Job Name: Location:
Drawing Reference: Schedule No.
System No.: Date:
• R410A refrigerant
•
• Five sizes from 6,000 to 18,000 Btu/h
• Three fan speed settngs
• Built-in condensate lift mechanism; lifts to 11-1/32 in.
•
•
Outside air capability
Quiet operation from 27 to 38 dB(A)
Model: PLFY-P12NLMU-E
GENERAL FEATURES
SPECIFICATIONS
Capacity*
h/utB 000,12 ….……………………………………………gnilooC
Heating…………………………………………….… 13,500 Btu/h
Power
Power Source………………..........208 / 230V, 1-phase, 60Hz
Power Consumption
Cooling………………………………………... 0.068 / 0.075 kW
Heating………………………………………... 0.068 / 0.075 kW
Current
Cooling……...................................................…... 0.34 / 0.37 A
Heating……...................................................…... 0.34 / 0.37 A
Minimum Circuit Ampacity (MCA)……………….….. 0.43 / 0.47 A
Maximum Overcurrent Protection (MOCP) Fuse..….......…..15 A
External Finish……..... Grille (No. 0.7Y 8.59 / 0.97)
Unit Dimensions
Inches…………………….. 11-7/16 H x 30-9/16 W x 24-31/32 D
mm……………………………………... 290 H x 776 W x 634 D
Net Weight
Unit………………..…...……………................ 53 lbs. / 24 kg
Coil Type………………...........................................….Cross Fin
(Aluminum Plate Fin and Copper Tube)
Fan
Type x Quantity………………..………….........…....... Turbo fan x1
Airflow Rate (Low-Mid-High)..................... 230 - 282 - 335 CFM
Motor
Type………..………..……….......... 1-phase induction motor
Output………..………..………..………..………..….0.015 kW
Ai
r Filter..……………………………................... Standard Filter
Refrigerant Piping Dimensions
Liquid (High Pressure)……............1/4" / 6.35 mm (Flared)
Gas (Low Pressure)………………..1/2" / 12.7 mm (Flared)
Drainpipe Dimension……............……...... O.D. 1-1/4" / 32 mm
Sound Pressure Levels
Low-Mid-High........(208V)....................... 27 - 30 - 33 dB(A)
OPTIONS
□ External Heat Adaptor................................... PAC-YU25HT
* Cooling / Heating capacity indicated at the maximum value at
operation under the following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F
(35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C)
WB
Note: Ventilation air: Providing suf ficient ventilation air is an impor-
tant part of every building design. ASHRAE Standard 62 provides
the minimum ventilation air requirement. Also, check local codes.
Notes:
Lightweight and compact desgin
Grille Dimensions
Inches……........................ 13/16 H x 42-17/32 W x 27-31/32 D
mm………………………………...…... 20 H x 1080 W x 710 D
Grille………………..…...…………….............. 15 lbs. / 6.5 kg
Low-Mid-High........(230V)....................... 28 - 31 - 34 dB(A)
□
OA Duct Flange............................................. PAC-KH11OF