Mitsubishi Electric LMAP02-E Especificaciones

Busca en linea o descarga Especificaciones para Acondicionadores de aire del sistema de división Mitsubishi Electric LMAP02-E. Mitsubishi Electric LMAP02-E Specifications Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 106
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente

Indice de contenidos

Pagina 1 - Remote Controller

Lossnay Remote Controller

Pagina 2

C-10Reference: Remote controller for the Lossnay and indoor unitRefer to the technical documentation related to the Remote controller for the indoor u

Pagina 3 - 2. Applicable Models

C-10015.2 Remote Controllers for Mr. Slim indoor unitsMA remote controller (PAR-21MAA)Without Lossnay interlock and indicators.15.2.1 Method for opera

Pagina 4 - 3. Terminology

C-101 12346705 A B9ABCE8EDFG1120FEGCDIABH15.2.2 Function Selection

Pagina 5 - 4.1 Features

C-102[Procedure] (Set only when change is necessary.)Check the settings of each mode. When the mode settings were changed by function selection, the f

Pagina 6 - 4.2 System Examples

C-10315.3.1 Operating Lossnay with ME remote Controller(When Interlocked with City Multi Indoor Unit)Operation method is same as A-control remote cont

Pagina 7 - ( ) address

C-1044To register the interlocked operation of the Lossnay unit and the indoor unit.• Use the [TEST RUN] buttons (shown as D) to register the interloc

Pagina 8 - 4.3 System Selection

C-1059Press the “Timer/continuous” button (shown as E) again. The display will now alternate between the registered unit and theaddress of the next re

Pagina 10 - DELAY START

C-11FeatureOne remote controller can operate from one to 15 Lossnay units. PZ-60DR-E has many functions.suchas Extra-Low fan speed, however, PZ-41SLB

Pagina 11 - 4.4 Basic System

C-124.4.3 Operation with two Remote controllersSystem ExampleOperation MethodThe operation is the same with each remote controller. In this case, the

Pagina 12 - Remote controller

C-134.5 Interlocking with Mr. Slim4.5.1 Interlocked Mr. Slim and Lossnay SystemFeatures● It is possible to Interlock Mr. Slim indoor units with Lossna

Pagina 13 - Mr.Slim indoor unit

C-144.6 Combining with City Multi4.6.1 Independent Lossnay System with Lossnay M-NET RemoteController and MELANSFeatures● The Mitsubishi Electric air-

Pagina 14 - 4.6 Combining with City Multi

C-15System Examples: 2 (Lossnay M-NET Remote Controller PZ-52SF-E)The following groups can be configured.● Further information please refer LGH-RX4 Te

Pagina 15 - Caution:

C-16Lossnay Function Table (Group Setting)ItemNumber of Lossnay remote controllers and/or MELANSremote controllers that can be connected to one Lossna

Pagina 16

C-174.6.2 City Multi and Lossnay Interlocked SystemCharacteristics● It is possible to interlock City Multi indoor units with Lossnay operation.● Indep

Pagina 17 - System Examples

C-18Lossnay Function Table (Interlocked Settings)ItemNumber of indoor units that can be set to interlocked opera-tion with one Lossnay unit in each gr

Pagina 18

C-194.6.3 MA Remote Controller/ME Remote Controller in Combinationwith Lossnay Non-M-NET Remote Controller (PZ-60DR-E)SystemCombining MA, ME and Lossn

Pagina 20 - System Examples: 2

C-20System Examples: 2A sophisticated system including City Multi can also be configured.Note:● Hard wire connection from PZ-60DR-E is required indepe

Pagina 21 - Compatible Adaptor (LMAP02-E)

C-21OperationMonitoringContentsON/OFFSwitch fan to High/LowSwitch ventilation modeProhibit local ON/OFF operationOperation conditionFan speedVentilati

Pagina 22 - Input and Output Terminals

C-225.Examples of Applications Using VariousInput and Output TerminalsVarious applications are possible by using the input/output termi-nals and conne

Pagina 23

C-235.1 External Control Operating Mode SelectionThere are four modes when operating using signals from external equipment.1. ON/OFF interlock (the ch

Pagina 24

C-245.2 Delayed Interlocked Operation It is possible to delay operation of the Lossnay if an external device is operating. (Energy saving capability.)

