Mitsubishi Electric CITY MULTI PQRY-P200YMF-B Especificaciones

Busca en linea o descarga Especificaciones para Acondicionadores de aire del sistema de división Mitsubishi Electric CITY MULTI PQRY-P200YMF-B. Mitsubishi Electric CITY MULTI PQRY-P200YMF-B Specifications Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 154
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente

Indice de contenidos

Pagina 1 - Service Handbook

AIR CONDITIONERS CITY MULTIModels PQRY-P200YMF-B, P250YMF-BCMB-P104, P105, P106, P108, P1010, P1013, P1016V-EService Handbook

Pagina 2 - Contents

–7–[7] Charging of RefrigerantR407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.For a cylinder with a syphon a

Pagina 3 - Safety precautions

–97–Note 1 :• Board connector CN10 corresponds to TH11 through TH12, while connectorCN11 corresponds to TH15 through TH16. Remove the applicable conne

Pagina 4

–98–3) LEV, solenoid valve troubleshooting flowNo coolingNo heatingCheck disconnection or loosenessof connectors.Is there a problem?Operate in cooling

Pagina 5

–99–1 LEVNote 1 :• Symptoms of incorrect connection to BC controller LEV boardImproper installation is the same for 1 and 2, so it is omitted here.Not

Pagina 6 - [2] Piping Machining

–100–665432154321251346BrownRedBlueOrangeYellowWhiteBrownRedBlueOrangeYellowWhiteToLEV10kΩ LED(Self-diagnostic monitor)Measured data Signal Heat sourc

Pagina 7

–101–2 Solenoid ValveChange thesolenoid valve.Change the controlboard.220-240V output?With the solenoid valve con-nector is disconnected from theboard

Pagina 8 - [4] Brazing

–102–1BASolenoid valves (SVA, SVB, SVC, SVM)Coordination signals output from the board and solenoid valve operations.Note 1 : (SVA, SVB, SVC)SVA, SVB

Pagina 9 - [6] Vacuuming

–103–[2] BC Controller Disassembly Procedure(1) Service panelBe careful on removing heavy parts.Procedure Photos & Illustrations1. Remove the two

Pagina 10 - [8] Dryer

–104–(2) Control boxBe careful on removing heavy parts.Procedure Photos<CMB-P104, 105, 106V-E>1. Removing the single screw that secures the elec

Pagina 11 - 2 COMPONENT OF EQUIPMENT

–105–(3) Thermistor (Liquid and gas piping temperature detection)Be careful when removing heavy parts.Procedure Photos1. Remove the service panel1 Use

Pagina 12 - Inner View

–106–(5) LEVBe careful on removing heavy parts.Procedure Photos1. Remove the service panel. See (1)-1.2.3.4.2. Replace the applicable LEV.Important!1

Pagina 13 - MAIN board

–8–22222 COMPONENT OF EQUIPMENT[1] Appearance of ComponentsHeat source unitHeatexchangerControl BoxCVBlockDrierAccumulatorCompressorSVBlock4-wayValve

Pagina 14 - INV board

–107–Check code listCheck code Check content0403 Serial transmission abnormality0900 Trial operation1102 Discharge temperature abnormality1111 Low pre

Pagina 15 - RELAY board

–108–Check code Check content6606 Communications with transmission processor abnormality6607 No ACK abnormality6608 No response abnormality7100 Total

Pagina 16 - BC board

–109–Checking code Meaning, detecting method Cause Checking method & CountermeasureSerialtransmissionabnormality0403If serial transmission cannot

Pagina 17 - RELAY 4 board

–110–Checking code Meaning, detecting method Cause Checking method & CountermeasureDischargetemperatureabnormality(Heat sourceunit)11021. When 140

Pagina 18

–111–Checking code Meaning, detecting method Cause Checking method & CountermeasureLowpressuresaturationtempera-turesensorabnormal-ity (TH2)Liquid

Pagina 19 - BC controller, Indoor unit

–112–Checking code Meaning, detecting method Cause Checking method & Countermeasure13011302Low pressureabnoramlityHigh pressureabnoramlity 1(Heat

