OC275-1
CONTENTS
1. TECHNICAL CHANGE ··················································································OC275- 2
2. FEATURES·····································································································OC275- 3
3. PART NAME AND FUNCTIONS····································································OC275- 4
4. SPECIFICATIONS··························································································OC275- 5
5. DATA ··············································································································OC275- 6
6. OUTLINES AND DIMENSIONS·····································································OC275-13
7. REFRIGERANT SYSTEM DIAGRAM····························································OC275-15
8. WIRING DIAGRAM ························································································OC275-16
9. OPERATION FLOW-CHART ·········································································OC275-17
10. MICROPROCESSOR CONTROL ··································································OC275-20
11. TROUBLESHOOTING····················································································OC275-32
12. DISASSEMBLY PROCEDURE ······································································OC275-35
13. PARTS LIST ···································································································OC275-38
PK18FL3
PK24FL3
PK30FL3
PK36FL3
OC275--1.qxp 01/12/14 3:06 PM Page 1
Vista de pagina 0
1 2 3 4 5 6 ... 41 42

Indice de contenidos

Pagina 1 - PK30FL3

OC275-1CONTENTS1. TECHNICAL CHANGE ··················································································OC275- 22. FEATURES··············

Pagina 2 - TECHNICAL CHANGE

OC275-103. STANDARD OPERATION DATA750 750750750 760 760CapacitySHFInputINDOOR UNIT MODELPower supply (V, phase, Hz)InputFan currentOUTDOOR UNIT MODELP

Pagina 3 - FEATURES

OC275-114. OPERATING RANGE1) POWER SUPPLY2) OPERATION5. OUTLET AIR SPEED AND COVERAGE RANGE● The air coverage range is the value up to the position wh

Pagina 4 - 3 PART NAME AND FUNCTIONS

OC275-1290807060504030201063 125 250 500 1000 2000 4000 8000APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISENC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND

Pagina 5 - SPECIFICATIONS4

OC275-13OUTLINES AND DIMENSIONS69-1/41-25/329-1/41-25/329-1/4 9-1/41-25/321/213-3/87-3/41-21/322-9/32TopFrontRight sideLeft side55-1/842-15/16 Air int

Pagina 6 - 1. PERFORMANCE DATA

OC275-1466-5/329-1/453-15/16 Air IntakeFrontKnock out holeRight side9-1/47-3/4Cfor right pipingBAABC4-1/32Liquid pipe 1/2FGas pipeSleeve >< 1&g

Pagina 7

OC275-152-9/326-3/83/4ON/OFF TEMPMODELSELECTNOT AVAILABLESWINGCHECKFANTESTRUN˚F˚CAMPMSTOPSTARTAMPMCOOLDRYAUTOFANHEATUnit : inch5.2. Remote controlle

Pagina 8 - Air flow should be set at HI

OC275-168WIRING DIAGRAMIndoor UnitPK18/24/30/36FL3GRL1NTB2POWER SUPPLY~(1PHASE)AC115V 60HzGROUNDWIRELESS REMOTE CONTROLLERW.RSW7ONOFFOFFON12324FL3MODE

Pagina 9

OC275-17OPERATION FLOW-CHART9STARTPower circuitbreakerCheck SWON twiceOperation SWON“OFF” timer“ON” timerSTOPSet timecompleteSet timecomplete1NONONONO

Pagina 10 - OC275-10

OC275-18COOL operationInitialCOOLINGNONONONONOYESYESYESYESYESYESNOYESYESYESYESYESYESYESYESYESYESYESNONONONOYESNONONONONONONONONOw 8w 9Vane initialsett

Pagina 11 - OC275-11

OC275-19w8—9 Refer to page OC275-18.w12 When room temperature is 64°F or below, the compressor cannot operate.When room temperature rises over 64°F t

Pagina 12 - OC275-12

OC275-21TECHNICAL CHANGEPK18FL1 ➔ PK18FL3 PK24FL1 ➔ PK24FL3 PK30FL1 ➔ PK30FL3 PK36FL1 ➔ PK36FL3 ● REMOTE CONTROLLER has changed.● INDOOR CONTROLLE

Pagina 13 - OUTLINES AND DIMENSIONS

OC275-2010 MICROPROCESSOR CONTROL1. OUTLINE OF MICROPROCESSOR CONTROL● OFF-ON switching.● COOL • DRY • FAN selector switching.● HIGH-LOW fan speed swi

Pagina 14 - OC275-14

OC275-212. INDOOR UNIT CONTROL2-1COOL operation<COOL operation time chart>ThermostatOperation starts byPOWER buttonON.ONOFFIndoor fanONOFFAuto v

Pagina 15 - REFRIGERANT SYSTEM DIAGRAM

OC275-22(1) Compressor control1 3-minute time delayTo prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor ru

Pagina 16 - WIRING DIAGRAM

OC275-23(3) Auto vane controlAuto vane position is set to 10 degrees airflow at the start-up of COOL operation. It can then be changed by the remoteco

Pagina 17 - OPERATION FLOW-CHART9

OC275-242-2 DRY operation<How to operate>1 Press POWER ON/OFF button.2 Press MODE button to set operation mode to DRY.3 Set desired temperature

