SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES
·······································
2
2. PART NAMES AND FUNCTIONS ····················· 2
3. SPECIFICATION ················································ 4
4. OUTLINES AND DIMENSIONS ························ 6
5. WIRING DIAGRAM ············································ 7
6. REFRIGERANT SYSTEM DIAGRAM ··············· 8
7. SERVICE FUNCTIONS ····································· 9
8. MICROPROCESSOR CONTROL ··················· 11
9. TROUBLESHOOTING ····································· 18
10. DISASSEMBLY INSTRUCTIONS ···················· 34
No. OBH548
REVISED EDITION-A
SPLIT-TYPE AIR CONDITIONERS
INDOOR UNIT
Outdoor unit service manual
MUZ-GENA MUY-GENA Series (OBH549)
MXZ-B·NA Series (OB444)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
PARTS CATALOG (OBB548)
Revision A:
• MSZ-GE24NA and MSY-GE24NA have been
added.
Please void OBH548.
MSZ-GE06NA
MSZ-GE09NA
MSZ-GE12NA
MSZ-GE15NA
MSZ-GE18NA
MSZ-GE24NA
MSY-GE09NA
MSY-GE12NA
MSY-GE15NA
MSY-GE18NA
MSY-GE24NA
Models
MSZ-GE06/09/12/15/18NA
MSY-GE09/12/15/18NA
Vista de pagina 0
1 2 3 4 5 6 ... 43 44

Indice de contenidos

Pagina 1 - SERVICE MANUAL

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES·······································22. PART NAMES AND FUNCTIONS ····················· 2 3. SPECIFICATION

Pagina 2 - PART NAMES AND FUNCTIONS

10NOTE:• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller.• If main powe

Pagina 3 - ACCESSORIES

11WIRELESS REMOTE CONTROLLERMSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSZ-GE24NAMSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA MSY-

Pagina 4 - SPECIFICATION

12Operation Indicator lampThe operation indicator at the right side of the indoor unit indicates the operation state.• The following indication applie

Pagina 5 - Max. 253

138-3. HEAT ( ) OPERATION (MSZ)(1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.(2) Sel

Pagina 6 - OUTLINES AND DIMENSIONS

148-6. AUTO CHANGE OVER ··· AUTO MODE OPERATION (MSZ)Once desired temperature is set, unit operation is switched automatically between COOL and HEAT o

Pagina 7 - WIRING DIAGRAM

15(4) VANE AUTO ( ) modeThe microprocessor automatically determines the vane angle to make the optimum room temperature distribution.Horizontalposit

Pagina 8 - REFRIGERANT SYSTEM DIAGRAM

168-8. TIMER OPERATION1. How to set the time(1) Check that the current time is set correctly.NOTE: Timer operation will not work without setting the c

Pagina 9 - SERVICE FUNCTIONS

178-9. SMART SET ( ) OPERATION (MSZ-GE06/09/12/15/18NA MSY-09/12/15/18NA)1. How to SET SMART SET operation(1) Press OPERATE/STOP (ON/OFF) button.(2)

Pagina 10 - Indoor electronic

18MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSZ-GE24NAMSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA MSY-GE24NA9-1. CAUTIONS ON TRO

Pagina 11 - MICROPROCESSOR CONTROL

199-2. FAILURE MODE RECALL FUNCTIONOutline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though

Pagina 12 - ) OPERATION

2MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSZ-GE24NAMSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA MSY-GE24NA 1. New model1TECHNI

Pagina 13 - ) OPERATION (MSZ)

202. Indoor unit failure mode tableUpper lamp of OP-ERATION INDICA-TOR lampAbnormal point (Failure mode) Condition RemedyNot lighted Normal — —1-tim

Pagina 14 - 8-7. AUTO VANE OPERATION

219-3. INSTRUCTION OF TROUBLESHOOTINGIndoor unit oper-ates.Outdoor unit does not operate.If blinking of OPERATION INDI-CATOR lamp cannot be checked, i

Pagina 15 - (MSZ-GE24NA MSY-GE24NA)

229-4. TROUBLESHOOTING CHECK TABLEBefore taking measures, make sure that the symptom reappears for accurate troubleshooting.When the indoor unit has s

Pagina 16

23OPERATION INDICATORNo. Abnormal point Operation indicator lamp Symptom Condition Remedy1MXZ type Operation mode settingUpper lamp lights and lower

Pagina 17 - Indicator lamp as following

24 A Check of indoor fan motor9-6. TROUBLESHOOTING FLOWThe indoor fan motor error has occurred, and the indoor fan does not operate.Turn OFF the pow

