TECHNICAL & SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
CONTENTS
1. SAFETY PRECAUTION·······································2
2.
COMBINATION OF INDOOR AND OUTDOOR UNITS
····6
3. FEATURES···························································7
4. SPECIFICATIONS················································8
5. DATA ····································································9
6. OUTLINES AND DIMENSIONS ·························11
7. WIRING DIAGRAM············································12
8. WIRING SPECIFICATIONS ·······························13
9. SPECIFICATIONS FOR ELECTRICAL WORK ····14
10.
REFRIGERANT SYSTEM DIAGRAM
···················17
11. CAPACITY CURVES ··········································18
12.APPLICABLE EXTENSION PIPE FOR EACH MODEL···19
13. TROUBLESHOOTING········································25
14. DISASSEMBLY PROCEDURE ··························71
15. PARTS LIST ·······················································79
16. OPTIONAL PARTS······························BackCover
No.OC317
R410A
Outdoor unit
[model names]
PUHZ-RP8YHA
PUHZ-RP10YHA
[Service Ref.]
PUHZ-RP8YHA
PUHZ-RP10YHA
Model name
indication
PUHZ-RP8YHA
PUHZ-RP10YHA
OC317-1.qxp 04.11.26 9:33 AM Page 1
Vista de pagina 0
1 2 3 4 5 6 ... 85 86

Indice de contenidos

Pagina 1 - PUHZ-RP10YHA

TECHNICAL & SERVICE MANUALSPLIT-TYPE, HEAT PUMP AIR CONDITIONERSCONTENTS1. SAFETY PRECAUTION·······································22. COMBINATION

Pagina 2 - 1 SAFETY PRECAUTION

105-2. COMPRESSOR TECHNICAL DATAU-VU-WW-VUnitCompressor modelWindingResistance( " )ANV47FFBMT(at 20°C)0.720.720.72PUHZ-RP8, 10YHA1m1mMICROPHONEUN

Pagina 3 - [1] Cautions for service

116 OUTLINES AND DIMENSIONSPUHZ-RP8YHAPUHZ-RP10YHA00[7O.D [ 28.582O.D [ 25.4[ 25.42Refrigerant GAS PIPE connection (BRAZING)[ 12.7 (1/2F)[ 9.52 (3/8F)

Pagina 4 - 1-2. CHANGED POINT

127 WIRING DIAGRAMPUHZ-RP8YHAPUHZ-RP10YHAOC317-1.qxp 04.11.26 9:33 AM Page 12

Pagina 5 - Dimension B

138 WIRING SPECIFICATIONS✽1 : In case that cable with stripe of yellow and green is available.✽2 : In the flat cables are connected as this picture, t

Pagina 6 - 2-1. 1:1 SYSTEM

14SPECIFICATIONS FOR ELECTRICAL WORK99-1. FIELD ELECTRICAL WIRING (POWER WIRING SPECIFICATIONS) PUHZ-RP•YHAOutdoor unitPower supplyPhaseFrequency &

Pagina 7 - 3 FEATURES

159-2. M-NET WIRING METHOD(Points to notice)(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electrom

Pagina 8 - 4 SPECIFICATIONS

169-2-3. Regulations in address settingsIn case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the

Pagina 9

1710 REFRIGERANT SYSTEM DIAGRAMPUHZ-RP8YHAPUHZ-RP10YHAStrainer#50Strainer#50Strainer#100Strainer#100Strainer#100Strainer#100OilseparatorStrainer#100St

Pagina 10 - 5-3. NOISE CRITERION CURVES

1811 CAPACITY CURVES-5 0 5 10 15 20 25 30 35 40 46161820220.60.811.21.4Cooling capacity ratioOutdoor intake air dry-bulb temperature <D.B. :>-5

Pagina 11 - 6 OUTLINES AND DIMENSIONS

1912 APPLICABLE EXTENSION PIPE FOR EACH MODEL12-1. 1:1 SYSTEM(1) Pipe length70m[30m]SWSW : When the outdoor unit is located lower than the indoor unit