Pagina 25 - Indoor Unit (M-NET only)

C-255.4 Multiple Lossnay Units Interlocked with OneIndoor Unit (M-NET only)[Example: System 1]Set the Main/Sub switch of the Lossnay connected to the

Pagina 26

C-265.8 Connection MethodLossnayM-NET transmission cableIndoor unitMA remote controllerOperation monitor output (TM4 )Electrically operated d

Pagina 27

C-27Connect the operating signal (wire) from the external devicevia the remote output to 1 and 3 on the external controlinput terminal block (TM2).Cau

Pagina 28 - 2 sensor or other equip

C-285.9 When switching High/Low/Extra-Low fan speedexternally (when CO2 sensor or other equip-ment is connected)Using marketed CO2 sensor, etc., make

Pagina 29 - 2 sensor

C-292 When using M-NET for a group of multiple units● Even if the units are in the same group, you can only change operation to High/Low for Lossnay u

Pagina 30 - (MELANS)

C-31. SummaryTechnical manual detailing the control and operation of commercial-type Lossnay units (LGH-RX5-E Series).Possible System Configurations(1

Pagina 31

C-30M-NET transmissioncableLossnayMA remotecontrollerIndoor unitof air conditionerIndoor unitof air conditionerPZ-60DR-E5.12 When connecting to the Ci

Pagina 32 - 6.3 Wiring Example

C-31Power supply unit PAC-SC50KUA6. Precautions When Designing M-NETSystems6.1M-NET Transmission Cable Power SupplyOn an M-NET system, the remote cont

Pagina 33

C-326.3 Wiring ExampleExample<Centralized remote controller and Lossnay units>Note:● Transmission booster cannot be used to extend the transmiss

Pagina 34 - 7. M-NET Cable Installation

C-336.4 Power Supply to the Indoor Unit TransmissionCableThe number of ME and Lossnay M-NET remote controllers that can be connected to one outdoor un

Pagina 35 - 7.2 Electrical Wiring

C-347. M-NET Cable Installation7.1 Precautions When Installing Wiring1. When routing the transmission cable outside of all units, position it 5 cm or

Pagina 36 - 7.3 Control Cable Length

C-357.2 Electrical WiringTypes of control cables1. Wiring the M-NET transmission cables•Types of transmission cablesTwo-core shielded cable (CVVS, CPE

Pagina 37 - 8. M-NET System Designs

C-367.3 Control Cable Length● Maximum power supply cable length (L1 + L2, L1 + L3, L1 + L4 + L5): the longest length of the cable from the power suppl

Pagina 38 - System configuration example

C-37UnitIndoor unit of air conditionerLossnay unitOutdoor unitBC controller(Main)BC controller(Sub)PZ-52SF-EM-NET, LOSSNAYRemote controller(Main)PZ-52

Pagina 39 - Precautions

C-38System configuration example(013)(015)(016)(010)(014)(005) (006) (007)(004)(003)(002)(001)(101)(105)(106)(107)(103)(051)(213)K-transmissionconvert

Pagina 40 - 9.2 Ventilation mode control

C-398.3Precautions When Performing Interlock Settings(when interlocked with City Multi indoor units)8.2Precautions When Setting the Groups (when notin

Pagina 41

C-43. Terminology● Interlocked LossnayA Lossnay linked to City Multi or Mr. Slim indoor units that has been set to interlocked group setting to receiv

Pagina 42

C-409. Automatic Ventilation Switching9.1 Effect of Automatic Ventilation ModeThe automatic damper mode provides the correct ventilation for the room

Pagina 43 - Bypass ventilation area

C-41Stand-alone/multi-ple Lossnay andLossnay remotecontroller: PZ-41SLB-EBasic SystemM- NET ControlFixed to automatic ventilation.Fixed to automatic v

Pagina 44 - 10. Troubleshooting

C-42When an outdoor temperature of 28ºC has notbeen detected within 24 hours0510152025303540051015 20 25 30 35 40Indoor temperature ºC24ºCLossnayVenti

Pagina 45 - 10.2 Checklist

C-43Pattern 2. Outdoor cooling priority modeWhen the outdoor temperature is lower than the indoor temperature, this mode actively takes in the outdoor

Pagina 46

C-4410. Troubleshootingn Work precautions• When removing or touching a transformer, printed circuit board or other parts, make sure to turn off the po

Pagina 47

C-4510.2 ChecklistIs the main power supply on?Checkpoint1No.2 Do the main power supply switching capacity and wiring diameter meetspecification?3 Is t

Pagina 48 - System checklist (Table 1-2)

C-46Do the transmission cables meet regulations? (Type, diameter)Checkpoint1No.2 Is the signal cable wired at least 5 cm away from the power supply ca

Pagina 49

C-47Do the signal cables meet regulations? (Type, diameter)Checkpoint1No.2Is the signal cable wired at least 5 cm away from the power supply cable?3 A

Pagina 50 - A , B

C-48« Check the power supply to theLossnay. (Refer to Table 1-1-1)« Set the Main/Sub (SW1) switchto “Main”.« Check the length of the trans-mission cab

