit.˚F˚C˚

Pagina 48 - Made in Japan

9SPECIFICATIONS4kWAAkWK/min(CFM)Pa(mmAq)dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)Service Ref.ModePower supply(phase, cycle, voltage)InputRunning currentSt