CAPACITY TABLES1394.3 3.1 4.4 3.2 4.7 3.1 4.8 3.3 5.0 3.3 5.3 3.2 5.7 3.24.2 3.0 4.3 3.1 4.6 3.1 4.8 3.3 5.0 3.3 5.3 3.2 5.6 3.24.2 3.0 4.3 3.1 4.6 3.
CAPACITY TABLES1481.6 1.2 1.7 1.2 1.8 1.2 1.9 1.3 2.0 1.3 2.1 1.3 2.2 1.21.6 1.2 1.7 1.2 1.8 1.2 1.9 1.3 1.9 1.3 2.0 1.2 2.2 1.21.6 1.1 1.6 1.2 1.8 1.
2. M-NET controlSYSTEM DESIGN 2382-2. Transmission cable specificationsCheck the existing wires for damage to insulation by measuring the resistance
2392. M-NET controlSYSTEM DESIGN2-2-1. Reusability check of the existing transmission lines for Replace Multi unitsCheck items Notes1. Remote control
2. M-NET controlSYSTEM DESIGN 240Table AIs the 2-core cable used?Is the 2-core cable used?Is the 2-core cable used?YESNOYESNOYESYES YESNOYESNOYESYESY
2412. M-NET controlSYSTEM DESIGNTable AReusability of Transmission lineIs the 2-core cable used?Is the shielded wiring used?Refer to Table A.Is a shi
2. M-NET controlSYSTEM DESIGN 2420501001502000 5 10 15 20 25 3230Number of indoor unitsLength of transmission line to the farthest unit (m)0.75mm20.5
2432. M-NET controlSYSTEM DESIGN2-3. System configuration restrictions2-3-1. Common restrictions for the CITYMULTI systemTable 2-3-1 The equivalent p
2. M-NET controlSYSTEM DESIGN 244PAC-SC51KUAOutdoor unitMA remote controllerGroup GroupIndoor unitM-NET transmission lines(transmission lines for ce
2452. M-NET controlSYSTEM DESIGN1-phase 220-240V AC power supply is needed.The power supply unit PAC-SC51KUA is not necessary when connecting only th
2. M-NET controlSYSTEM DESIGN 2462-4. Address settingBranchNo. settingUnit address No. settingRotary switchIn order to constitute CITY MULTI in a com
2472. M-NET controlSYSTEM DESIGN2-4-2. Rule of setting addressUnitIndoor unitME, LOSSNAYRemote controller(Main)ME, LOSSNAYRemote controller(Sub)Addre
CAPACITY TABLES1496.9 5.3 7.1 5.4 7.6 5.4 7.9 5.8 8.2 5.8 8.7 5.7 9.3 5.66.7 5.2 7.0 5.4 7.5 5.4 7.8 5.7 8.0 5.7 8.6 5.6 9.1 5.56.7 5.2 6.9 5.3 7.4 5.