Pagina 51 - A , B

C-49« Check the Interlock mode settingwith the remote controller (PZ-60DR-E). (Refer to page C-78)« Check the Interlock mode settingwith the remote co

Pagina 52 - 0.25S 0.25S 0.25S

C-5ClassificationControlFunctionInstallation MaintenanceItem• Multiple unit operation• Remote controller operation• External device operation and exte

Pagina 53

C-50«Check the power supply to Lossnayand perform the registration again.« Connect the transmission cableto TB5 A , B . « Check the transmission cabl

Pagina 54

C-51No.Error Cause Action« Check the power to Lossnay.« Check the address registrationof PZ-52SF-E with MELANS(“HO” displays for 3 to 10 min-utes when

Pagina 55

C-520.25S 0.25S 0.25S5SOFFONError display example: (Two blinks)Checklist of error codes displayed on the PZ-60DR-E (when not using M-NET) or PZ-41SLB-

Pagina 56

C-53LC 3602SLC 3602Error code3blinksLED1(green)—LED2(red)Damperrelatederror« Damper board operation is not cor-rect.« Connectors for the damper unit a

Pagina 57 - A , B for M

C-54Checklist of error codes displayed on PZ-60DR-E (when using M-NET), PZ-52SF-E or M-NET controllers, and LED displays(Table2-2)Error codeLED1(green

Pagina 58

C-55——— — Lit No M-NETconnectioninformation« The Lossnay units have not beenset to group setting (registration). « Check the Lossnay address andconfir

Pagina 59 - Lossnay checklist (Table 4)

C-56Checklist for PZ-60DR-E or PZ-41SLB-E (Table 3-1)1No.Nothing displays on theLCD.« Transmission cable is connected to the wrongterminal block.« No

Pagina 60

C-578 When the main powersupply is turned on, theremote controller displaywill indicate and Lossnaywill start.« When using PZ-60DR-E, “RECOVERY SET-TI

Pagina 61

C-58« After supplying power to the sys-tem, “HO” blinks for a maximumof about 10 minutes. (This is not an error.)«Perform the group setting (registra-

Pagina 62

C-59Lossnay checklist (Table 4)1No.The fan does not operate.The fan does not operatenormally.« Connectors for the fan or connectors for theLossnay cir

Pagina 63

C-6M-NET System4.2 System ExamplesOperating with an external device● Lossnay operation will be performed via the external device.● Level signal or pul

Pagina 64 - 11. Installation method

C-604 Lossnay operates whenthe main power is turnedon.« When using PZ-60DR-E, “RECOVERY SET-TING” is set to “on” or “AUTo” with the functionselection

Pagina 65 - 220-240V 50Hz

C-618 The damper board doesnot operate.« The outdoor air temperature is 8°C or lower.« The bypass ventilation switching external input(CN16) is set to

Pagina 66 - 11.3 System configuration

C-62No.1 Immediately after turning onthe main power, LED1 (green)on the Lossnay circuit boardblinks.LED1 blinks at 1 second intervals during starting

Pagina 67 - CAUTION:

C-63No.11 When PZ-60DR-E is used, thetimer operation does not work.Timer operation does not work in the following circumstances: • When the timer func

Pagina 68

C-64POWER SUPPLY220-240V 50Hz 21TB5(M-NET)(*1)Optional Remote controllerABS(PZ-60DR-E)*When the optional Remote Controller PZ-60DR-Ecable(non-polar)

Pagina 69 - First Lossnay

M1: Motor for exhaust fanM2: Motor for supply fanC: CapacitorGM: Motor for By-pass movementLS: MicroswitchTH1: Thermistor for outside airTH2: Thermist

Pagina 70 - 2 sensor or other

C-6611.2 Connecting the power supply cable1. Remove the screws and the control box coverLGH-15 to 100 RX5(1) Tighten the ground wire and transmission

Pagina 71 - Relay power supply

C-6721* When controlling Lossnay units with the central control, con-nect wires according to 10 (Refer to C-71).Securely connect the transmission cabl

Pagina 72 - 11.4 Function settings

C-68(1)Connect the interlocking cable connector side to CN2L onthe circuit board for the indoor Mr. Slim unit, then connect thelead wire side to the 1

Pagina 73 - 1. Settings for pulse input

(1) Move the pulse input switch [SW2-2] to the ONposition.(Refer to function settings 1 (Refer to C-73)“Settings for pulse input”.)(2) Connect the pul

Pagina 74 - 6. Setting for TM4 90 output

C-7Use Lossnay remote controller PZ-60DR-E .(Do not use PZ-41SLB-E).Lossnay transmission connection terminalTwo remote controller system with multipl

Pagina 75

C-70Connect the power supply cable from the Electrically operateddamper to 9 and 0 of the monitor output terminal block (TM4)with reference to the wir