Pagina 20 - [3] Equipment Composition

–113–1302150015011) Fall in internal press. caused bygas leak.2) Press. sensor trouble.3) Film breakage.4) Coming off of pin in connector por-tion, po

Pagina 21 - [4] Electrical Wiring Diagram

–114–Checking code Meaning, detecting method Cause Checking method & Countermeasure150520002134SuctionpressureabnormalityInterlockoperationAbnorma

Pagina 22 - <Symbol explanation>

–115–Checking code Meaning, detecting method Cause Checking method & Countermeasure21352500250225033152Freezing ofthe water heatexchanger.Leakage

Pagina 23 - • CMB-P104V-E

–116–Checking code Meaning, detecting method Cause Checking method & Countermeasure41034115Reverse phaseabnormalityPower supplysync signalabnoraml

Pagina 24 - • CMB-P105V-E

–9–Control BoxINV boardRELAYboardTransformer(T01)MAINboardTerminal block TB7Transmission (Centralized Control)Terminal block TB8UNIT ON/OFF,Pump inte

Pagina 25

–117–Checking code Meaning, detecting method Cause Checking method & Countermeasure41164200Fan speedabnormality(motorabnoramlity)VDC·IDCsensor/cir

Pagina 26

–118–Checking code Meaning, detecting method Cause Checking method & Countermeasure42104220Breaking ofovercurrentBus voltageabnormality1. If IDC

Pagina 27

–119–Checking code Meaning, detecting method Cause Checking method & Countermeasure42304240Radiator paneloverheatprotectionOvercurrentprotectionIf

Pagina 28 - • CMB-P1013V-E

–120–Discharge(TH1)Lowpressuresaturation(TH2)Accumulaterliquid level(TH3)Accumulaterliquid level(TH4)Watertempera-ture (TH6)(THINV)CS circuit(TH9)Radi

Pagina 29 - • CMB-P1016V-E

–121–See Troubleshooting of pressuresensor.Check the contacts of CNCT on theINV board.Check the DCCT polarity.• With SW1-1 OFF, is the inverter’soutpu

Pagina 30 - [5] Standard Operation Data

–122–(2) Communication/systemCheckingcode66006602Multiple address errorTransmission from units with thesame address is detected.Note:The address/attri

Pagina 31

–123–Transmission processor hardwareerrorTransmission circuit bus-busy er-ror1. Collision of data transmission:Transmission can not be per-formed for

Pagina 32 - (1) Heat source unit

–124–Checkingcode6606Meaning, detecting method Cause Checking method & Countermeasure1) Data is not properly transmitted dueto casual errouneous o

Pagina 33 - Cooling capacity saving

–125–Checkingcode6607Meaning, detecting methodNo ACK error When no ACK signal is detected in 6 continuous times with 30 second interval bytransmissio

Pagina 34

–126–Checkingcode6607(continued)Meaning, detecting methodSystemcompo-sitionGeneratingunit addressDisplay oftroubleDetectingmethodCause Checking method

Pagina 35

–10–MAIN boardCNTR CNVCC4 CNS1 CNS2 CN40 CN41CNVCC3CN51CN3DLD1Service LEDSW1SW2SWU1SWU2SW3SW4CN20Power sourcefor control (5V)Power sourcefor control1-

Pagina 36 - 3 TEST RUN

–127–Checkingcode6607(continued)Meaning, detecting methodSystemcompo-sitionGeneratingunit addressDisplay oftroubleDetectingmethodCause Checking method

Pagina 37 - Insulation pipe

–128–Checkingcode6607(continued)Meaning, detecting methodSystemcompo-sitionGeneratingunit addressDisplay oftroubleDetectingmethodCause Checking method

Pagina 38

–129–1) Total capacity of indoor units in thesame refrigerant system exceedsthe following:2) Erroneous setting of OC model se-lector switch (SW3-10).1

