HVAC Guide Specifications
Multi Indoor Unit, Variable Capacity, Mini-splits – R2-Series and Y-Series
Section 15700 – Mechanical HVAC
Size Range:
6 TO 8.5 TONS NOMINAL
Mitsubishi Model Number:
PURY-80TMU-A R2-SERIES (SIMULTANEOUS COOL/HEAT MODEL)
PURY-100TMU-A R2-SERIES (SIMULTANEOUS COOL/HEAT MODEL)
PUHY-80TMU-A Y-SERIES (COOL/HEAT MODEL)
PUHY-100TMU-A Y-SERIES (COOL/HEAT MODEL)
Part 1 – General
1.01 SYSTEM DESCRIPTION
The variable capacity, heat pump heat recovery air conditioning system shall be
a Mitsubishi Electric CITY MULTI VRFZ (Variable Refrigerant Flow Zoning)
System. The CITY MULTI VRFZ systems are the R2-Series (simultaneous heat
and cooling) split system and Y-Series (cool/heat) split system.
The R2-Series system shall consist of multiple indoor units, DDC (Direct Digital
Controls) controls, BC (Branch Circuit) controller and PURY series outdoor unit.
Outdoor unit model numbers may be PURY-80TMU-A or PURY-100TMU-A. Up
to 16 indoor units may be connected to a single PURY-100TMU-A outdoor unit
and up to 15 indoor units may be connected to a single PURY-80TMU-A outdoor
unit. Each indoor unit can be independently controlled. The R2-Series is a
vertical discharge, 208/230 volt, three phase outdoor unit.
The Y-Series system shall consist of multiple indoor units, DDC (Direct Digital
Controls) controls, and PUHY outdoor unit. Outdoor unit model numbers may
be PUHY-80TMU-A or PUHY-100TMU.-A Up to 16 indoor units may be
connected to a single PUHY-100TMU-A outdoor unit and up to 13 indoor units
may be connected to a single PUHY-80TMU-A outdoor unit. Each indoor unit can
be independently controlled. The Y-Series is a vertical discharge, 208/230 volt
three phase outdoor unit.
1.02 QUALITY ASSURANCE
A. The units shall be listed by Electrical Laboratories (ETL) and bear the ETL
label.
B. All wiring shall be in accordance with the National Electrical Code (N.E.C.).
C. The units shall be manufactured in a facility registered to ISO 9001 and
ISO14001 which is a set of standards applying to environmental protection
set by the International Standard Organization (ISO).
1
Vista de pagina 0
1 2 3 4 5 6 ... 24 25

Indice de contenidos

Pagina 1

HVAC Guide Specifications Multi Indoor Unit, Variable Capacity, Mini-splits – R2-Series and Y-Series Section 15700 – Mechanical HVAC S

Pagina 2

1. The indoor fan shall be an assembly with a turbo fan direct driven by a single motor. 2. The fan shall be statically and dynamically balanced and

Pagina 3

Each system shall perform in accordance to the ratings shown in the table below. Performance shall be based on 67° FWB, 80° FDB for the indoor unit an

Pagina 4

7. Both refrigerant lines to and from the PMFY indoor units shall be insulated. G. Electrical: 1. The unit electrical power shall be 208/230 volts,

Pagina 5

3. There shall be a separate back plate which secures the unit firmly to the wall. D. Fan: 1. The indoor fan shall be an assembly with one or two li

Pagina 6

10NRMU-A / PFFY-12NRMU-A / PFFY-16NEMU-A / PFFY-20NRMU-A / PFFY24-NRMU-A. These system model numbers include the R2-Series variable capacity, vertica

Pagina 7

5. The indoor fan shall consist of four (4) speeds, High, Mid1, Mid2, and Low, two of which are selectable by the room controller. F. Filter: 1. Ret

Pagina 8

5.03 CITY MULTI Controls Network (CMCN) The CITY MULTI Controls Network (CMCN) consists of remote controllers, timers, centralized controllers, and i

Pagina 9

The MA Remote Controller can only be used in same group with other PAR-20MAU (MA Remote Controllers) and with PAC-YT51CRA (Simple MA Remote Controller

Pagina 10

B. PAR-F27MEA-US-E: ME REMOTE CONTROLLER The ME Remote Controller (PAR-F27MEA-US-E) is capable of controlling up to 16 indoor units (defined as 1 gro

Pagina 11

Functions Item Description Operation DisplayON/OFF Run and stop operation for a single group ○ ○ Operation mode switching Switches between Cool/Dry

Pagina 12

D. A full charge of R-22 for the condensing unit only shall be provided in the condensing unit. E. System efficiency shall meet or exceed 8.5 EER du

Pagina 13

C. PAC-YT51CRA-E: SIMPLE MA REMOTE CONTROLLER The Simple MA Remote Controller (PAC-YT51CRA-E) is capable of controlling up to 16 indoor units (define

Pagina 14

5.05 CMCN: Timers A. PAC-YT32PTA-E: PROGRAM TIMER The Program Timer (PAC-YT32PTA-E) can be used only in conjunction with one PAR-20MAU (MA Remote Con

Pagina 15

Functions Item Description Operation DisplayUnit control 50 units/50 groups (Maximum 16 units connected in one group) ◙ ○ Schedule control One wee

Pagina 16 - CMCN System Configuration

5.06 CMCN: System Controllers A. G-50A Centralized Controller The G-50A Centralized Controller is capable of controlling a maximum of 50 indoor unit

Pagina 17 - ■Functions

Functions Item Description Operation Display ON/OFF Run and stop operation for a single group ○◙ ○◙ Operation mode switching Switches between Cool/

Pagina 18

All G-50A Centralized Controllers are equipped with a RJ-45 Ethernet port to support interconnection with a network PC via a closed/direct Local Area

Pagina 19

3.03 Cooling and heating simultaneous performance: Heat Recovery Capacity Cooling/Heating System Model PURY-100TMU-A Capacity Cooling Capacity Hea

Pagina 20

1. The casing shall be fabricated of galvanized steel, bonderized and finished with a powder coated baked enamel. C. Fan: 1. The unit shall be furni

Pagina 21 - 5.05 CMCN: Timers

4. The control voltage between the indoor units and the outdoor unit shall be completed using a 2-conductor shielded cable to provide total integrati

Pagina 22

D. Integral Drain Pan: 1. An integral condensate pan and drain shall be provided. E. Electrical: 1. The unit electrical power shall be 208/230 volt

Pagina 23

1. The compressor shall be a high performance, inverter driven, modulating capacity scroll compressor. 2. A crankcase heater shall be factory mounte

Pagina 24

System Model Number Btu/h Cooling Btu/h Heating PDFY-10NAMU-A 9,500 10,800 PDFY-16NAMU-A 15,700 18,700 PDFY-24NAMU-A 23,600 25,400 PDFY-32NAMU-A

Pagina 25

2. The system shall be capable of satisfactory operation within voltage limits of 188 volts to 253 volts. H. Controls: 1. This unit shall have contr