SERVICE MANUAL
No.OCH467
REVISED EDITION-A
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
CONTENTS
1.
COMBINATION OF INDOOR AND OUTDOOR UNITS
...
2
2. PART NAMES AND FUNCTIONS
......................
2
3. SPECIFICATION
.................................................
3
4. OUTLINES AND DIMENSIONS
..........................
4
5. WIRING DIAGRAM
............................................
5
6. REFRIGERANT SYSTEM DIAGRAM
................
8
7. DATA
.................................................................
11
8. ACTUATOR CONTROL
....................................
13
9. SERVICE FUNCTION
.......................................
14
10. TROUBLESHOOTING
......................................
14
11. FUNCTION SETTING
.......................................
30
12. DISASSEMBLY INSTRUCTIONS
.....................
33
HFC
utilized
R410A
July 2011
R410A
Outdoor unit
[Model names] [Service Ref.]
SUZ-KA09NA SUZ-KA09NA.TH
SUZ-KA12NA SUZ-KA12NA.TH
SUZ-KA15NA SUZ-KA15NA.TH
SUZ-KA18NA SUZ-KA18NA.TH
Note:
This service manual describes serv-
ice data of the outdoor units.
RoHS compliant products have
<G> mark on the spec name plate.
PARTS CATALOG (OCB467)
SUZ-KA18NA.TH
Revision:
SLZ-KA·NA models have been
added as connectable indoor units.
Some descriptions have been mod-
ified.
Please void OCH467.
Vista de pagina 0
1 2 3 4 5 6 ... 39 40

Indice de contenidos

Pagina 1 - SERVICE MANUAL

SERVICE MANUALNo.OCH467REVISED EDITION-ASPLIT-TYPE, HEAT PUMP AIR CONDITIONERSCONTENTS1. COMBINATION OF INDOOR AND OUTDOOR UNITS... 22. PART NAMES AND

Pagina 2 - PART NAMES AND FUNCTIONS

10 11ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation

Pagina 3 - SPECIFICATION

10 117 DATASTANDARD OPERATION DATARepresentative matching SEZ-KD09NA4 SEZ-KD12NA4 SEZ-KD15NA4 SEZ-KD18NA4Item Unit Cooling Heating Cooling Heating Coo

Pagina 4 - OUTLINES AND DIMENSIONS

12 13Representative matching SLZ-KA09NA SLZ-KA12NA SLZ-KA15NAItem Unit Cooling Heating Cooling Heating Cooling HeatingTotalCapacity Btu/h 8400 10900 1

Pagina 5 - WIRING DIAGRAM

12 13SUZ-KA09NA SUZ-KA12NA SUZ-KA15NA SUZ-KA18NA8-2. R.V. COIL CONTROL Heating . . . . . . . . . . . . . . . . .ON Cooling . . . . . . . . . . . .

Pagina 6 - SUZ-KA15NA

14 159-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> To change the defrost finish temperature, cut/solder the JS wire

Pagina 7

14 1510-2. FAILURE MODE RECALL FUNCTIONAs this air conditioner has a function to memorize all the failures that had happened, the latest failure detai

Pagina 8 - REFRIGERANT SYSTEM DIAGRAM

161710-2-3. Outdoor unit failure mode tableAbnormal point (Failure mode / protection) LED indication (Outdoor P.C. board) Condition Remedy Indoor/ou

Pagina 9

161710-3. TROUBLESHOOTING CHECK TABLENo. Symptom LED indication Abnormal point/ Condition Condition Remedy1Outdoor unit does not oper-ate. 1-time 

Pagina 10

181910-4. TROUBLE CRITERION OF MAIN PARTSSUZ-KA09NA SUZ-KA12NA SUZ-KA15NA SUZ-KA18NAPart name Check method and criterion FigureDefrost thermistor

Pagina 11 - STANDARD OPERATION DATA

181910-5. TROUBLESHOOTING FLOWAre the voltages balanced?Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).Repl

Pagina 12

23Air outletDrain outletPipingDrain hoseAir inlet(back and side)1COMBINATION OF INDOOR AND OUTDOOR UNITSOUTDOOR UNITPipingAir outletDrain hoseDrain ou

Pagina 13 - ACTUATOR CONTROL

2021 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time● Disconnect the connector (CN61) betw

Pagina 14 - SERVICE FUNCTIONS

2021Is the resistance of thermistor normal? (Refer to 10-6.1.)Reconnect the connector of thermistor.Turn ON the power supply and press the TEST button

Pagina 15 - OPERATION

2223 I Check of outdoor fan motorIs the resistance of outdoor fan motor normal?(Refer to 10-4.)Replace the outdoor fan motor.Replace the inverter P.C

Pagina 16

2223 J Check of power supplyIs there voltage 208/230 VAC between the indoor terminal block S1 and S2?NoYesReplace the indoor electronic control P.C.