Pagina 39

–130–Checkingcode71027105710771117130Meaning, detecting method Cause Checking method & CountermeasureConnected unit count overAddress setting erro

Pagina 40

–131–[4] LED Monitor Display(1) How to read LED for service monitorBy setting of DIP SW1-1 ~ 1-8, the unit operating condition can be observed with th

Pagina 41 - Rotary switch

–132–E: E2 Contents stored in the E2PROM; M: Monitored by the IC through communications; E*: Stored in service memory.No SW1 Item Display Remarks12345

Pagina 42

–133–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8212223242526272829303132333435363738394041424344454647484950511010100000011

Pagina 43

–134–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8525354555657585960616263646566676869707172737475767778798081820010110000101

Pagina 44

–135–When there is an error stop with No95-121,the data on error stops or the data immediately before the error postpone-ment stop, which is stored in

Pagina 45

–136–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8112113114115116117118119120121122123124125126127128129130131132133134135136

Pagina 46 - [3] Test Run Method

–11–INV boardCN3 CN2-1 CN2-2 CN2-3CNVDCCN52CCNFANCNAC2CNR CNRS2 SW1CNCTCN30VCNTHCNL2CNVCC1CNVCC2Power source1 L23 NPower supply (5V)Power supply1-2 30

Pagina 47 - (1) Switch function

–137–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8140141142143144145146147148149150151152153154155156157158159160161162163164

Pagina 48

–138–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8166167168169170171172173174175176177178179180181182183184185186187188189190

Pagina 49 - Group setting mode

–139–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8200201202203204205206207208209210211212213214215216217218219220221222223224

Pagina 50 - CENTRALLY CONTROLLED

–140–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8229230231232233234235236237238239240241242243244245246247248249250251252253

Pagina 51 - (Alternative

–141–88888 PREPARATION, REPAIRS AND REFRIGERANT REFILLING WHEN REPAIRINGLEAKS[1] Location of leaks: Extension piping or indoor units (when cooling)1 A

Pagina 52

–142–[3] Location of Leaks: Extension Piping or Indoor Units (Heating mode)1 Test run all indoor units in heating mode.1. With SW3-1 on the MAIN board

Pagina 53 - 5 CONTROL

–143–99999 CHECK THE COMPOSITION OF THE REFRIGERANTYESYESYESYESYESNONONONONOStartTest run all indoor units.Is the refrigerantcomposition of αOCcorrect

Pagina 54

–144–Note 1 Wait until the units stabilize as described in the refrigerant amount adjustment procedure in “Chapter 6”.Note 2 After the units are opera

Pagina 55

–145–00000 DIFFERENCES BETWEEN THE PREVIOUS REFRIGERANT AND THE NEW RE-FRIGERANT[1] Chemical CharacteristicsThe new refrigerant (R407C) is a chemicall

Pagina 56

–146–[3] Pressure CharacteristicsCompared to the previous refrigerant (R22), the pressure of the new refrigerant (R407C) is higher.Pressure (Gauge) R4

Pagina 57

–12–RELAY board

Pagina 58 - [3] Control of BC Controller

–147–Contaminants is a general term for moisture, air, process oil, dirt, other refrigerants and other refrigerator oils, etc.CauseMixing with moistur

Pagina 62 - 3-minute

Service Handbook PQRY-P200YMF-B, P250YMF-BCMB-P104, P105, P106, P108, P1010, P1013, P1016V-EHEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI TOKYO 100-00

Pagina 63

–13–BC controllerCNTRCN02M-NETtransmissionCN03CN12Powersupply1 EARTH3 N5 LSW4 SW2 SW1BC board

Pagina 64 - Thermostat ON

–14–RELAY 10 boardRELAY 4 board

Pagina 65

–15–[2] Refrigerant Circuit Diagram and Thermal Sensor : Solenoid valve : Orifice : Capillary : Check valv

Pagina 66

–16–Valves BlockTH23TH21TH22LEVSVCSVASVBIndoorunits BC controllerCMB-P104V-EGas/liquid separatorPS1LEV1SVMPS3LEV3TH12TH11TH15TH16 : Solenoi

Pagina 67 - 0/100=3460

Contents1 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANT ... 1[1] Storage of Piping Material ...

