SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················2
3. INDOOR/OUTDOOR
CORRESPONDENCE TABLE ···························3
4. INDOOR UNITS COMBINATION ·······················3
5. SPECIFICATION·················································4
6. NOISE CRITERIA CURVES······························ 5
7. OUTLINES AND DIMENSIONS ························ 6
8. WIRING DIAGRAM ············································7
9. REFRIGERANT SYSTEM DIAGRAM················8
10. PERFORMANCE CURVES································9
11. MICROPROCESSOR CONTROL·····················14
12. TROUBLESHOOTING······································19
13. DISASSEMBLY INSTRUCTIONS·····················29
14. PARTS LIST······················································32
15. OPTIONAL PARTS···········································34
Inverter-controlled multi system
Model
MXZ-18TV -
MXZ-18TV -
E2
E1
No. OB280
REVISED EDITION-A
This manual describes technical data of outdoor unit.
For the indoor unit refer to the service manuals No. OB229, OB227 REVISED EDITION-B, OB252 REVISED EDI-
TION-A,OC280 REVISED EDITION-A,OC281 REVISED EDITION-A and OC165 of corresponding models.
Model indication
Revision:
MXZ-18TV - has been added.
• Please void OB280.
E2
SPLIT-TYPE, HEAT PUMP AIR CONDITIONER
OB280-1.qxp 02.12.19 11:15 AM Page 1
Vista de pagina 0
1 2 3 4 5 6 ... 35 36

Indice de contenidos

Pagina 1 - MXZ-18TV

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ····································22. PART NAMES AND FUNCTIONS······················23. INDOOR/OUTDOOR CO

Pagina 2 - PART NAMES AND FUNCTIONS

1010-2. Capacity and input correction by inverter output frequency (OUTDOOR UNIT:MXZ-18TV)NOTE 1 : Inverter output frequency : COOL 55Hz,HEAT 80HzNOT

Pagina 3 - INDOOR UNITS COMBINATION

1110-3. Outdoor low pressure and outdoor unit current 1. 07-class unit in single operation (OUTDOOR UNIT : MXZ-18TV)NOTE:The unit of pressure has been

Pagina 4 - SPECIFICATION

122. 09-class unit in single operation (OUTDOOR UNIT : MXZ-18TV)NOTE:The unit of pressure has been changed to MPa on the international system of units

Pagina 5 - NOISE CRITERIA CURVES6

133. 12-class unit in single operation (OUTDOOR UNIT : MXZ-18TV)NOTE:The unit of pressure has been changed to MPa on the international system of units

Pagina 6 - OUTLINES AND DIMENSIONS

MICROPROCESSOR CONTROL1411CompressorpowerfactorIndoor unitmicroprocessorSSR61DrivecircuitTransistormoduleIndoor UnitBIndoor UnitBComp.Dischargetempera

Pagina 7 - WIRING DIAGRAM

15Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.• The standard opening is on the straight line

Pagina 8 - REFRIGERANT SYSTEM DIAGRAM

16(1) LEV opening correction by suction super heat (COOL, DRY)(Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature)When CO

Pagina 9 - PERFORMANCE CURVES

1711-2.Operational frequency range(3) LEV opening correction by discharge temperatureWhen LEV correction output is 0 pulse by the suction super heat a

Pagina 10 - (OUTDOOR UNIT:MXZ-18TV)

18This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge temp. thermistor.(1) Compressor ON/

Pagina 11

1912 TROUBLESHOOTING3. Troubleshooting procedure1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate

Pagina 12

PART NAMES AND FUNCTIONS2OUTDOOR UNITAir inletAir outlet(back and side)Model indicationMXZ-18TV-MXZ-18TV-E2E12TECHNICAL CHANGES1MXZ-18RV - ➔ MXZ-18TV

Pagina 13

20Outdoor power system When the compressor operation has been interrupted by overcurrentprotection continuously three times within 1 minute after star

Pagina 14 - MICROPROCESSOR CONTROL

21Current protection When the outdoor unit input current exceeds 15.5A.These symptoms do not mean any abnor-mality of the product, but check the follo

Pagina 15 - 11-1.LEV control

22BBCheck of outdoor unit serial signalNoYesStart1. Check the indoor unit with referring to the indoor unit service manual.2. Turn off the power suppl

Pagina 16

23CCCheck of R. V. coilNoYesNoYesNoYesNoYesNoYesStart1. Disconnect the lead wire leading to the compressor.2. Turn on power supply to the indoor and