Pagina 18 - TROUBLESHOOTING

25MSZ-GE24NA MSY-GE24NAThe indoor fan motor error has occurred, and the indoor fan does not operate.Turn OFF the power supply.Is there any foreign ma

Pagina 19 - MSY-GE24NA

26 B Check of remote controller and indoor electronic control P.C. board Check if the remote controller is exclusive for this air conditioner.Does th

Pagina 20

27 C Check of indoor P.C. board and indoor fan motorTurn OFF the power supply.Remove indoor fan motor connector CN211 from indoor power P.C. board a

Pagina 21

28CN211R111Indoor electroniccontrol P.C.BoardIndoor terminalP.C. boardFuse(F11)Varistor(NR11)YesNo 1. The fan motor connector's lead wire is

Pagina 22

29 D How to check miswiring and serial signal errorTurn OFF inverter-controlled lighting equipment.Turn OFF the power supply and then turn ON again.P

Pagina 23

3Remote controller Display sectionFront panelAir filter(Nano platinum filter)Air inletAir cleaning filter(Electrostatic anti-allergy enzyme filter)Air

Pagina 24 - A Check of indoor fan motor

30Turn OFF inverter-controlled lighting equipment.Turn OFF the power supply and then turn ON again.Press EMERGENCY OPERATION switch.•••AIs serial sign

Pagina 25

31 E Electromagnetic noise enters into TV sets or radiosYesIs the unit grounded?NoGround the unit.YesIs the distance between the antennas and the ind

Pagina 26 - MSZ-GE24NA MSY-GE24NA

321. Indoor power P.C. board, Indoor terminal P.C. board9-7. Test point diagram and voltageIndoor terminal P.C. board Indoor power P.C. board Please r

Pagina 27

33MSZ-GE24NA MSY-GE24NA3. Indoor terminal P.C. board, Indoor electronic control P.C. board, Power monitor receiver SW P.C. boardJR24JRREJRDFTJR07JRPR

Pagina 28

3410-1. MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NA MSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NANOTE: Turn OFF power supply before d

Pagina 29

35OPERATING PROCEDURE PHOTOS2. Removing the indoor electronic control P.C. board and the room temperature thermistor(1) Remove the panel (Refer to 1.)

Pagina 30

36OPERATING PROCEDURE PHOTOS4. Removing the nozzle assembly(1) Remove the panel (Refer to 1.) and the corner box.(2) Remove the indoor/outdoor connect

Pagina 31

37OPERATING PROCEDURE PHOTOS6. Removing the indoor fan motor, the indoor coil thermistor, and the line flow fan(1) Remove the panel (Refer to 1.) and

Pagina 32

3810-2. MSZ-GE24NA MSY-GE24NANOTE: Turn OFF power supply before disassembling.OPERATING PROCEDURE PHOTOS1. Removing the panel(1) Remove the horizont

Pagina 33

39OPERATING PROCEDURE PHOTOS4. Removing the nozzle assembly(1) Remove the panel (Refer to 1.) and the corner box.(2) Remove the V.A. clamp, and then t

Pagina 34 - DISASSEMBLY INSTRUCTIONS

4Indoor model MSZ-GE06NAMSZ-GE09NAMSY-GE09NAMSZ-GE12NAMSY-GE12NAPower supply V, phase, Hz 208/230, 1, 60Max. fuse size (time delay)/ Disconnect switch

Pagina 35 - OPERATING PROCEDURE PHOTOS

40OPERATING PROCEDURE PHOTOS7. Removing the water cut, the indoor fan motor, the indoor coil thermistor, and the line flow fan(1) Remove the panel (Re

Pagina 39

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN© Copyright 2009 MITSUBISHI ELECTRIC CO.,LTDDistributed in Sep. 2010. No

Pagina 40

53-2. OUTLET AIR SPEED AND COVERAGE● The air coverage is the figure up to the position where the air speed is 1 ft./s., when air is blown out horizont

Pagina 41

6Unit: inchMSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NAMSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA8-5/169-1/89-15/167/86-1/8 6-1/83-1

Pagina 42

7MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NAMSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NA5WIRING DIAGRAMMSZ-GE24NAMSY-GE24NA

Pagina 43

8MSZ-GE06NA MSZ-GE09NA MSZ-GE12NA MSZ-GE15NA MSZ-GE18NAMSY-GE09NA MSY-GE12NA MSY-GE15NA MSY-GE18NAUnit: inchIndoorheatexchangerFlared connectio

Pagina 44

97-1. TIMER SHORT MODEFor service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P.C. board.The time will be