Pagina 12 - 7 WIRING DIAGRAM

21 SAFETY PRECAUTIONCautions for units utilizing refrigerant R410A1-1. CAUTIONS RELATED TO NEW REFRIGERANTUse new refrigerant pipes.Make sure that the

Pagina 13 - 8 WIRING SPECIFICATIONS

20(3) Capacity correctionCooling and heating capacity is lowered according to the piping length. Capacity can be obtained by referring to the followin

Pagina 14 - Electrical wiring

21Liquid pipeGas pipeLiquid pipeGas pipeLiquid pipeGas pipeLiquid pipeGas pipeLiquid pipeGas pipe[19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [

Pagina 15

22OD(mm)Pipe diameter and thickness[6.350.8Be sure to use hard (tempered) one for pipe over [22.2.(Do not use soft (annealed) one.) 0.8 0.8 1.0 1.0 1.

Pagina 16

23A+B+C+DAmount of additional refrigerant charge (kg)30 m and less 31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less 71-80 m and les

Pagina 17 - 10 REFRIGERANT SYSTEM DIAGRAM

24Refrigerant collecting (pump down)Perform the following procedures to collect the refrigerant when moving the indoorunit or the outdoor unit.1 Befor

Pagina 18 - 11 CAPACITY CURVES

2513 TROUBLESHOOTING<Error code display by self-diagnosis and actions to be taken for service (summary)>Present and past error codes are logged

Pagina 19 - 12-1. 1:1 SYSTEM

2613-2. CHECK POINT UNDER TEST RUN(MA remote controller)(1) Before test run• After installation of indoor and outdoor units, piping work and electric

Pagina 20 - Cpacity ratio [%]

27wPress the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the contents of LCD display.LCDContents of

Pagina 21 - Marks in the table above

2813-3. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER13-3-1. Error history of unit(1) Wired remote controllerMode numberSetting numberRefrigerant

Pagina 22 - Pipe diameter and thickness

294 To cancel self-diagnosisThere are following two methods to cancel self-diagnosis:Press the H “CHECK” button twice within three seconds.➜Self-diagn

Pagina 23 - <Table 10>

3GravimeterUnit[3] Service toolsUse the below service tools as exclusive tools for R410A refrigerant.No. Specifications1 Gauge manifold ·Only for R410

Pagina 24 - Start and finish of test run

30[Procedure]1. Press the CHECK button twice.2. Press the temperaturebuttons.3. Point the remote controller at the sensor on the indoor unit andpress

Pagina 25 - 13 TROUBLESHOOTING

3113-3-2. Wired Remote controller DiagnosisIf operation can not be carried out from remote controller, tryremote controller diagnosis with following p

Pagina 26 - PAR-20MAA

3213-4. SELF-DIAGNOSIS ACTION TABLE <Abnormalities detected when the power is put on>(Note 1) Refer to indoor unit section for code P and code

Pagina 27 - (Factory setting)

33Error CodeMeaning of error code and detection method Judgment and actionEb(6845)Mis-wiring of indoor/outdoor unit connecting wire (converse wiring o

Pagina 28

34<Abnormalities detected while unit is operating>Error CodeMeaning of error code and detection method Judgment and actionU1(1302)Abnormal high

Pagina 29

35ThermistorsOpen detection Short detectionSymbolNameTH3, TH32TH6TH7TH8– 40: or below– 40: or below– 40: or below– 35: or below90: or above90: or abov

Pagina 30 - TEST RUN

36Error CodeMeaning of error code and detection method Judgment and actionUL(1300)Abnormal low pressure (63L worked)Abnormal if 63L is worked (under-0

Pagina 31

37Error CodeMeaning of error code and detection method Judgment and actionE9(6841)Indoor/outdoor unit communicationerror (Transmitting error) (Outdoor