Pagina 76 - 11.5 Trial operation

C-71SW1: When this is ON, Lossnay cannot turn ON/OFF by theRemoteController (PZ-60DR-E, PZ-52SF-E).SW2: When SW1 is ON, Lossnay can be turned ON by se

Pagina 77

C-72SA1 SA210 digit 1 digitAddress setting switch11.4 Function settingsAddress setting is requiered when connecting to City Multi, Lossnay remote cont

Pagina 78 - 12.1 Parts Names

C-73OFF ON Mode Operation6OFF Stop and start is performed according to SW5-4 settings SW2(factory setting) when the power is on.6ONOperation possible

Pagina 79 - Using the Remote Controller

C-749. Operation output monitorThis setting is available when SW2-8 is OFF.OFF ON OperationSW25. By-pass automatic ventilation priority settingTwo the

Pagina 80 - Using the Timer

C-7510.Exhaust fan stop during defrosting, exhaust fan Low speed operation at outdoor airlower than -15°CSets the operation of the exhaust fan (when t

Pagina 81

C-7614.Settings for interlock modeThese settings indicate how Lossnay should operate when external devices are started or stopped. (If the PZ-41SLB-E

Pagina 82 - Using the operation lock

C-7711.5.3 Complete system trial operation Interlock system containing an indoor unit and/or external device• Use the remote controller for the indoo

Pagina 83 - 12.5 Servicing

C-7812.Lossnay Remote Controller (PZ-60DR-E)12.1 Parts NamesDisplay SectionIdentifies the current operationShows the operating mode, etc. * Multilang

Pagina 84 - 12.6 How to Install

C-7912.2 Setting the Day of theWeek and Time Use this screen to change the current day of the week and time setting.Note:The day and time will not ap

Pagina 85 - 12.7 Test Run

C-84.3 System SelectionInterlocked with City Multi (Refer to page C-14)Lossnay operation when indoor unit is stopped ●●Lossnay stopping when indoor un

Pagina 86 - 12.8 Function Selection

C-80Ventilation mode DisplayAUTOHEAT EX.BY-PASSDisplay will change automatically depending on environmental circumstances. * If either “HEAT EX.” or “

Pagina 87

C-819. After making the appropriate settings at Steps 5, 6, 7. and 8, press the button 4 to lock in the values.* “TIMER SET” indicator flashes thre

Pagina 88 - Dot display

C-82Using the Night PurgeNight purge operation is used in the summer to automatically ventilate a room at night while the air conditioner is stopped,

Pagina 89

C-83Button Display SequenceCleaning of the Lossnay unit'sfilter*(i.e., resetting the total Lossnay-unit operating time)Clean the air filter, Pres

Pagina 90

C-8412.6 How to Install1. Choose a place in which to install the remote controller (switch box).Be sure to observe the following steps:(1) When inst

Pagina 91 - MIN. DELAYED

C-8512.7 Test Run6. Wiring hole for installing directly on the wall (or open wiring)• Cut off the shaded area from the upper cover using a knife, nip

Pagina 92 - (PZ-52SF-E)

C-8612.8 Function SelectionWhen the functions of the Lossnay unit were changed by function selection after installation, always indicate the set conte

Pagina 93 - 15. Appendix

C-87Dot displayThe language that is selected in CHANGE LANGUAGE mode appears on this display. English is set in this manual.[Function selection flowch

Pagina 94

C-88• If the remote controller Function Selection mode is entered during timer operation, the timer operation will be cancelled. Set timer operation a

Pagina 95

C-89[1] Change LanguageThe language that appears on the dot display can be selected.• Press the [ MENU] button to change the language.Japanese ( ) (ja

Pagina 96

C-9Central Con-troller Sys-temCentralized Controller SystemCentralized controllerAG-150APower supply unit(PAC-SC51KUA)Outdoor unitM-NET remotecontroll

Pagina 97

C-90[5] Installation settings (1) Supply fan speed setting (SW2-4,9)Set supply to Extra High/High fan speed notch selection or Low fixed (multi vent

Pagina 98

C-9113.Lossnay Remote Controller (PZ-41SLB-E)OperationVentilation Mode Selector ButtonUsed to select the ventilation mode from Energy recovery (Heat e

Pagina 99

C-9214. Lossnay M-NET Remote Controller (PZ-52SF-E)OperationCENTRALHEAT EX.BY-PASSAUTOCHECKINTERLOCKEDFILTERON/OFFNOTAVAILABLEFILTER[CENTRAL] DisplayD

Pagina 100 - Lossnay fan speed

C-9315. Appendix15.1 Centralized Controller (AG-150A)* For details on other function settings, refer to the manual for the AG-150A.

Pagina 105

C-985 3