Pagina 68

–17–[3] Equipment Composition40LW-FA. Heat source unitPQRY-P200YMF-BB. BC controller Branch pipe kitCMY-Y102S-F CMY-Y102L-FD. Indoor unitCassette cei

Pagina 69

–18–[4] Electrical Wiring Diagram• PQRY-P200·250YMF-B<ELECTRICAL WIRING DIAGRAM>Refer to the [6]the switch operations.L2SM2M1L11L3PER65243324112

Pagina 70 - 12345678910

–19–• PQRY-P200·250YMF-BSV1, SV24-way valveSolenoid valve (Discharge-suction bypass)21S4Aux. relayDischarge pipe temp. detectSaturation evapo. temp. d

Pagina 71

–20–Symbol explanationPE321321EARTHTerminal block(for Transmission)TB02Terminal block(for power source)TB01Note:TB02 is terminal block for transmissio

Pagina 72

–21–• CMB-P105V-ESymbol explanationPE321321EARTHTerminal block(for Transmission)TB02Terminal block(for power source)TB01Note:TB02 is terminal block fo

Pagina 73 - 1 Flow chart

–22–• CMB-P106V-EPE321321EARTHNote:TB02 is terminal block for transmission. Never connect power line to it.Transmission lineShield wire /N 220V

Pagina 74

–23–• CMB-P108V-EPE321321EARTH}Power source}}LNPower source /N 220V 240V 50HzNote:TB02 is terminal block for transmission. Never connect pow

Pagina 75

–24–• CMB-P1010V-EPE321321EARTH}Power source}}LNPower source /N 220V 240V 50HzNote:TB02 is terminal block for transmission. Never connect po

Pagina 76

–25–• CMB-P1013V-EPEEARTH123123TB02TB01NameSymbolTerminal block(for Transmission)Solenoid valveSolenoid valveSolenoid valveSolenoid valveTerminal bloc

Pagina 77 - Piping length (m)

–26–• CMB-P1016V-EPEEARTH123123TB02TB01NameSymbolTerminal block(for Transmission)Solenoid valveSolenoid valveSolenoid valveSolenoid valveTerminal bloc

Pagina 78 - 7 TROUBLESHOOTING

Safety precautionsBefore installation and electric workBefore installing the unit, make sure you read allthe “Safety precautions”.The “Safety precauti

Pagina 79

–27–[5] Standard Operation Data1 Cooling operationHeat source unitItemsPQRY-P200YMF-B PQRY-P250YMF-BIndoorQuantityQuantity in operationModelMain pipeB

Pagina 80

–28–2 Heating operationHeat source unitItemsPQRY-P200YMF-B PQRY-P250YMF-BIndoorQuantityQuantity in operationModelMain pipeBranch pipeTotal piping leng

Pagina 81

–29–Changes as shown below by on → off change0% → 3% → 6% → 9% → 12% → –6% → –3% → 0%Before power is turned on.During normal operation when poweris on

Pagina 82 - Valve opening (Flow rate)

–30–(2) Indoor unitDIP SW1, 3Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to th

Pagina 83 - Caution:

–31–Setting of DIP SW4 Setting of DIP SW5Model Circuit board usedSW41234ON OFF ON OFF––––ON OFF ON OFFOFF OFF OFF ONON OFF OFF ONOFF ON OFF ONOFF OFF

Pagina 84

–32–[7] External Input/Output Specifications(1) Output1 Operation ON signalTerminal No. TB8-1, 2Output Relay contacts output Rated voltage: L1 - N: 22

Pagina 85

–33–33333 TEST RUN[1] Before Test Run(1) Check points before test runNeither refrigerant leak nor loose power source/ transmission lines should be fou

Pagina 86

–34–(3) Check points for test run when mounting options(4) Attention for mounting drain water lifting-up mechanismCheck pointLocal remote controller d