2. M-NET controlSYSTEM DESIGN 2482-4-3. System examplesOriginal switch setting of the outdoors, indoors, controllers, LMAP and BM ADAPTER at shipment
2492. M-NET controlSYSTEM DESIGN2-4-3-2. MA remote controller, Single-refrigerant-system, System Controller1. Address should be set to Indoor units a
2. M-NET controlSYSTEM DESIGN 2502-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/ TB3 side, Booster for long M-NET
2512. M-NET controlSYSTEM DESIGN2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller1. Address should be set to Indoor unit
2. M-NET controlSYSTEM DESIGN 2522-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-
2532. M-NET controlSYSTEM DESIGN2-4-3-8. ME remote controller, Multi-refrigerant-system, No Power supply unitNOTE• It is necessary to change the con
2. M-NET controlSYSTEM DESIGN 2542-4-3-10. TG-2000A(*1)+AG-150A(*2) AG-150A can control max. 50 indoor units;TG-2000A can control max. 40 pieces of A
2552. M-NET controlSYSTEM DESIGNNOTE When connecting AG-150A to PAC-YG50ECA, TB2 for power supply unit does not need to be connected to AG-150A.2-4-
2. M-NET controlSYSTEM DESIGN 2562-4-3-12. LMAPLMAP(01)24VDC (LONWORKS adapter)PCLONWORKS cardLONWORKS cardLONWORKS cardFor other equipments (Lightin
2572. M-NET controlSYSTEM DESIGN2-4-3-13. BM ADAPTERBM ADAPTER(01)HUBFor other equipments (Lighting, security, elevator etc.)BM ADAPTER can transmiss
CAPACITY TABLES150H5. Cooling capacity with PUHY-RP850, 900YSJM1.6 1.2 1.6 1.2 1.8 1.2 1.8 1.2 1.9 1.2 2.0 1.2 2.1 1.21.6 1.2 1.6 1.2 1.7 1.2 1.8 1.2
2. M-NET controlSYSTEM DESIGN 2582-4-3-14. BM ADAPTER+PAC-YG50ECA (Expansion controller)BM ADAPTER can transmission for max. 50 indoor units in singl
2593. Piping DesignSYSTEM DESIGN3. Piping Design3-1. Piping Design3-1-1. IF 16 ports or less are in use, I.e., if only one BC controller is in use wi
3. Piping DesignSYSTEM DESIGN 2603-1-2. IF more than 16 ports are in use, or if there is more than one BC controller in use for one outdoor unitTable
2613. Piping DesignSYSTEM DESIGN3-1-3. Pipe diameter compatibility table(1) Main pipe(30m or shorter) (20m or shorter)ø12.7ø9.52ø12.7ø15.88ø19.05ø19.
3. Piping DesignSYSTEM DESIGN 2623-1-4. Flow chart to check if the existing piping can be reusedYESYESYESYESYESYESYESYESYESNONONONONONONONONONOIs the
2633. Piping DesignSYSTEM DESIGN3-2. Refrigerant charging calculationSample connection (with BC controller and 4 indoor units)Amount of additional re
4. Outdoor InstallationSYSTEM DESIGN 2644. Outdoor In stallation4-1. Requirement on installation site1. No direct thermal radiation to the unit.2.
2654. Outdoor InstallationSYSTEM DESIGN4-2. Spacing1000[39-3/8]240 [9-15/32]45°50 [1-31/32]<C>(Unit : mm [in.])<B>500[19-11/16] HhhH100*[
4. Outdoor InstallationSYSTEM DESIGN 266In case of collective installation and continuous installation:: Wall height (H)(Unit : mm [in.])ABC30450* 3
2674. Outdoor InstallationSYSTEM DESIGN4-3. Piping direction4-3-1. Lifting method· When lifting the unit with ropes, run the ropes under the unit and
CAPACITY TABLES151H5. Cooling capacity with PUHY-RP850, 900YSJM6.7 5.2 6.9 5.3 7.4 5.3 7.6 5.6 7.9 5.6 8.4 5.6 8.9 5.56.6 5.1 6.8 5.3 7.3 5.3 7.5 5.6
4. Outdoor InstallationSYSTEM DESIGN 2684-3-2. Installation30mm[1-3/16 in.]30mm[1-3/16 in.]Install the unit in such a way that the corner of the angl
2694. Outdoor InstallationSYSTEM DESIGN4-3-5. Refrigerant pipe routing4-3-4. Installation · RP200, 250, 300(Unit : mm [in.])Installation base paralle
4. Outdoor InstallationSYSTEM DESIGN 2704-4. Weather countermeasurePrevention the Outdoor unit from wind and snow damages in cold or snowy areas, sno
2715. Caution for refrigerant leakageSYSTEM DESIGN5. Caution for refrigerant leakageThe installer and/or air conditioning system specialist shall sec
272I.Optional parts for the heat source units1. JOINT
273CONTROLLERCONTROLLER4-1.System component ...
