Vista de pagina 0
1
1 each
CENTRALIZED CONTROL(M-NET)
BG4H0
4
PAC-SF48MA-E
PUH-P1.63VGA, PUH-P14VGAA
MODELS
PUH-P1.66YGA, PUH-P1.66YGAA
PUH-P8, 10YE
1. Parts List
1 2
RG79B202H03
INSTALLATION MANUAL FOR A-M CONVERTER
This manual is written only for the models
PU(H)-P1.63VGA , PU(H)-P1.66YGA,
PU(H)-P14VGAA, PU(H)- P1.66YGAA,
and PUH-P8,10YE,
SAFETY PRECAUTIONS
After installation, make test operation and confirm that it works properly, and explain the safety precautions, operation method, and
maintenance to your customers.
Tell your customers to keep this installation manual together with operation manual with them, and when they give or sell this machine
to other person put this installation manual and operation manual with it.
Before starting installation, read the "Safety Precautions" described below.
The following precautions must be observed as it describes the serious matters for safety.
The safety precautions are described with the degree of danger.
WARNING
WARNING
CAUTION
When you handle wrong, it can lead to death or serious injury.
When you handle wrong, it can lead to injury or damage to building and furniture.
The installation must be done by dealer or qualified person.
If the customers do the installtion by themselves and it is not perfectly
installed it can cause water leak, electric shock, or fire.
If the installation is not perfectly done, it can cause water leak, electric
shock, or fire.
The installation must be done in accordance with this manual.
Never try any modification.
For repair, ask your dealer.
If the machine is modified or repaired unperfectly, it can cause water
leak, electric shock, or fire.
Never move or reinstall the machine by the customers.
If the installation is not perfectly done, it can cause water leak, electric
shock, or fire. Ask your dealer or qualified person.
Before electric wiring
CAUTION
The wiring must be securely done by using proper cable. The wires should
be connected to the terminals not to have external force of the cable.
Unperfect connections can cause heat or fire.
The termial cover (panel) of the unit must be installed securely.
Unperfect installation can cause fire or electric shock by dust or water.
The electric installation must be done by qualified person in accordance
with this installation manual. Use the separate circuit only for this machine
and use rated voltage and circuit breaker.
If the electric circuit power is not sufficient or the wiring is not properly
done, it can cause electric shock or fire.
Without a circuit breaker, it can cause electric shock.
Install a circuit breaker depending upon the location.
Use standard wires which meet current capacity.
Otherwise, it can cause short-circuit, heat, or fire.
Wires must not have tension.
It can cause snipping, heat, or fire.
Put ground wire.
Never ground to gas pipe, water pipe, lightning conductor, or
telephone ground wire.
Unperfrect ground can cause short-circuit.
Use proper fuses
If you use larger size fuses or neelde wire, it can cause failure or fire.
Before test operatoin
Turn the power on 12 hours or more before operation.
If you start operation as soon as the power on, it can cause failure.
Never turn the power off during season.
Never operate the machine without panel or guard off.
It can cause serious injury being caught by rotating part or burn or
electric shock by high voltage part.
Never operate the machine without air filter off.
It can cause failure by dust.
Never operate the switches with your hand wet.
It can cause electric shock.
Never touch refrigerant pipes while the machine running.
The refrigerant pipes becomes high and low temperature while the
machine running. If you touch the pipes by hand, it can cause chilblain
or burn.
Never turn the power off as soon as the machine stops.
Wait for 5 minutes or more. It can cause water leak or failure.
CAUTION
Description Figure Q'ty Note
M-NET board
Take measures forstatic when
handling the board.
Otherwise,the part can be broken.
Support
Insert it to electric box from
arrow side.
Terminal base
Screw (M4×10)
Terminal bed (M-NET)
Terminal screw (M3x20)
Label
Lead wire (5 wires)
Lead wire (3 wires)
Lead wire (2 wires)
Ground wire and screw
(M4×10)
Pull tight
Vista de pagina 0
1 2 3 4 5

Indice de contenidos

Pagina 1 - SAFETY PRECAUTIONS

⑨ 1 ⑩ ⑪ ⑫ 1 1 1 11 each⑦ ⑧ 1 CENTRALIZED CONTROL(M-NET)A B S BG79H744H02 ① 1 № ② 4③ 1 ④ ⑤ 1 ⑥ 1 PAC-SF48MA-EPU(H)-P1.6∼3VGA, PU(H)-P1∼4VGAAMODELSPU(

Pagina 2 - SW1−1 OFF

2SW12 SW11ABSPosition holeHole for M-NET groundCENTRALIZED CONTROL(M-NET)A B S A B S CN 5CN 2 M CN M N TCN V M N TCND 1M-NET address No.2 50Swit

Pagina 3 - RG79B202H04

1M-NET address No.2 50Switch set〈Setting example〉 0123456789012345678901234567890123456789012345678901234567895 62. Installation procedure (PUH-P8, 1

Pagina 4 - (    )

Wiring method for M-NET (1) Attention ① Outside of the unit, the wires for transmission (called for transmit wires later) should keep away (5 cm or m

Pagina 5

9 Centralized controll remote controlCentralized controll remote controlCentralized controll remote controlOutdoor unit corresponds to M-NETO

Comentarios a estos manuales

Sin comentarios