Split-type Air-ConditionerMXZ-6C120VAEnglishInstallation Manual For INSTALLER• This manual only describes the installation of outdoor unit. When inst
En-1n Install an earth leakage breaker depending on the installation place. If an earth leakage breaker is not installed, it could cause electric sho
En-23. Obstacles in front (blowing) onlyWhen there is an obstacle in front of the unit as shown in the gure, open space above, behind, and on th
En-31-5. INSTALLATION DIAGRAMUnits should be installed by licensed contractor according to local code requirements.After the leak test, apply insulat-
En-4A B CD EPFA B CD EPFA B CEPFA B CPD E FA B CD D E FP2. OUTDOOR UNIT INSTALLATION2-1. INSTALLING THE UNITFix here with M10 bolts.Make the setting
En-54-1.PURGINGPROCEDURESANDLEAKTESTFig. 1 Fig. 2Fig. 3 Fig. 4Fig. 5 Fig. 63. FLARINGWORKANDPIPECONNECTION3-1.FLARINGWORKPipe diameter (mm
En-64-3.LOCKINGTHEOPERATIONMODEOFTHEAIRCONDITIONER(COOL,D RY,HEAT)4-4.LOWERINGTHEOPERATIONNOISEOFTHEOUTDOORUNIT4-2.GASCHARGEPerfo
En-74-6.TESTRUN• Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make