CONTROLLERCONTROLLER 274I.1. System component4-1. System componentOKNOCITY MULTI system can be monitored or controlled with signal to/from the outsid
275CONTROLLERCONTROLLERIndoor group can be controlled ON/OFF by an ON/OFF switching or contact input to the connector of the head Indoor in an Indoor
CONTROLLERCONTROLLER 2764-2. Outdoor unit input/output connectorCN51XYL1L2Lamp power sourceDistant control boardRelay circuit Adapter *1Outdoor unit
277CONTROLLERCONTROLLER4-3. Indoor unit "-E" type input/output connectorInput OutputON/OFF (Pulse) input specification Caution:3.The electr
CAPACITY TABLES1522.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.82.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.82.1 1.7 2.2 1.7 2.3 1.
278I.Optional parts for the heat source units1. JOINT
DATA BOOK PUHY-RP-Y(S)JM-APURY-RP-YJM-Ahttp://Global.MitsubishiElectric.comHEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310,
CAPACITY TABLES1532.1 1.9 2.2 2.0 2.3 1.9 2.4 2.0 2.5 2.1 2.6 2.0 2.8 2.02.1 1.9 2.2 2.0 2.3 1.9 2.4 2.0 2.5 2.1 2.6 2.0 2.8 2.02.1 1.9 2.2 2.0 2.3 1.
CAPACITY TABLES154PFFY-P-VLRMM-ECA : Capacity(kW) SHC : Sensible Heat Capacity(kW)2.0 1.6 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.82.0 1.6 2.1 1
CAPACITY TABLES1552.1 1.7 2.2 1.8 2.4 1.7 2.5 1.8 2.5 1.9 2.7 1.8 2.9 1.82.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.6 1.8 2.8 1.82.1 1.7 2.2 1.7 2.3 1.
CAPACITY TABLES1562.1 1.9 2.2 2.0 2.4 2.0 2.5 2.0 2.5 2.1 2.7 2.1 2.9 2.12.1 1.9 2.2 2.0 2.3 2.0 2.4 2.0 2.5 2.1 2.6 2.1 2.8 2.02.1 1.9 2.2 1.9 2.3 1.
CAPACITY TABLES157PFFY-P-VLRMM-ECA : Capacity(kW) SHC : Sensible Heat Capacity(kW)kcal/h = kW x 860, Btu/h = kW x 3,412Indoor air temp.71 ˚FDB / 59˚
CAPACITY TABLES1404.3 3.1 4.5 3.2 4.8 3.2 5.0 3.4 5.2 3.4 5.5 3.3 5.9 3.34.3 3.1 4.4 3.2 4.7 3.1 4.9 3.3 5.1 3.3 5.4 3.3 5.8 3.34.2 3.0 4.4 3.2 4.7 3.
CAPACITY TABLES1582.1 1.7 2.1 1.7 2.3 1.7 2.4 1.7 2.5 1.8 2.6 1.8 2.8 1.82.1 1.7 2.1 1.7 2.3 1.7 2.3 1.7 2.4 1.8 2.6 1.8 2.7 1.82.0 1.7 2.1 1.7 2.2 1.
CAPACITY TABLES1592.1 1.9 2.1 1.9 2.3 1.9 2.4 2.0 2.5 2.1 2.6 2.0 2.8 2.02.1 1.9 2.1 1.9 2.3 1.9 2.3 2.0 2.4 2.1 2.6 2.0 2.7 2.02.0 1.9 2.1 1.9 2.2 1.
CAPACITY TABLES160PFFY-P-VLRMM-ECA : Capacity(kW) SHC : Sensible Heat Capacity(kW)kcal/h = kW x 860, Btu/h = kW x 3,412Indoor air temp.71 ˚FDB / 59˚
CAPACITY TABLES1612.1 1.7 2.2 1.7 2.4 1.7 2.4 1.8 2.5 1.9 2.7 1.8 2.9 1.82.1 1.7 2.2 1.7 2.3 1.7 2.4 1.8 2.5 1.8 2.7 1.8 2.8 1.82.1 1.7 2.1 1.7 2.3 1.