Pagina 17

2425K Check of LEV (Expansion valve)Replace the inverter P.C.board.NoSelf-check (Refer to 10-2-1.) start.Expansion valve operates in full-opening dir

Pagina 18

2425 L Check of inverter P.C. boardCheck the outdoor fan motor. (Refer to 10-5. .)Is the fuse (F901) blown on the inverter P.C. board?Check the conne

Pagina 19 - C Check of compressor

2627 M How to check miswiring and serial signal errorTurn OFF inverter-controlled lighting equipment.Turn OFF the power supply and then turn ON again

Pagina 20

2627 N Electromagnetic noise enters into TV sets or radiosYesIs the unit grounded?NoGround the unit.YesIs the distance between the antennas and the i

Pagina 21 - H Check of R.V. coil

2829-4 14 32 50 68 86 1040102030405060708090100Temperature(°F)Defrost thermistor(RT61) Ambient temperature thermistor(RT65)Outdoor heat exchanger temp

Pagina 22 - SUZ-KA18NA

2829-4 14 32 50 68 86 1040102030405060708090100Temperature(°F)Defrost thermistor(RT61) Ambient temperature thermistor(RT65)Outdoor heat exchanger temp

Pagina 23 - J Check of power supply

23Outdoor unit model SUZ-KA09NA SUZ-KA12NA SUZ-KA15NA SUZ-KA15NAPower supply V , phase , Hz 208/230 , 1 , 60Max. fuse size (time delay) A 15Min. circ

Pagina 24

30 3111FUNCTION SETTING11-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER (S series only)Each function can be set according to necessity using the r

Pagina 25

30 31 Select mode No. 02 (room temperature detection position). Select setting No. 03 (remote controller fixed). (Use  and .) Enter the s

Pagina 26

32 33Turn off the remote controller.Hold down 2 buttons simultaneously for 2 seconds: the and  buttons to set the modes 01 through 1

Pagina 27

SUZ-KA09NA SUZ-KA12NA SUZ-KA15NA NOTE: Turn OFF power supply before disassembling.OPERATING PROCEDURE PHOTOS1. Removing the cabinet(1) Remove the sc

Pagina 28 - 1. Inverter P.C. board

3435OPERATING PROCEDUREPHOTOS2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and panels. (Refer to procedure 1.)(2) Disco

Pagina 29

3435OPERATING PROCEDUREPHOTOS5. Removing outdoor fan motor(1) Remove the cabinet and panels. (Refer to procedure 1.)(2) Disconnect the following conne

Pagina 30 - (RF thermostat)

11-2. SUZ-KA18NANOTE: Turn OFF power supply before disassembling.OPERATING PROCEDUREPHOTOS1. Removing the cabinet(1) Remove the screws of the service

Pagina 31 - Mode number

OPERATING PROCEDUREPHOTOS2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and panels. (Refer to procedure 1.)(2) Disconnec

Pagina 32 - [Operating Procedure]

3839OPERATING PROCEDURE PHOTOS4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera-ture thermistor and

Pagina 34 - OPERATING PROCEDURE

45Unit: inchSUZ-KA09NA SUZ-KA12NA SUZ-KA15NA Liquid pipe :1/4 (flared)Gas pipe :3/8 (flared) (KA09/12) 1/2 (flared) (KA15)6-23/3225-7/82-23/321-3/

Pagina 35

HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANCCopyright 2010 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.Distributed in

Pagina 36 - 11-2. SUZ-KA18NA

45SUZ-KA09NA SUZ-KA12NA5WIRING DIAGRAMSUZ-KA09NA, SUZ-KA12NA WIRING DIAGRAMLEDLEDH26HIC802IPM,IC932L61DB61,DB65C62,C63SYMBOLNAME SYMBOL SYMBOLNAME NA

Pagina 37

67SUZ-KA15NASUZ-KA15NA WIRING DIAGRAMRT68TB1,TB2TR821T80121S4X63,X64,X6626HF701,F801,F901MFRT61RT62MCPTC64,PTC65RT64LEVC61,C62,C63SYMBOL SYMBOL SYMBOL

Pagina 38 - OPERATING PROCEDURE PHOTOS

67SUZ-KA18NART68TR821TB1,TB2X63,X64,X6621S4T801HEATER PROTECTOR(OPTION PARTS)26HDB61,DB65C61,C62,C63SYMBOL NAME SYMBOL NAME SYMBOL NAMEDEFROST HEATER(

Pagina 39

8 9Unit: inch (mm)SUZ-KA09NAOutdoorheatexchangerFlared connectionDefrostthermistorRT61DischargetemperaturethermistorRT62Flared connectionStop valve(wi

Pagina 40

8 9SUZ-KA18NAOutdoorheatexchangerFlared connectionDefrostthermistorRT61DischargetemperaturethermistorRT62Flared connectionStop valve(with strainar)Sto