Mitsubishi Electric MUZ-A09YVH-E1 Manual de servicio

Busca en linea o descarga Manual de servicio para Acondicionadores de aire del sistema de división Mitsubishi Electric MUZ-A09YVH-E1. Mitsubishi Electric MUZ-A09YVH-E1 Service manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 24
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
SERVICE MANUAL
CONTENTS
1. PART NAMES AND FUNCTIONS······················2
2. SPECIFICATION·················································4
3. NOISE CRITERIA CURVES·······························5
4. OUTLINES AND DIMENSIONS ·························6
5. WIRING DIAGRAM ············································7
6. REFRIGERANT SYSTEM DIAGRAM················7
7. SERVICE FUNCTIONS ······································8
8. TROUBLESHOOTING······································10
9. DISASSEMBLY INSTRUCTIONS ····················19
10. PARTS LIST······················································21
11. OPTIONAL PARTS···········································23
Wireless type
Models
MSZ-A09YV -
(WH)
MSZ-A12YV -
(WH)
E1
E1
No. OB327
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Indication of model name
MSZ-A09YV -
MSZ-A12YV -
E1
E1
NOTE:
This service manual describes technical data of the indoor units.
•Refer to the service manual OB328 when MSZ-A09YV- or MSZ-A12YV- is connected
with MUZ-A09YV- , MUZ-A12YV- , MUZ-A09YVH- or MUZ-A12YVH- .
•Refer to the service manual OB319 when MSZ-A09YV- or MSZ-A12YV- is connected
with MXZ-A18WV- , MXZ-A26WV- or MXZ-A32WV- as multi system units.
E1E1E1
E1E1
E1E1E1E1
E1E1
OB327 --1qxp 04.1.8 1:41 PM Page 1
Vista de pagina 0
1 2 3 4 5 6 ... 23 24

Indice de contenidos

Pagina 1 - MSZ-A12YV

SERVICE MANUALCONTENTS1. PART NAMES AND FUNCTIONS······················22. SPECIFICATION·················································43. NOISE CRI

Pagina 2 - PART NAMES AND FUNCTIONS

108TROUBLESHOOTING3. Troubleshooting procedure1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an

Pagina 3

115. How to install the horizontal vanesUpper vaneLower vaneIn procedures 2,3,5, and 6, lock the stoppers until they click into place.654321If horizon

Pagina 4 - SPECIFICATION

12StartIndoor unit operates.Outdoor unit doesn't operate.Indoor unit doesn't receive the signal from remote controller.OPERATION INDICATORl

Pagina 5 - NOISE CRITERIA CURVES

13No.1w2456SymptomOperation indicator lamp Detection methodCheck pointLeft lamp flashes.0.5-second ON0.5-second OFFMis-WiringOutdoor power systemOutdo

Pagina 6 - OUTLINES AND DIMENSIONS

142. Trouble criterion of main partsMSZ-A09YV - MSZ-A12YV -E1E1Part name FigureCheck method and criterionIndoor fan motor(MF)INNER FUSE 136i 3:

Pagina 7 - REFRIGERANT SYSTEM DIAGRAM

15Check of indoor electronic control P.C. boardCThe unit doesn’t operate with the remote controller.Also, the OPERATION INDICATOR lamp doesn’t light u

Pagina 8 - SERVICE FUNCTIONS

16How to check mis-wiringDWhen OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second or flashes once.Outdoor unit doesn’t operate.Is there v

Pagina 9

17Check of installation of the horizontal vanesETurn OFF the power supply.Replace the thermal fuse (F12).Is resistance ∞ between the connector CN 201

Pagina 10 - TROUBLESHOOTING

18TEST POINT DIAGRAM AND VOLTAGEMSZ-A09YV - MSZ-A12YV -Indoor electronic control P.C. boardE1E1Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)]Room

Pagina 11 - Operation Indicator

19DISASSEMBLY INSTRUCTIONS9(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal with

Pagina 12

21PART NAMES AND FUNCTIONSACCESSORIES1234567Installation plateInstallation plate fixing screw 4 o 25 mmRemote controller holderFixing screw for 3 3.5

Pagina 13 - Both lamp

20OPERATING PROCEDUREPHOTOS3. Removing the electrical box(1) Remove the panel. (Refer to 1.)(2) Remove the electrical cover. (Refer to 2.)(3) Remove t

Pagina 14 - MSZ-A09YV - MSZ-A12YV

21PARTS LIST10MSZ-A09YV - (WH)MSZ-A12YV - (WH)10-1. INDOOR UNIT STRUCTURAL PARTSE1E1No.Part No.Part nameRemarksSymbolin WiringDiagramQ'ty/unit123

Pagina 15 - Terminal

22No. Part No.Part nameRemarksSymbolin WiringDiagramQ'ty/unit12345678910111213141516171819202122E02 001 504 E02 661 702E02 838 235E02 815

Pagina 16 - How to check mis-wiring

23OPTIONAL PARTS1110-5. AIR CLEANING FILTER● AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.● Normal lif

Pagina 17 - Check of thermal fuse

HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPANCCCopyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistri

Pagina 18 - Resistance (k")

3ON/OFFTOOCOOL PMAMTOOWARMON/OFFFANTOOWARMTOOCOOLVANEMODEECONO COOL STOP STARTHR.MIN.AMPMCLOCK˚CAMRESET CLOCKI FEELCOOLDRYAUTOHEATOpen the

Pagina 19 - DISASSEMBLY INSTRUCTIONS

1.5+ 440V250V 3.15A93:5A 250VMSBPC20 12V 250"ERZV10D471S201DH1Y5PJM1aN-ZTMP-DC12V136:i3: 2AINDOOR UNITItemModelIndoor fan capacitorFuse Thermal f

Pagina 20 - OPERATING PROCEDURE

5NOISE CRITERIA CURVES390807060504030201063 125 250 500 1000 2000 4000 8000NC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.000

Pagina 21 - PARTS LIST10

64OUTLINES AND DIMENSIONSMSZ-A09YV -E1Unit : mmINDOOR UNIT244242 57 or more901103014960627860815783Power supply cordLead to right 1.0mLead to left 0.3

Pagina 22

7WIRING DIAGRAM5REFRIGERANT SYSTEM DIAGRAM6MSZ-A09YV -E1IndoorheatexchangerFlared connectionRoom temperaturethermistorRT11Indoor coil thermistorRT13(

Pagina 23 - OPTIONAL PARTS11

87SERVICE FUNCTIONS7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATIONA maximum of 4 indoor units with wireless remote controllers can be used in a

Pagina 24

9NOTE:• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remotecontroller.• If main power