Pagina 32

38Error CodeMeaning of error code and detection method Case Judgment and actionA0(6600)Address duplicate definitionThis error is displayed when transm

Pagina 33

39A6(6606)Communication error with communica-tion processorDefective communication between unitprocessor and transmission processorNote) The address a

Pagina 34

41-2. CHANGED POINT• Precautions when reusing existing R22 refrigerant pipes (1) Flowchart Connecting a new air conditioner to existing R22 refrigera

Pagina 35

40Error CodeMeaning of error code and detection method Case Judgment and actionA7(6607)5. If displayed address or attribute isFRESH MASTER, Indoor uni

Pagina 36

4113-5. TROUBLESHOOTING BY INFERIOR PHENOMENAPhenomenaFactor Countermeasure1. Remote controller display does notwork.2. “H0” display is remained on th

Pagina 37

42PhenomenaFactorCountermeasure7. Remote controller display works nor-mally and the unit performs heatingoperation, however, the capacitycannot be ful

Pagina 38

4313-6. HOW TO CHECK THE PARTSPUHZ-RP8YHAPUHZ-RP10YHA123456MBlueBrownYellowOrangeRedWhiteParts nameCheck pointsDisconnect the connector then measure t

Pagina 39 - Continued to the next page

4413-7. HOW TO CHECK THE COMPONENTS<Thermistor feature chart>Low temperature thermistors• Thermistor <Outdoor pipe> (TH3, TH32)• Thermisto

Pagina 40 - From the previous page

45<Output pulse signal and the valve operation>(2) Linear expansion valve operationABCOpenExtra tightning (about 32 pulse)Pulse number500 pulseO

Pagina 41

46Main bodyLead wireStopperCoilABe sure to attach thestopper to pipe B.BA(3) How to attach and detach the coil of linear expansion valve <Composit

Pagina 42

4713-8. EMERGENCY OPERATION (1) When the error codes shown below are displayed on outdoor unit or microcomputer for wired remote controller or indoor

Pagina 43 - 13-6. HOW TO CHECK THE PARTS

4813-9. TEST POINT DIAGRAMOutdoor controller circuit boardPUHZ-RP8YHAPUHZ-RP10YHACommunicationpower supply D71 Voltage developed across:16-30V DC–+CNS

Pagina 44

282V DC282V DCBrief Check of POWER MODULEW Usually, they are in a state of being short-circuited if they are broken.Measure the resistance in the foll

Pagina 45 - Linear expansion valve

5(2) Cautions for refrigerant piping workNew refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R4

Pagina 46 - <Composition>

50Outdoor Noise filter circuit boardPUHZ-RP8YHAPUHZ-RP10YHALI1, LI2, LI3, NIPOWER SUPPLYLI1-LI2/LI-LI3/LI3-LI1 : AC380/400/415V inputLI1-NI/LI2-NI/LI3

Pagina 47 - 13-8. EMERGENCY OPERATION

51Outdoor Fan controller circuit boardPUHZ-RP8YHAPUHZ-RP10YHABrief Check of IGBTW Usually, they are in a state of being short-circuited if they are br

Pagina 48 - 13-9. TEST POINT DIAGRAM

52SwitchTypeofswitchDipswitchSW112No.Function Effective timingAction by the switch operationCompulsory defrosting Start NormalWhen compressor is worki

Pagina 49 - Outdoor Power circuit board

53(2) Function of connectorsCN31Types Connector Function Effective timingConnectorSW6SW8SW10SW6-1SW6-2SW6-3SW6-4SW6-5SW6-6SW8-1SW10-1SW10-2StartShort

Pagina 50

54Special function(a) Low-level sound priority mode (Local wiring)Unit enters into Low-level sound priority mode by SW7-1, 2 and external signal input

Pagina 51

55<Display function of inspection for outdoor unit>The blinking patterns of both LED1(green) and LED2(red) indicate the types of abnormality whe