CAPACITY TABLES1622.1 1.9 2.2 2.0 2.4 2.0 2.4 2.0 2.5 2.1 2.7 2.1 2.9 2.12.1 1.9 2.2 2.0 2.3 1.9 2.4 2.0 2.5 2.1 2.7 2.1 2.8 2.02.1 1.9 2.1 1.9 2.3 1.
CAPACITY TABLES163PFFY-P-VLRMM-ECA : Capacity(kW) SHC : Sensible Heat Capacity(kW)2.12.12.12.02.01.91.91.91.81.82.72.72.62.62.52.52.42.42.42.33.53.43.
CAPACITY TABLES164I5. Cooling capacity with PUHY-RP850, 900YSJM2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.82.1 1.7 2.1 1.7 2.3 1.7 2.3 1.8
CAPACITY TABLES165I5. Cooling capacity with PUHY-RP850, 900YSJM2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.8 2.4 1.8 2.6 1.8 2.8 1.82.1 1.6 2.1 1.7 2.3 1.7 2.3 1.8
CAPACITY TABLES166I5. Cooling capacity with PUHY-RP850, 900YSJMPFFY-P-VLRMM-ECA : Capacity(kW) SHC : Sensible Heat Capacity(kW)2.1 1.7 2.1 1.7 2.3 1.7
CAPACITY TABLES167Indoor air temp.15.0˚CDB 20.0˚CDB 25.0˚CDB 27.0˚CDB 59 ˚FDB 68 ˚FDB 77 ˚FDB 81 ˚FDB 15.0˚CDB 20.0˚CDB 25.0˚CDB 27.0˚CDB 5
CAPACITY TABLES141G5. Cooling capacity with PUHY-RP850, 900YSJM4.3 3.1 4.4 3.1 4.7 3.1 4.8 3.3 5.0 3.3 5.3 3.3 5.6 3.24.2 3.0 4.3 3.1 4.6 3.1 4.8 3.3
CAPACITY TABLES168Indoor air temp.15.0˚CDB 20.0˚CDB 25.0˚CDB 27.0˚CDB 59 ˚FDB 68 ˚FDB 77 ˚FDB 81 ˚FDB 15.0˚CDB 20.0˚CDB 25.0˚CDB 27.0˚CDB 5
CAPACITY TABLES169Indoor air temp.15.0˚CDB 20.0˚CDB 25.0˚CDB 27.0˚CDB 59 ˚FDB 68 ˚FDB 77 ˚FDB 81 ˚FDB 15.0˚CDB 20.0˚CDB 25.0˚CDB 27.0˚CDB 5
CAPACITY TABLES170Indoor air temp.15.0˚CDB 20.0˚CDB 25.0˚CDB 27.0˚CDB 59 ˚FDB 68 ˚FDB 77 ˚FDB 81 ˚FDB 15.0˚CDB 20.0˚CDB 25.0˚CDB 27.0˚CDB 5
CAPACITY TABLES171X5. Heating capacity with PUHY-RP850, 900YSJMIndoor air temp.15.0˚CDB 20.0˚CDB 25.0˚CDB 27.0˚CDB 59 ˚FDB 68 ˚FDB 77 ˚FDB 81
CAPACITY TABLES1723-1. Cooling capacity of PEFY-P-VMH-E-FOutdoorair temp.2123252729313335374070737781848891959910495˚FWB90˚FWB86˚FWB82˚FWB79˚FWB73˚FWB
CAPACITY TABLES1733-2. Outlet air temp. cooled˚CWB5.05.05.0-------˚CDB5.15.15.1-------˚CWB5.65.65.75.7------˚CDB5.65.75.75.8------˚CWB-7.07.17.27.37.4
CAPACITY TABLES1743-3. Heating capacity of PEFY-P-VMH-E-FSHC8.2--------SHC-9.1-------SHC--8.5------SHC---7.9-----SHC---7.97.1----SHC----7.1----SHC----
CAPACITY TABLES1753-4. Outlet air temp. heated˚CDB40.6--------˚CDB-53.1-------˚CDB--51.9------˚CDB---51.3-----˚CDB---51.850.5----˚CDB----50.5----˚CDB-
176
177SYSTEM DESIGN Y SERIESSYSTEM DESIGN Y SERIES1. Electrical work...