Pagina 87

–35–

Pagina 88 - In case no MELANS used

–36–Check itemInstruction for selecting combination of heat sourceunit, and indoor unit followed? (Maximum number ofindoor units which can be connecte

Pagina 89

–1–11111 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANTCautionDo not use the existing refrigerant piping.• The old refrigerant and refrigerator oi

Pagina 90

–37–ClassificationTransmissionlineSystem setBefore startingPortion Check item1Limitation of transmission line length followed? Forexample, 200m or le

Pagina 91 - BN = 1.3V or less

–38–UnitIndoor unitHeat source unitBC controllerRemote controller(Main)Remote controller(Sub)MJ-103Fresh MasterLossnay unitIndoor unitHeat source unit

Pagina 92

–39–2 Branch number switch (Indoor Units and Fresh Master)Match the indoor unit’s refrigerant pipe with the BC controller’s end connection number.When

Pagina 93

–40–Range01~5001~50101~150Note 1151~200Note 151~100Note 251~100Note 2SettingSmallest address amongseveral indoor units thatform a single group.Address

Pagina 94

–41–5551TB7TB7TB3TB3010807 06 0502 03 04103101107CN40CN41Indoor unitChangeIndoor unit Indoor unit Indoor unitIn series with ventilationIndoor unit Ind

Pagina 95 - 2/T1 4/T2 6/T3

–42–104 1050504 06201201GRTB7TB354TB7TB351101 10301 02 03GRCN40CN41Indoor unitIndoor unit Indoor unit Indoor unitWhere a group remote controller iscon

Pagina 96

–43–[3] Test Run MethodOperation procedure1Turn on universal power supply at least 12 hours before getting started → Displaying “HO” on display panel

Pagina 97 - 1) Pressure sensor

–44–44444 GROUPING REGISTRATION OF INDOOR UNITS WITH REMOTE CONTROLLER(1) Switch function• The switch operation to register with the remote controller

Pagina 98

–45–(2) Attribute display of unit• At the group registration and the confirmation/deletion of registration/connection information, the type (attribute

Pagina 99 - 2) Temperature sensor

–46–(3) Group registration of indoor unit1) Registration method• Group registration of indoor unit ...

Pagina 100

–2–[1] Storage of Piping Material(1) Storage locationStore the pipes to be used indoors. (Warehouse at site or owner’s warehouse)Storing them outdoors

Pagina 101

–47–2) Method of retrieval/confirmation• Retrieval/confirmation of group registration information on indoor unit ... 2The address of the

Pagina 102

–48–3) Method of deletion• Deletion of group registration information of indoor unit ... 4[Operation procedure]1 Wi

Pagina 103

–49–4) Deletion of information on address not existing• Deletion of information on address not existing ...

Pagina 104 - Clicking noise

–50–55555 CONTROL[1] Control of Heat Source Unit(1) Initial processing• When turning on power source, initial processing of microcomputer is given top

Pagina 105

–51–▼1.5kg/cm2G 2.5kg/cm2G(0.15MPa) (0.25MPa)▼20kg/cm2G 27kg/cm2G(1.96MPa) (2.65MPa)▼▼ONOFFONOFF2) Pressure limitThe upper limit of high pressure (Pd)

Pagina 106

–52–(7) Judgement and control of refrigerant amountJudge refrigerant amount by detecting refrigerant liquid surface accumulator.1) Judgement of accumu

Pagina 107

–53–ModeHeat Exchanger SwitchingRemarksSV3 SV4 SV5 SV6 SV71 SV72 SV73Cooling-only × ××× ××××× ×××××× ×××××× × × 8 HP only× ×× ×××10 HP only× ×× × × 10

Pagina 108 - TH15 TH11 TH12

–54–[2] Control box cooling systemIn PQRY, in order to cool the parts in the control box which emit heat, a refrigerant evaporator has been placed int

Pagina 109 - Solenoid valve

–55–[3] Control of BC Controller(1) Control of SVA, SVB and SVCSVA, SVB and SVC are turned on and off depending on connection mode.Cooling Heating Sto

