CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 6
5. OUTLINES AND DIMENSIONS ························ 7
6. WIRING DIAGRAM ············································ 7
7. REFRIGERANT SYSTEM DIAGRAM ··············· 8
8. SERVICE FUNCTIONS ····································· 9
9. MICROPROCESSOR CONTROL ····················11
10. TROUBLESHOOTING ······································20
11. DISASSEMBLY INSTRUCTIONS ·····················36
SPLIT-TYPE AIR CONDITIONERS
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
Outdoor unit service manual
MUZ-FD·VA(H) Series (OBH489)
MUZ-FD·VABH Series (OBH519)
MXZ-A·VA Series (OB377)
MXZ-8A140A (OC316)
SERVICE MANUAL
Models
No. OBH488
REVISED EDITION-C
INDOOR UNIT
PARTS CATALOG (OBB488)
Revision C:
MSZ-FD•VA(S)-
E2
has been added.
Please void OBH488 REVISED EDITION-B.
MSZ-FD25VA -
E1
,
E2
MSZ-FD25VAS -
E1
,
E2
MSZ-FD35VA -
E1
,
E2
MSZ-FD35VAS -
E1
,
E2
MSZ-FD50VA -
E1
,
E2
MSZ-FD50VAS -
E1
,
E2
Downloaded from AC-Manual.com Manuals
Vista de pagina 0
1 2 3 4 5 6 ... 39 40

Indice de contenidos

Pagina 1 - INDOOR UNIT

CONTENTS1. TECHNICAL CHANGES ··································· 32. PART NAMES AND FUNCTIONS ····················· 43. SPECIFICATION ················

Pagina 2 - Revision C:

10NOTE:• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller.• If main powe

Pagina 3 - TECHNICAL CHANGES

11ON TIMER buttonCLOCK SET buttonTIME SET buttonsFORWARD buttonBACKWARD buttonOFF TIMER buttonRESET buttonVANE CONTROL buttonWIDE VANE button(Vertical

Pagina 4 - PART NAMES AND FUNCTIONS

129-1. COOL ( ) OPERATION(1) Press OPERATE/STOP (ON/OFF) button. POWER lamp of the indoor unit turns on with a beep tone.(2) Select COOL mode with OP

Pagina 5 - SPECIFICATION

139-5. AUTO VANE OPERATION1. Horizontal vane(1) Vane motor driveThese models are equipped with a stepping motor for the horizontal vane. The rotating

Pagina 6 - NOISE CRITERIA CURVES

14(7) SWING ( ) modeBy selecting SWING mode with VANE CONTROL button, the horizontal vane swings vertically. (8) Cold air prevention in HEAT operation

Pagina 7 - WIRING DIAGRAM

159-6. i-see CONTROL OPERATIONThe sensors constantly measure the room and floor/wall temperatures to automatically adjust to the set temperature by es

Pagina 8 - REFRIGERANT SYSTEM DIAGRAM

16Indoor unit installation location and air-conditioning area•Be sure to set the slide switch inside the remote controller to an appropriate position

Pagina 9 - SERVICE FUNCTIONS

17Operation and operating rangei-see sensor moves 30 degrees from the center in both right and left side.i-see Sensor operates as follows in accordanc

Pagina 10 - 8-4. REMOTE CONTROLLER

189-10. TIMER OPERATION1. How to set the time(1) Check that the current time is set correctly.NOTE: Timer operation will not work without setting the

Pagina 11 - MICROPROCESSOR CONTROL

19EMERGENCY OPERATION switch (E.O.SW)9-11. EMERGENCY/TEST OPERATIONIn case of test run operation or emergency operation, use EMERGENCY OPERATION switc

Pagina 12

2Revision A:• 3. SPECIFICATION has been corrected.• 10-5. TROUBLE CRITERION OF MAIN PARTS has been corrected.Revision B:• MSZ-FD50VA(S)- E1 has been a

Pagina 13 - 9-5. AUTO VANE OPERATION

20Insert the negative pole of the batteries first. Check if the polarity of the batteries is correct.NOTE: 1. If RESET button is not pressed, the remo

Pagina 14 - Horizontal

21Outline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though LED indication listed on the tro

Pagina 15 - for a long period

222. Flow chart of PLASMA operation failure mode recall function2. Blinking pattern when plasma unit is abnormal:ONOFFBeepsRepeated cycle Repeated cyc

Pagina 16 - Not lighted

235. PLASMA operation failure mode tablePOWER lamp Abnormal point(Failure mode)Condition Correspondence1-time fl ash PLASMA power supply control PLASMA

Pagina 17 - 9-8. PLASMA ( ) OPERATION

2410-3. INSTRUCTION OF TROUBLESHOOTINGIndoor unit oper-ates.Outdoor unit does not operate.If blinking of OPERATION INDI-CATOR lamp cannot be checked,

