SPLIT-TYPE, AIR CONDITIONERS
ADVANCE AND EVER ADVANCING
TECHNICAL & SERVICE MANUAL
<indoor unit> Service ref.
Models
PED-2EJA
1
.UK
PED-2.5EJA
1
.UK
The Slim Line.
From Mitsubishi Electric
TM
1. FEATURES ················································· 1
2. PART NAMES AND FUNCTIONS ·············· 2
3. SPECIFICATIONS ······································ 4
4. DATA ··························································· 5
5. REFRIGERANT SYSTEM DIAGRAM ······· 8
6. OUTLINES AND DIMENSIONS ················· 9
7. WIRING DIAGRAM ···································· 10
8. DISASSEMBLY INSTRUCTIONS ············· 11
9. PARTS LIST ·············································· 14
10
. MICROPROCESSOR CONTROL·············· 19
11
. TROUBLE SHOOTING ······························ 25
12
. OPTIONAL PARTS ···································· 27
CONTENTS
INDOOR UNIT
REMOTE CONTROLLER
This manual does not cover the
following outdoor units. When
servicing them, please refer to
the service manual No.OC149B
and this manual as a set.
PU-2VJA2.UK
PU-2.5VJA
2.UK
2000
Vista de pagina 0
1 2 3 4 5 6 ... 35 36

Indice de contenidos

Pagina 1 - PED-2.5EJA

SPLIT-TYPE, AIR CONDITIONERSADVANCE AND EVER ADVANCINGTECHNICAL & SERVICE MANUAL<indoor unit> Service ref.ModelsPED-2EJA1.UKPED-2.5EJA1.UKTh

Pagina 2

8PED-2EJA1.UKPED-2.5EJA1.UKStrainerRefrigerant pipe(option) 9.52mm(3/8)(With heat insulator)Flexible tubeFlaredconnectionThermistorRT2DistributorRe

Pagina 3 - FEATURES

91010301525617640A81 C B 81292276181AE 13131632828545 802772130 640 30243510179109103.53.525628840176Set10-ø3 (1.6, 2HP)12-ø3 (2.5HP)10-ø3 (1.6, 2HP)1

Pagina 4 - PART NAMES AND FUNCTIONS

107WIRING DIAGRAM31312312432132132113137** Drain sensor Drain pump Drain sensor connector Drain pump connector DS DP CN50 CNP* fig: *1220V

Pagina 5 - ● Operation buttons

118DISASSEMBLY INSTRUCTIONSFigure1.Disconnect the fan motor connecter(and the booster heater connector)Drain pancatches (Hidden)Dr

Pagina 6 - SPECIFICATION

12Figure3.Fan baseSirocco fanSirocco fanHousing assemblyHousing assemblyPiecePieceLegBushBushMotor

Pagina 7

13Pump coverassemblyDrain socketDrain pan coverDrain pumpassemblyDrain hoseRubber plugDrain pan122. Removing the drain water lift-up pump1. Remove the

Pagina 8

149PARTS LISTPED-2EJA1.UKPED-2.5EJA1.UKEXTERNAL PARTS9, 101.27, 83, 45, 6No.1234567891011Part No. Part Name Drawing No.Qt’y/setSpec.11PED-2.5EJA1PED-2

Pagina 9 - 4. ELECTRICAL DATA

15PED-2EJA1.UKPED-2.5EJA1.UKBLOWER PARTS5, 67, 811449, 10117, 85, 62, 3No.1234567891011121314Part No. Part Name Drawing No.Qt'y/setW353715H01 222

Pagina 10 - Indoor unit

16PED-2EJA1.UKPED-2.5EJA1.UKCONTROL BOX PARTS65347217No.12345678910Part No. Part Name Drawing No.P436109X01P436110X01BG00L760G22BG65T178H03BG71V161H04

Pagina 11 - OUTLINES & DIMENSIONS

17PED-2EJA1.UKPED-2.5EJA1.UKELECTRICAL PARTSNo.12345Part No. Part Name Drawing No.BC00C006G34BG00K507G02BG78R190G10Qt’y/setSpec.J controller10m0.5m111

Pagina 13 - Fan base

18PED-2EJA1.UKPED-2.5EJA1.UKDRAIN WATER LIFT-UP PUMP PARTS (OPTIONAL PARTS)341.25No.12345Part No. Part Name Drawing No.BG56J144G13DB26F111H03BB00P145G

Pagina 14 - Figure3

1910MICROPROCESSOR CONTROL

Pagina 20

2511TROUBLE SHOOTING

Pagina 22

2712OPTIONAL PARTS1. REFRIGERANT PIPES28˚C26˚C8:00Normaioperation8:00Normaioperation23:00Setbackoperation3. TIMERWhen using a program timer, a program

Pagina 23

11. TOTALLY INVISIBLE INDOOR UNIT BEHIND THE CEILINGThe totally hidden indoor unit that lies above the ceiling surface enables you to utilize full flo

Pagina 24

283-3 HOW to connect program timer(1) Install the program timer next to the remote controller the same way as the remote controller is installed.(2)

Pagina 25

291171171211311356.523.5 118"ENGAGED" indicatorWhen this indicator is lit, transmisson is in progress and all swiches are inoperative.

Pagina 26

304-3 Connection method(1) Connection in the power supply cord.1. Connect the power supply cord to the power supply terminal-block and fix in-place wi

Pagina 27 - TROUBLE SHOOTING

315. PROGRAM TIMER ADAPTERThis adapter is needed when a program timer(PAC-815PT)or a centralised remote controller(PAC-805RC)is used.Part No. PAC-825A

Pagina 28

32Part No. PAC-559AD7. REMOTE INDICATION ADAPTERThis adapter is used for remote indication(operation/check.)15PowersupplyBRNREDORNYRWGRNBRNREDORNYRWG

Pagina 30 - <PAC-SK65PTA>

HEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYOMEE00K028Issued in Nov. 2000Printed in JapanNew publication, effe

Pagina 31 - 4-2 Functions

25. ADVANCED MICROPROCESSOR CONTROL(1) Ultra - thin 12mm(1/2" )remote controller.(2) Attractive LED display .Every operation condition is indica

Pagina 32 - 4-3 Connection method

3● Remote controller● Operation buttons● Settings remain in effect until changed. Air conditioner canbe operated by simply pushing ON/OFF button once

Pagina 33 - 5-2 Connection method

43SPECIFICATIONModelPED-2.5EJA1.UKPED-2EJA1.UKItemCooling capacity4 Btu/h 22,200W 6,500Total input 4 kW 2.69Power supply~/N, 50Hz, 220-240VInput kW 0.

Pagina 34 - 6. TIMER ADAPTER

54DATAService Ref.Indoorintake airWB˚C20 25 30 35 40 45CA P.C. CA P.C. CA P.C. CA P.C. CA P.C. CA P.C.1. PERFORMANCE DATA1) COOLING CAPACITYNote C A:

Pagina 35

6Fan Performance <30Pa>External static pressure (Pa)(1Pa 0.1mmAg)Air Flow (CMM)6 8 10 12 14 16 18 208 10121416 1820 22204060801001201400.80.

Pagina 36 - Printed in Japan

7ModelsIndoorOutdoorCapacity(W)Total input(kW)Input(kW)Current(A)Starting current(A)Input(kW)Current(A)Starting current(A)IndoorOutdoorIndoor ······22