Pagina 52

56LED indications of fan operating condition (LED1 on outdoor Fan controller circuit board)Operation LED1 (Red)LightedNormal (Stop)Normal (Operating)F

Pagina 53 - (2) Function of connectors

57<Outdoor unit operation monitor function>[When option part ‘A-Control Service Tool(PAC-SK52ST)’ is connected to outdoor controller circuit boa

Pagina 54

58SW2 setting1ON23456Display detailExplanation for display UnitPipe temperature / Liquid(TH3)– 40~90– 40~90(When the coil thermistor detects 0: or bel

Pagina 55 - Detailed

59SW2 setting1ON23456Display detailExplanation for display UnitPipe temperature / Liquid(TH3) on erroroccurring– 40~90– 40~90(When the coil thermistor

Pagina 56

62 COMBINATION OF INDOOR AND OUTDOOR UNITSIndoor unitOutdoor unitPUHZ-RP·YHA810PEH-RP·MYAIndoor unitOutdoor unitPUHZ-RP·YHA810PLA-RP4AA ✕ 2PLA-RP5AA ✕

Pagina 57 - 1 second

60SW2 setting1ON23456Display detailExplanation for displayUnitCapacity setting displayDisplayed as an outdoor capacity code.Codedisplay1ON234561ON2345

Pagina 58 - Explanation for display Unit

611ON23456°CDischarge super heat. SHd0~255Cooling = TH4-TH6Heating = TH4-TH50~255(When the temperature is 100°C or more, hundredsdigit, tens digit and

Pagina 59

62SW2 settingDisplay detailExplanation for display Unit1ON23456%Capacity save0~255When air conditioner is connected to M-NET and capacity save mode is

Pagina 60

63SW2 settingDisplay detailExplanation for display Unit1ON23456PulseLEV-A opening pulse on error occurring0~4800~480(When it is 100 pulse or more, hun

Pagina 61

64SW2 settingDisplay detailExplanation for display Unit:0~255(When the temperature is 100°C or more, hundredsdigit, tens digit and ones digit are disp

Pagina 62

65SW2 settingDisplay detailExplanation for display UnitControlling status of compressor operating frequency1ON23456CodedisplayThe following code will

Pagina 63

66FunctionSettingsMode No.Setting No.RemarksFilter signFan speedNo. of air outletsInstalled options (high- performance filter)Horizontal vane settingE

Pagina 64

67FUNCTIONFUNCTION3[Operating instructions]11Checking the function settingsIf you change the setting in the function setting procedure, the contents o

Pagina 65 - •The ones digit

68FUNCTIONFUNCTION444Setting the indoor unit numberPress D(CLOCK ON OFF) and [--] will start to flash in the unitnumber display (4) .Press C (TIMER SE

Pagina 66

69FUNCTIONFUNCTIONFUNCTION212188Registering the settings from steps 33to 77into memoryThe mode and setting numbers (1)(2) will start to flash when the

Pagina 67

73 FEATURESCHARGELESS SYSTEMPRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.(Max.30m)The refrigerant circuit with LEV(Linear Expansi

Pagina 68

70By setting unit number with the button, specified indoor unit starts performing fan operation. Detect which unit is assigned to which numbe

Pagina 69 - FUNCTION

7114 DISASSEMBLY PROCEDUREOPERATING PROCEDUREPHOTOSPUHZ-RP8YHA PUHZ-RP10YHAPhoto 1 (front)Photo 2 (rear)Service panelfixing screw(8pcs)Front panelfixi

Pagina 70

72OPERATING PROCEDURE PHOTOSPhoto 5Photo 3Photo 44. Removing the fan motor(1) Remove• 10 fan guard fixing screws (5o15) (see photo 3).• Fan guard by s

Pagina 71 - 14 DISASSEMBLY PROCEDURE

73OPERATING PROCEDURE PHOTOSPhoto 6Photo 75. Removing the electrical parts box(1) Remove• Service panel.• Waterproof sheet for the electrical parts.(2