Pagina 18 - START

2510-4. TROUBLESHOOTING CHECK TABLEBefore taking measures, make sure that the symptom reappears for accurate troubleshooting.When the indoor unit has

Pagina 19

26 L AREA R POWER CLEAN PLASMA No. Abnormal pointOperation indicator lamp Symptom Condition Correspondence1Attachment of the hori-zontal va

Pagina 20 - TROUBLESHOOTING

2710-5. TROUBLE CRITERION OF MAIN PARTSMSZ-FD25VA MSZ-FD25VAS MSZ-FD35VA MSZ-FD35VAS MSZ-FD50VA MSZ-FD50VASPart name Check method and criterion

Pagina 21

28 A Check of indoor fan motor10-6. TROUBLESHOOTING FLOWThe indoor fan motor error has occurred, and the indoor fan does not operate.Turn OFF the pow

Pagina 22

29 B Check of remote controller and indoor electronic control P.C. board Check if the remote controller is exclusive for this air conditioner.Does th

Pagina 23

3MSZ-FD25VA - E1 MSZ-FD25VAS - E1MSZ-FD35VA - E1 MSZ-FD35VAS - E1MSZ-FD50VA - E1 MSZ-FD50VAS - E1 1. New modelTECHNICAL CHANGES1MSZ-FD25VA(S) - E1

Pagina 24

30 C Check of indoor electronic control P.C. board and indoor fan motorTurn OFF the power supply.Remove indoor fan motor connector CN211, vane motor

Pagina 25 - Blinking

31 D How to check miswiring and serial signal errorTurn OFF the power supply.Is there rated voltage in the power supply?YesNoTurn ON the power supply

Pagina 26

32 E Check of installation of the horizontal vane F Check of PLASMA operationIs the stopper of the horizontal vane locked to the indoor unit correct

Pagina 27

33 G Electromagnetic noise enters into TV sets or radiosYesIs the unit earthed?NoEarth the unit.YesIs the distance between the antennas and the indoo

Pagina 28 - A Check of indoor fan motor

3410-7. TEST POINT DIAGRAM AND VOLTAGEMSZ-FD25VA MSZ-FD25VAS MSZ-FD35VA MSZ-FD35VAS MSZ-FD50VA MSZ-FD50VAS1. Indoor electronic control P.C. board

Pagina 29

352. Power monitor receiver P.C. boardDC 2.5 V during PLASMA DEODORIZING operationDC 12.5 V during PLASMA DEODORIZING operationGNDCN14. Plasma power P

Pagina 30

36MSZ-FD25VA MSZ-FD25VAS MSZ-FD35VA MSZ-FD35VAS MSZ-FD50VA MSZ-FD50VASNOTE: Turn OFF power supply before disassembling.OPERATING PROCEDURE PHOTOS

Pagina 31

37OPERATING PROCEDURE PHOTOS2. Removing the electronic control P.C. board, the power monitor receiver P.C. board, i-see Sensor, SW P.C. board and the

Pagina 32 - F Check of PLASMA operation

38OPERATING PROCEDURE PHOTOS3. Removing the electrical box(1) Remove the panel (refer to 1.) and the corner box.(2) Remove the indoor/outdoor connecti

Pagina 33

39OPERATING PROCEDURE PHOTOS6. Removing the horizontal vane motor(1) Remove the nozzle assembly. (Refer to 4.)(2) Remove the screws of the horizontal

Pagina 34 - Interlock switch(Fan)

4ACCESSORIESInstallation plate 1Installation plate fi xing screw 4 × 25 mm 5Remote controller holder 1Fixing screw for 3.5 × 1.6 mm (Black) 2Battery

Pagina 35 - 3. Monitor P.C. board

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN© Copyright 2007 MITSUBISHI ELECTRIC CO.,LTDDistributed in Dec. 2008. No

Pagina 36 - DISASSEMBLY INSTRUCTIONS

5Indoor modelMSZ-FD25VAMSZ-FD25VASMSZ-FD35VAMSZ-FD35VASMSZ-FD50VAMSZ-FD50VASPower supplySingle phase 230 V, 50 HzElectrical dataPower input 1Cooling

Pagina 37 - OPERATING PROCEDURE PHOTOS

6MSZ-FD25VA MSZ-FD25VASINDOOR UNITWALLMICROPHONE0.8 m1 m90807060504030201063 125 250 500 1000 2000 4000 8000NC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND

Pagina 38

7225 225646415515534554330 6942211.53253231.541212.52544369743859729521.55655 556881007857986.547Wall hole ø6511 X 26 Oblong hole11 X 20 Oblong holeIn

Pagina 39

8MSZ-FD25VA MSZ-FD25VAS MSZ-FD35VA MSZ-FD35VASIndoorheatexchangerFlared connectionRoom temperaturethermistorRT11Flared connectionRefrigerant pipe ø

Pagina 40

98-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board. The time will be