CAPACITY TABLES1421.6 1.2 1.7 1.2 1.8 1.2 1.8 1.3 1.9 1.2 2.0 1.2 2.1 1.21.6 1.2 1.7 1.2 1.8 1.2 1.8 1.3 1.9 1.2 2.0 1.2 2.1 1.21.6 1.2 1.7 1.2 1.8 1.
1. Electrical workSYSTEM DESIGN 178I.1. Electr ical work1-1. General cautionsOK NOFollow ordinance of your governmental organization for technical st
1791. Electrical workSYSTEM DESIGN1-2. Power supply for Indoor unit and Outdoor unit1-2-1. Electrical characteristics of Indoor unitSymbols: MCA : M
1. Electrical workSYSTEM DESIGN 180Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan moto
1811. Electrical workSYSTEM DESIGNSymbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor
1. Electrical workSYSTEM DESIGN 182Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan moto
1831. Electrical workSYSTEM DESIGN1-2-2. Electrical characteristics of Outdoor unitModel Unit CombinationUnits Power supply Compressor FAN RLA (A) (5
1. Electrical workSYSTEM DESIGN 1841-3. Power cable specificationsThickness of wire for main power supply, capacities of the switch and system impeda
1851. Electrical workSYSTEM DESIGN1-4. Power supply examples The local standards and/or regulations is applicable at a higher priority.1-4-1. PUHY
1. Electrical workSYSTEM DESIGN 186 The local standards and/or regulations is applicable at a higher priority.1-4-2. PUHY-RP400-650YSJM-APower su
1871. Electrical workSYSTEM DESIGN The local standards and/or regulations is applicable at a higher priority.1-4-3. PUHY-RP700-900YSJM-ANote4Note
CAPACITY TABLES1436.7 5.2 7.0 5.4 7.5 5.4 7.7 5.7 7.9 5.6 8.4 5.6 9.0 5.56.7 5.2 7.0 5.4 7.5 5.4 7.7 5.7 7.9 5.6 8.4 5.6 9.0 5.56.7 5.2 7.0 5.4 7.5 5.
2. M-NET controlSYSTEM DESIGN 1882. M-NET control2-1. Transmission cable length limitation2-1-1. Using MA Remote controller2-1-2. Using ME Remote con
1892. M-NET controlSYSTEM DESIGN2-2. Transmission cable specificationsCheck the existing wires for damage to insulation by measuring the resistance b
2. M-NET controlSYSTEM DESIGN 1902-2-1. Reusability check of the existing transmission lines for Replace Multi unitsCheck items Notes1. Remote contro
1912. M-NET controlSYSTEM DESIGNTable AIs the 2-core cable used?Is the 2-core cable used?Is the 2-core cable used?YESNOYESNOYESYES YESNOYESNOYESYESYE
2. M-NET controlSYSTEM DESIGN 192Table AReusability of Transmission lineIs the 2-core cable used?Is the shielded wiring used?Refer to Table A.Is a sh
1932. M-NET controlSYSTEM DESIGN0501001502000 5 10 15 20 25 3230Number of indoor unitsLength of transmission line to the farthest unit (m)0.75mm20.5m
2. M-NET controlSYSTEM DESIGN 1942-3. System configuration restrictions2-3-1. Common restrictions for the CITYMULTI systemTable 2-3-1 The equivalent
1952. M-NET controlSYSTEM DESIGNPAC-SC51KUAOutdoor unitMA remote controllerGroup GroupIndoor unitM-NET transmission lines(transmission lines for cen
2. M-NET controlSYSTEM DESIGN 1961-phase 220-240V AC power supply is needed.The power supply unit PAC-SC51KUA is not necessary when connecting only t
1972. M-NET controlSYSTEM DESIGN2-4. Address settingBranchNo. settingUnit address No. settingRotary switchIn order to constitute CITY MULTI in a comp
CAPACITY TABLES1441.6 1.2 1.7 1.2 1.8 1.2 1.9 1.3 2.0 1.3 2.1 1.3 2.2 1.21.6 1.2 1.7 1.2 1.8 1.2 1.9 1.3 1.9 1.3 2.0 1.2 2.2 1.21.6 1.2 1.7 1.2 1.8 1.