Pagina 17 - 11-3.Heat defrosting control

24DDCheck of LEVNoYesNoYesStartTurn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.Is "click - c

Pagina 18 - 11-7.Outdoor fan control

25GGCheck of outdoor fan motorAbnormalNormalYesNoNoYesNoYesStartCheck the connection of connector (CN851) in the fan motor relay connector and outdoor

Pagina 19 - 12 TROUBLESHOOTING

26HHThe other casesIndoor unit dose not operate. (difference modes)• When you try to run two indoor unit simultaneously, one for cooling and the other

Pagina 20

27-20 -10 0 10 20 30 400102030405060708090100Temperature(:)Gas pipe temperature thermistor (RT65,66)Evaporation temperature thermistor (RT63)Temperatu

Pagina 21

28Noise filter P.C.boardMXZ-18TV-E1230V AC 50Hz InputOutdoor FanFan speed “Hi”230V ACOutdoor FanFan speed “Lo”230V AC230V AC 50Hz OutputReversing valv

Pagina 22 - Check of power supply

29DISASSEMBLY INSTRUCTIONS13OPERATING PROCEDUREPHOTOS1. Removing the top panel ~ back panel(1) Remove the screws fixing the top panel and remove it.(P

Pagina 23 - Check of R. V. coil

33INDOOR / OUTDOOR CORRESPONDENCE TABLE❈There is no combination other than this table.MXZ-18TV- E1OUTDOOR UNITCombination of the connectable indoor un

Pagina 24 - Check of inverter/ compressor

30OPERATING PROCEDUREPHOTOS5. Removing the 4-way coil(1) Remove the top panel, front cover and service panel.(2) Remove the inside and outside connect

Pagina 25 - Check of outdoor fan motor

31OPERATING PROCEDURE PHOTOS9. Remove the compressor(1) Remove the top panel, front cover, service panel.(2) Remove the inside and outside connection

Pagina 26 - The other cases

14-1. OUTDOOR UNIT FUNCTIONAL PARTSMXZ-18TV -MXZ-18TV -E2E1PARTS LIST321412345678910111213141516FIN TEMPERATURE THERMISTORDIODE STACKREACTORCONNECTOR

Pagina 27 - MXZ-18TV

3314-2. OUTDOOR UNIT STRUCTURAL PARTSMXZ-18TV -MXZ-18TV -E2E11234567891011121314151617181920FRONT PANEL ASSEMBLYGRILLE BASE ASSEMBLYCOMPRESSOREXPANSIO

Pagina 28 - Noise filter P.C.board

3415-1. Different-diameter pipeUnit : mm (inch)For different-diameterpipesMXZ-18TVMAC-454JPModel name51H-454Model codeConnected pipesdiameter (mm)Leng

Pagina 29 - DISASSEMBLY INSTRUCTIONS

OB280-2.qxp 02.12.19 11:18 AM Page 35

Pagina 30 - OPERATING PROCEDURE

HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPANCCCopyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD.Distri

Pagina 31 - OPERATING PROCEDURE PHOTOS

45SPECIFICATIONOutdoor modelIndoor units numberIndoor units total capacity (Connectable)indoor units total capacity (Simultaneous operation)Piping tot

Pagina 32 - PARTS LIST

5NOISE CRITERIA CURVES690807060504030201063 125 250 500 1000 2000 4000 8000APPROXIMATETERESHOLD OFHEARING FORCONTINUOUSNOISENC-60NC-50NC-40NC-30NC-20N

Pagina 33

6OUTLINES AND DIMENSIONS7MXZ-18TV -MXZ-18TV -E2E1Unit: mmOUTDOOR UNIT23166980050040045.440165347.5Air inAir outAir inDrainage hole {33Drainagehole {33

Pagina 34 - OPTIONAL PARTS

7WIRING DIAGRAM8R61IPMFUSE(1A)T801CT62WVUTAB61TAB65C65SSR61CN664 CN663 CN66166MF61CN912CN91121S4CN61R62TAB62VWUMCBLKWHTRED REDWHTBLKPEF911(1A)BLUORNYL

Pagina 35

8REFRIGERANT SYSTEM DIAGRAM9Unit:mmMXZ-18TV -MXZ-18TV -E2E1CompressorDischargetemperaturethermistorR.V. coilheating ONcooling OFFRefrigerant flow in c

Pagina 36

910The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,since operating cond