Pagina 110

–56–YESNOYESNOYESYESNONONormal operationsTrouble observedStopStartBreakerturned onSet indoor ad-dress No. to remotecontrollerOperationcommandOperation

Pagina 111

–3–[2] Piping MachiningUse ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.Use only

Pagina 112 - (1) Mechanical

–57–(2) BC controllerNote : 1 Two error modes include indoor unit side trouble, BC controller trouble, and heat source unit side trouble. In the case

Pagina 113

–58–YESNOYESNOYESNOYESNOYESNOYESNOYESNOYESNONormal operationsTrouble observedStopStartBreakerturned onOperation SWturned on1. Protection functionself-

Pagina 114

–59–YESNOYESYESNONO(4) Cooling operation1. Inverter output 0Hz2. Indoor unit LEV, oil return LEV(SLEV), INV cooling LEV (LEV2)fully closed3. Solenoid

Pagina 115

–60–YESNOYESYESNONONO(5) Heating operationNormal operationsStopTest run1. Indoor unit fan very low speedoperations2. Inverter output 0Hz3. Indoor un

Pagina 116

–61–YESNOYESYESNO(6) Dry operationNormal operationsThermostat ONStop1. Indoor unit fan stop2. Inverter output 0Hz3. Indoor unit LEV, oil return LEV(S

Pagina 117

–62–Low pressure shell scroll type withcapacity control mechanismWinding resistance:Each phase 0.388Ω (20˚C)Setting 30kg/cm2G (2.94MPa)OFFR120=7.465kΩ

Pagina 118

–63–Name Symbol (function) Application Specification Check methodHeat source unitThermistorSolenoidvalveLinearexpansionvalveLiquid leveldetectionheate

Pagina 119

–64–R0=15kΩB0/100=3460Rt =15exp{3460( - )}0˚C : 15kΩ10˚C : 9.7kΩ20˚C : 6.4kΩ25˚C : 5.3kΩ30˚C : 4.3kΩ40˚C : 3.1kΩAC 220~240VOpen wh

Pagina 120

–65–[6] Resistance of Temperature SensorThermistor for low temperatureThermistor Ro= 15kΩ ± 3% (TH3 ~ 9, THINV) Thermistor R120 = 7.465kΩ ± 2% (TH1, 1

Pagina 121

–66–66666 REFRIGERANT AMOUNT ADJUSTMENTClarify relationship between the refrigerant amount and operating characteristics of CITY MULTI, and perform se

Pagina 122

–4–[3] Necessary Apparatus and Materials and Notes on Their HandlingThe following tools should be marked as dedicated tools for R407C.<<Comparis

Pagina 123

–67–JudgmentNormal if the resistance is 2 kΩ ± 5%.Normal if AC 198~264 V is outputtogether with the LED lighting.JudgementRefrigerant volume tends tow

Pagina 124

–68–3 Check the refrigerant volume by self-diagnosis using the LED.Set the self-diagnosis switch (SW1) as shown below and check the past information (

Pagina 125 - (2) Communication/system

–69–(3) Refrigerant amount adjustment mode operations1) ProcedureFollow the procedure shown below when needs to additionally replenish or discharge re

Pagina 126

–70–YESNO2) Refrigerant adjustment in cooling season1 Flow chartCooling operations of all indoor unitsin test run mode.After compressor start, turn on

Pagina 127

–71–2 Additional replenishment amount and discharge amount of refrigerantTable-1 PQRY-P250YMF-B (In case total capacity code is 40 or more and display

Pagina 128

–72–3 Time required for recovering refrigerant from low pressure service port (minute)3.5~4.5 4.5~5.5 5.5 ~ 7.5(0.34~0.44) (0.44~0.54) (0.54~0.74)1 4.