2. M-NET controlSYSTEM DESIGN 1982-4-2. Rule of setting addressUnitIndoor unitME, LOSSNAYRemote controller(Main)ME, LOSSNAYRemote controller(Sub)Addr
1992. M-NET controlSYSTEM DESIGN2-4-3. System examplesFactory settingSetting at the siteOriginal switch setting of the outdoors, indoors, controllers
2. M-NET controlSYSTEM DESIGN 2002-4-3. System examples2-4-3-2. MA remote controller, Single-refrigerant-system, System Controller2. Address should b
2012. M-NET controlSYSTEM DESIGN2-4-3. System examples2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Boo
2. M-NET controlSYSTEM DESIGN 2022-4-3. System examples2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller2. Address shoul
2032. M-NET controlSYSTEM DESIGN2-4-3. System examples2-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY
2. M-NET controlSYSTEM DESIGN 2042-4-3-7. ME remote controller, Multi-refrigerant-system, No Power supply unitNOTE It is necessary to change the co
2052. M-NET controlSYSTEM DESIGN2-4-3-9. TG-2000A(*1)+AG-150A*2AG-150A can control max. 50 indoor units;TG-2000A can control max. 40 pieces of AG-150
2. M-NET controlSYSTEM DESIGN 2062-4-3. System examples2-4-3-10. AG-150A + PAC-YG50ECA (Expansion controller)AG-150A can control max. 150 indoor unit
2072. M-NET controlSYSTEM DESIGN2-4-3. System examples2-4-3-11. LMAPLMAP(01)24VDC(LONWORKs adapter)PCLONWORKS cardLONWORKS cardLONWORKS cardFor other
CAPACITY TABLES1456.9 5.3 7.1 5.4 7.7 5.4 8.0 5.8 8.2 5.8 8.7 5.7 9.2 5.66.9 5.3 7.1 5.4 7.6 5.4 7.8 5.7 8.1 5.7 8.5 5.6 9.1 5.56.8 5.2 7.0 5.4 7.4 5.
2. M-NET controlSYSTEM DESIGN 2082-4-3. System examples2-4-3-12. BM ADAPTERBM ADAPTER(01)HUBFor other equipments (Lighting, security, elevator etc.)B
2092. M-NET controlSYSTEM DESIGN2-4-3. System examples2-4-3-13. BM ADAPTER+PAC-YG50ECA (Expansion controller)BM ADAPTER can transmission for max. 50
3. Piping DesignSYSTEM DESIGN 2103. Piping Desi gn3-1. Piping DesignNote 3. Indoor capacity is described as its model size. For example, PEFY-P32VM
2113. Piping DesignSYSTEM DESIGNOutdoor Twinning KitCMY-RP100VBKNote 1. No Joint after Header; Piping direct to Indoor Unit from HeaderNote 2. As ben
3. Piping DesignSYSTEM DESIGN 212Outdoor Twinning KitCMY-RP100VBKNote 1. No Joint after Header; Piping direct to Indoor Unit from HeaderNote 2. As be
2133. Piping DesignSYSTEM DESIGN2nd Outdoor Twinning Kit1st Outdoor Twinning KitNote 1. No Joint after Header; Piping direct to Indoor Unit from Head
3. Piping DesignSYSTEM DESIGN 2143-1-5. Pipe diameter compatibility table(1) Main pipe(45m or shorter) (30m or shorter)(30m or shorter) (20m or short
2153. Piping DesignSYSTEM DESIGN3-1-6. Flow chart to check if the existing piping can be reusedYESYESYESYESYESYESYESYESYESNONONONONONONONONONOIs the
3. Piping DesignSYSTEM DESIGN 2163-1-7. Refrigerant charging calculationSample connection (with 8 indoor units)Amount of refrigerant to be chargedRe
2174. Outdoor InstallationSYSTEM DESIGN4. Outdoor Installati on4-1. Requirement on installation site1. No direct thermal radiation to the unit.2.