Pagina 18 - OC275-18

OC275-25(2) Indoor fan controlThe indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote con-trolle

Pagina 19 - OC275-19

OC275-26<How to operate>1 Press POWER ON/OFF button.2 Press MODE button to set operation mode to FAN.(1) Indoor fan controlThe indoor fan speed

Pagina 20 - 10 MICROPROCESSOR CONTROL

OC275-27Test run Measure an impedance between the power supply terminal block onthe outdoor unit and ground with a 500V Megger and check that it isequ

Pagina 21 - OC275-21

OC275-282-6 Emergency operationWhen the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is starte

Pagina 22 - OC275-22

OC275-29(2) SW2 (Address selector)SW2-1~6) Not for use.1 2 3 4 5 6ONOFF2-7 Dip switch functionsEach figure shows the initial factory setting.1. On ind

Pagina 23 - OC275-23

OC275-3FEATURES21. COMPACT DESIGNThe PK series models have been downsized and now require such minimal wall space that they can even be installedabove

Pagina 24 - OC275-24

OC275-30PK18FL3(6) SW7 (Model selector)Switch to set the output of phase-controlled indoor fan motor.Address setting is available at any time.The init

Pagina 25 - OC275-25

OC275-312-8 Wireless remote controller pair number setting operationON/OFFTEMPFANVANEMODECHECKLOUVERTEST RUN AUTO STOP AUTO STARThminRESETSETCL

Pagina 26 - OC275-26

OC275-3211TROUBLESHOOTING1. Self-diagnostic functionSelf-check1 Turn on the main power to the unit.2 Press the button twice continuously.(Star

Pagina 27 - OC275-27

OC275-33CheckcodeDiagnosis of malfunction Cause Check points4Abnormality of drain sensor 1) Bad contact of transmissionwire2) Damaged thermistor1) Che

Pagina 28 - OC275-28

OC275-343. WRONG WIRING ON SITESymptom due to wrong wiring between indoor and outdoor units4. HOW TO CHECK THE PARTSWrong wiring Thermostat PhenomenaO

Pagina 29 - OC275-29

OC275-35DISASSEMBLY PROCEDURE12OPERATING PROCEDURE PHOTOS&ILLUSTRATIONMetal fixtureScrews1. Removing the lower side of the indoor unit from the in

Pagina 30 - OC275-30

OC275-36OPERATING PROCEDURE PHOTOS&ILLUSTRATION(8) Remove the screws of the indoor controller board case,and pull out the indoor controller board

Pagina 31 - OC275-31

OC275-37OPERATING PROCEDURE PHOTOS8. Removing the line flow fan and the fan motor(1) Remove the left and right side panels. (2) Remove the grilles. (3

Pagina 32 - OC275-32

OC275-3813 PARTS LISTELECTRICAL PARTSPK18FL3PK24FL3 PK30FL3PK36FL3No.Parts No. Parts Name SpecificationsRemarks(Drawing No.)WiringDiagramSymbolQ'

Pagina 33 - OC275-33

OC275-3978910111213141516171819202122232425262728CENTER COVERAUTO VANE WAUTO VANE WDRAIN HOSEVANE MOTORROOM TEMPERATURE THERMISTORPIPE TEMPERATURE THE

Pagina 34 - OC275-34

OC275-43 PART NAME AND FUNCTIONS●Wireless remote controller● When cover is open.ON/OFF TEMPFANVANETEST RUNAUTO STOPAUTO STARThminLOUVERMODECHECKRESE

Pagina 35 - OC275-35

OC275-40STRUCTURAL PARTSPK18FL3PK24FL3PK30FL3PK36FL3Part number that is circled is not shown in the figure.123456789101112SIDE PANEL (L) WUNDER PLATEU

Pagina 36 - OC275-36

3400 Lawrenceville Suwanee Road ● Suwanee, Georgia 30024 Toll Free: 800-433-4822 ● Toll Free Fax: 800-889-9904 www.mrslim.com Specifications ar

Pagina 37 - OC275-37

3400 Lawrenceville Suwanee Road ● Suwanee, Georgia 30024 Toll Free: 800-433-4822 ● Toll Free Fax: 800-889-9904 www.mrslim.com Specifications ar

Pagina 38 - 13 PARTS LIST

OC275-5SPECIFICATIONS4CapacityPower consumptionEERSEERINDOOR UNIT MODELExternal finishPower supplyMax. fuse size (time delay)Min ampacityFan motorAirf

Pagina 39 - OC275-39

OC275-65 DATANotes 1. B.F. : Bypass Factor, IWB : Intake air wet-bulb temperature TC : Total Capacity (x103 Btu/h), SHC : Sensib

Pagina 40 - OC275-40

OC275-7427167637167633036244.54.03.53.02.5023 323545 5565(67) 7585 95 105 115Total capacity (✕103 Btu/h)Total power consumption (kW)Outdoor intake air

Pagina 41 - ● Suwanee, Georgia 30024

OC275-8Data is based on the condition under indoor humidity 50%.Air flow should be set at HI.A point on the curve shows the reference point.PK18FL3<

Pagina 42

OC275-9Data is based on the condition under indoor humidity 50%.Air flow should be set at HI.A point on the curve shows the reference point.Outdoor am