Pagina 129

–73–3) Refrigerant adjustment in heating season1 Flow chartYESNO* Valid for only 2 hours in the test run mode. All work must therefore be carried out

Pagina 130

–74–Note :1. Be sure to operate all indoor units because refrigerant is accumulated in stopped unit. Change mode to test runmode for preventing stabil

Pagina 131

–75–77777 TROUBLESHOOTING[1] Principal PartsPressure sensor(1) Judging failure1) Check for failure by comparing the sensing pressure according to the

Pagina 132 - (3) System error

–76–* Connector connection specifications on the pressure sensor body side.The connector’s pin numbers on the pressure sensor body side differ from th

Pagina 133

–5–[4] BrazingNo changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt,etc.) does no

Pagina 134 - [4] LED Monitor Display

–77–(d) The refrigerant flow is as following figure. Hot gas (high pressured) flows in cooling mode and cool gas/liquid(low pressured) flows in heatin

Pagina 135

–78–LEV for heat source unitThe valve opening angle changes in proportion to the number of pulses.(Connections between the heat source unit’s MAIN boa

Pagina 136

–79–LEV for BC controller and indoor unit1 LEV receives pulse signal from microcomputer, and operates valve with stepping motor.2 Valve opening change

Pagina 137

–80–1 Disconnect the control board connector and connectthe check LED as shown in the figure below.When the base power supply is turned on, the indoor

Pagina 138

–81–Heat source LEV (SLEV) coil removal procedure (configuration)As shown in the figure, the heat source LEV is made in such a way that the coils and

Pagina 139

–82–Check valves block (PURY-P200·250YMF-B)The refrigerant flow in the pipe 6, 7, 8 and 9 are depend on ON/OFF of the SV3, 4, 5 and 6.Please confirm b

Pagina 140

–83–Power transistorMeasure resistances between each terminal of transistor module with tester, and use the results for troubleshooting.Specified resi

Pagina 141

–84–(5) Trouble and remedy of remote controllerSymptom Cause Checking method & countermeasure12Despite pressing ofremote controllerswitch, operati

Pagina 142

–85–Symptom Cause3 “HO” display on re-mote controller doesnot disappear andswitch is ineffective.(Without using MELANS)1) Heat source unit address is

Pagina 143

–86–Symptom Cause Checking method & countermeasure4 “88” appears on re-mote controller at theregistration andaccess remotecontrollera) Confirm the

Pagina 144 - 2345678910

–6–[5] Airtightness TestNo changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407Cleakage.Halide to

Pagina 145

–87–Transmission power circuit (30 V) check procedureIf “” is not displayed by the remote control, investigate the points of the trouble by the follow

Pagina 146

–88–(6) Investigation of transmission wave shape/noiseControl is performed by exchanging signals between heat source unit, indoor unit and remote cont

Pagina 147

–89–3) Checking and measures to be taken(a) Measures against noiseCheck the items below when noise can be confirmed on wave shape or the error code in

Pagina 148 - FRIGERANT

–90–4) Treatment of inverter and compressor troublesIf the compressor does not work when error codes 4210, 4240, 4310 or 4340 are detected, determine

Pagina 149 - [3] Pressure Characteristics

–91–5) Troubleshooting at breaker trippingCheck items Measures to be taken 1 Check the breaker capacity. 2 Check the a short circuit or grounding in t

Pagina 150 - A REFRIGERATOR OIL

–92–6) Individual parts failure judgment methods.Part name Judgment methodDiode Stack (DS) Refer to “Judging Diode Stack Failure.”Transistor Module (T

Pagina 151

–93–

Pagina 152

–94–(8) Troubleshooting the major components of the BC controller1) Pressure sensorPressure sensor troubleshooting flowCheck on the LED monitor dis-pl

Pagina 153

–95–Note 1 :• Symptoms of incorrect connection of BC controller pressure sensor to the boardNote 2 :• Check using LED monitor display switch (heat sou

Pagina 154 - Printed in Japan

–96–2) Temperature sensorThermistor troubleshooting flowStartDisconnect applicable thermistorconnector from the board.Measure temperature of applicabl

Comentarios a estos manuales

Sin comentarios