CAPACITY TABLES1461.6 1.2 1.7 1.2 1.8 1.2 1.8 1.2 1.9 1.2 2.0 1.2 2.1 1.21.6 1.2 1.6 1.2 1.8 1.2 1.8 1.2 1.9 1.2 2.0 1.2 2.1 1.21.6 1.1 1.6 1.2 1.7 1.
4. Outdoor InstallationSYSTEM DESIGN 2184-2. Spacing1000[39-3/8]240 [9-15/32]45°50 [1-31/32]<C>(Unit : mm [in.])<B>500[19-11/16] HhhH100*
2194. Outdoor InstallationSYSTEM DESIGNIn case of collective installation and continuous installation:: Wall height (H)(Unit : mm [in.])ABC30450* 30
4. Outdoor InstallationSYSTEM DESIGN 2204-3. Piping direction4-3-1. Lifting method· When lifting the unit with ropes, run the ropes under the unit an
2214. Outdoor InstallationSYSTEM DESIGN4-3-2. Installation30mm[1-3/16 in.]30mm[1-3/16 in.]Install the unit in such a way that the corner of the angle
4. Outdoor InstallationSYSTEM DESIGN 2224-3-5. Refrigerant pipe routing4-3-4. Installation· RP200-RP350Installation base perpendicular to the unit’s
2234. Outdoor InstallationSYSTEM DESIGN4-3-6. Twinning on the outdoor unit side Reducer±15°The tilt angle of the reducer should be within ±15°with th
4. Outdoor InstallationSYSTEM DESIGN 224Field pipingField pipingTwinning kitThe length of the straight pipe must be 500 mm [19 in.] or longerField pi
2254. Outdoor InstallationSYSTEM DESIGN4-4. Weather countermeasure• Snow hoodCountermeasure to windOutletInletReferring to the figure shown below, ta
4. Outdoor InstallationSYSTEM DESIGN 2264-5. Caution on selecting outdoor unitsConsult your dealer when the following issues on Y system are the key
2275. Caution for refrigerant leakageSYSTEM DESIGN5. Caution for refrigerant leakageThe installer and/or air conditioning system specialist shall sec
CAPACITY TABLES1476.7 5.2 6.9 5.3 7.4 5.3 7.6 5.6 7.9 5.6 8.4 5.6 8.9 5.56.7 5.2 6.9 5.3 7.3 5.3 7.5 5.6 7.8 5.6 8.3 5.5 8.8 5.46.6 5.1 6.8 5.3 7.2 5.
228I.Optional parts for the heat source units1. JOINT
229SYSTEM DESIGN R2 SERIESSYSTEM DESIGN R2 SERIES1. Electrical work...
1. Electrical workSYSTEM DESIGN 230I.1. Electr ical work1-1. General cautionsOK NOFollow ordinance of your governmental organization for technical st
2311. Electrical workSYSTEM DESIGN1-2. Power supply for Indoor unit and Outdoor unit1-2-1. Electrical characteristics of Indoor unitSymbols: MCA : M
1. Electrical workSYSTEM DESIGN 232Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan moto
2331. Electrical workSYSTEM DESIGNSymbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan motor
1. Electrical workSYSTEM DESIGN 234Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor Output : Fan moto
2351. Electrical workSYSTEM DESIGN1-2-2. Electrical characteristics of Outdoor unit at cooling mode1-3. Power cable specificationsModel Unit Combinat
1. Electrical workSYSTEM DESIGN 2361-4. Power supply examplesNote4Note3To *1 or *2*1*2Note7Connector CN41 CN40Power supply3-phase 4-wire380-400-415
2372. M-NET controlSYSTEM DESIGN2. M-NET control2-1. Transmission cable length limitationV+V-FGnV+V-FGV+V-FGnV+V-FGLong transmission cable causes vo
Comentarios a estos manuales