Pagina 72 - OPERATING PROCEDURE PHOTOS

74OPERATING PROCEDURE PHOTOSPhoto 9Photo 88. Removing the thermistor <Discharge>(1) Remove the service panel.(2) Disconnect the connector TH4 (3

Pagina 73

75OPERATING PROCEDURE PHOTOSPhoto 10Photo 1110. Removing the 4-way solenoid valve(1) Remove• Service panel.• 3 cover panel fixing screws (5o10).• Cove

Pagina 74

Photo 12Lead wire for thehigh pressureswitchHigh pressureswitchLead wire forthe low pressureswitchLow pressureswitch76OPERATING PROCEDUREPHOTOS &

Pagina 75

77Photo 13PHOTOS & ILLUSTRATIONOPERATING PROCEDURE14. Removing the reactor(1) Remove• Service panel• 2 screws (4o8) that hold the terminal block f

Pagina 76 - PHOTOS & ILLUSTRATION

78OPERATING PROCEDURE PHOTOSPhoto 17Photo 1616. Removing the accumulator(1) Remove• Service panel (see photo 1).• Electrical parts box (see photo 6).•

Pagina 77

7915 PARTS LISTFAN PARTSPUHZ-RP8YHAPUHZ-RP10YHAPUHZ112211112211MOTOR CAPNUT M16SUPPORTMOTOR SUPPORTFAN MOTORPROPELLERR01 E01 122R01 E05 097—R01 E

Pagina 78

84 SPECIFICATIONS3-ph, 50Hz, 380-400-415V (4wires)Munsell 3Y 7.8/1.1Linear Expansion ValveHermeticANV47FFBMTLine start HP switch, LP switch, Discharge

Pagina 79 - 15 PARTS LIST

80STRUCTURAL PARTSPUHZ-RP8YHAPUHZ-RP10YHA11261314151612181917222526242320214321098751112OC317-3.qxp 04.11.26 9:41 AM Page 80

Pagina 80 - STRUCTURAL PARTS

81PUHZ11111111112411111111111111111121111111111241111111111111111112FAN GUARDSIDE PANEL (L)FRONT PANELSERVICE PANELCOVER PANELSEPARATORTHERMISTOR (OUT

Pagina 81 - RP8 RP10

82FUNCTIONAL PARTSPUHZ-RP8YHAPUHZ-RP10YHA117161514131211109876543219 1820OC317-3.qxp 04.11.26 9:41 AM Page 82

Pagina 82 - FUNCTIONAL PARTS

83PUHZ111111111112111111111111111111111112111111111111MOTOR FOR COMPRESSORLINEAR EXPANSION VALVE COILLINEAR EXPANSION VALVECHARGE PLUGCHARGE PLUGSTOP

Pagina 83

84ELECTRICAL PARTSPUHZ-RP8YHAPUHZ-RP10YHA12345678 9 11121314161015OC317-3.qxp 04.11.26 9:41 AM Page 84

Pagina 84 - ELECTRICAL PARTS

85PUHZ1122211111111121111222111111111211CONTROLLER CIRCUIT BOARDCIRCUIT BOARD SUPPORT PLATEFUSEFUSEFUSE HOLDERNOISE FILTER CIRCUIT BOARDTERMINAL BLOCK

Pagina 85

16 OPTIONAL PARTSParts nameRP8·RP10Parts No.MSDD-50WR-EMSDT-111R-EMSDF-1111R-EPAC-SG73RJ-E([9.52 ➝ [12.7)PAC-SG92DS-EPAC-SG86AG-EPAC-SG87AG-EPAC-SG82D

Pagina 86 - 16 OPTIONAL PARTS

95 DATAParts nameOutdoor unit250V 6.3AANV47FFBMTHAM-BD32(0~480 Pulse)2.7mH 25ADC12V0:/15t, 10:/9.6t, 20:/6.3t, 25:/5.4t, 30:/4.3t, 40:/3.0t0:/1