CITY MULTI
DATA U10
SYSTEM DESIGN H2i Y SERIES
SYSTEM DESIGN H2i Y SERIES
1. Electrical work.................................................................................................................................................. 4 - 86
1-1.General cautions ....................................................................................................................................... 4 - 86
1-2.Power supply for Indoor unit and Outdoor unit .......................................................................................... 4 - 87
1-3.Power cable specifications ........................................................................................................................ 4 - 89
1-4.Power supply examples............................................................................................................................. 4 - 90
2. M-NET control.................................................................................................................................................. 4 - 92
2-1.Transmission cable length limitation.......................................................................................................... 4 - 92
2-2.Transmission cable specifications ............................................................................................................. 4 - 93
2-3.System configuration restrictions............................................................................................................... 4 - 94
2-4.Address setting.......................................................................................................................................... 4 - 97
3. Piping Design................................................................................................................................................... 4 - 110
3-1.R410A Piping material............................................................................................................................... 4 - 110
3-2.Piping Design ............................................................................................................................................ 4 - 110
3-3.Refrigerant charging calculation ................................................................................................................ 4 - 112
4. Outdoor Installation.......................................................................................................................................... 4 - 113
4-1.Requirement on installation site ................................................................................................................ 4 - 113
4-2.Spacing...................................................................................................................................................... 4 - 114
4-3.Piping direction .......................................................................................................................................... 4 - 116
4-4.Weather countermeasure .......................................................................................................................... 4 - 121
4-5.Caution on selecting outdoor units ............................................................................................................ 4 - 122
5. Installation information..................................................................................................................................... 4 - 123
5-1.General precautions .................................................................................................................................. 4 - 123
5-2.Precautions for Indoor unit ........................................................................................................................ 4 - 124
5-3.Precautions for Outdoor unit/Heat source unit .......................................................................................... 4 - 125
5-4.Precautions for Control-related items ........................................................................................................ 4 - 126
6. Caution for refrigerant leakage ........................................................................................................................ 4 - 127
6-1.Refrigerant property................................................................................................................................... 4 - 127
6-2.Confirm the Critical concentration and take countermeasure.................................................................... 4 - 127
Vista de pagina 0
1 2 3 4 5 6 ... 42 43

Indice de contenidos

Pagina 1 - SYSTEM DESIGN H2i Y SERIES

4 - 85CITY MULTIDATA U10SYSTEM DESIGN H2i Y SERIESSYSTEM DESIGN H2i Y SERIES1. Electrical work...

Pagina 2 - 1. Electrical work

2. M-NET controlDATA U10SYSTEM DESIGN 4 - 94S.D. H2i Y2-3. System configuration restrictions For each Outdoor unit, the maximum connectable quantity o

Pagina 3

4 - 952. M-NET controlDATA U10SYSTEM DESIGNS.D. H2i Y The power to System controller (excluding LM-AP) is supplied via M-NET transmission line. M-NET

Pagina 4

2. M-NET controlDATA U10SYSTEM DESIGN 4 - 96S.D. H2i Y1-phase 208-230V AC power supply is needed.The power supply unit PAC-SC51KUA is not necessary wh

Pagina 5

4 - 972. M-NET controlDATA U10SYSTEM DESIGNS.D. H2i Y2-4. Address settingBranchNo. settingUnit address No. settingRotary switchIn order to constitute

Pagina 6

2. M-NET controlDATA U10SYSTEM DESIGN 4 - 98S.D. H2i Y2-4-2. Rule of setting addressUnitIndoor unitME, LOSSNAYRemote controller(Main)ME, LOSSNAYRemote

Pagina 7

4 - 992. M-NET controlDATA U10SYSTEM DESIGNS.D. H2i YDipSW2-1(Outdoor) : When the System Remote Controller is used, all the Dip SW2-1 at the outdoor

Pagina 8 - S.D. H2i Y

2. M-NET controlDATA U10SYSTEM DESIGN 4 - 100S.D. H2i Y2. Address should be set to Indoor units and central controller.3. For a system having more tha

Pagina 9 - SYSTEM DESIGN

4 - 1012. M-NET controlDATA U10SYSTEM DESIGNS.D. H2i Y2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7 side, Booster

Pagina 10 - System example

2. M-NET controlDATA U10SYSTEM DESIGN 4 - 102S.D. H2i Y2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller2-4-3-5. ME remot

Pagina 11 - 2. M-NET control

4 - 1032. M-NET controlDATA U10SYSTEM DESIGNS.D. H2i Y2-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY,

Pagina 12

1. Electrical workDATA U10SYSTEM DESIGN 4 - 86S.D. H2i YI.1. Electr ical work1-1. General cautionsOK NOFollow ordinance of your governmental organizat

Pagina 13

2. M-NET controlDATA U10SYSTEM DESIGN 4 - 104S.D. H2i YNOTE It is necessary to change the connecter to CN40 on the outdoor unit control board (only o

Pagina 14

4 - 1052. M-NET controlDATA U10SYSTEM DESIGNS.D. H2i YPUHY-P-TSJMU/YSJMU PUHY-P-TSJMU/YSJMU PUHY-P-TJMU/YJMUPUHY-P-TSJMU/YSJMU PUHY-P-TSJMU/YSJMU PUHY

Pagina 15

2. M-NET controlDATA U10SYSTEM DESIGN 4 - 106S.D. H2i Y2-4-3. System examples2-4-3-10. AG-150A-A + PAC-YG50ECA (Expansion controller)AG-150A-A can con

Pagina 16

4 - 1072. M-NET controlDATA U10SYSTEM DESIGNS.D. H2i Y2-4-3-11. LM-APLM-AP(01)24VDCPCLONWORKS® cardLONWORKS® cardLONWORKS® cardFor other equipments (L

Pagina 17

2. M-NET controlDATA U10SYSTEM DESIGN 4 - 108S.D. H2i Y2-4-3-12. BM ADAPTERBM ADAPTER(01)HUBFor other equipments (Lighting, security, elevator etc.)BM

Pagina 18

4 - 1092. M-NET controlDATA U10SYSTEM DESIGNS.D. H2i YPAC-YG50ECA *4BM ADAPTER can transmit for max. 50 indoor units in single-refrigerant-system or m

Pagina 19

3. Piping DesignDATA U10SYSTEM DESIGN 4 - 110S.D. H2i Y3. Piping Desi gn3-1. R410A Piping materialThe maximum operation pressure of R410A air conditio

Pagina 20

4 - 1113. Piping DesignDATA U10SYSTEM DESIGNS.D. H2i YTable3-2-2-4. R410A Selection criteria for joints (second and successive branches) Total down-

Pagina 21

3. Piping DesignDATA U10SYSTEM DESIGN 4 - 112S.D. H2i Y3-3. Refrigerant charging calculation(1) Calculation of additional refrigerant charge Calcul

Pagina 22

4 - 1134. Outdoor InstallationDATA U10SYSTEM DESIGNS.D. H2i Y4. Outdoor Installation4-1. Requirement on installation site1. No direct thermal radiati

Pagina 23

4 - 871. Electrical workDATA U10SYSTEM DESIGNS.D. H2i Y1-2. Power supply for Indoor unit and Outdoor unit1-2-1. Electrical characteristics of Indoor u

Pagina 24

4. Outdoor InstallationDATA U10SYSTEM DESIGN 4 - 114S.D. H2i Y4-2. Spacing1000[39-3/8]240 [9-15/32]45°50 [1-31/32]<C>(Unit : mm [in.])<B>5

Pagina 25

4 - 1154. Outdoor InstallationDATA U10SYSTEM DESIGNS.D. H2i YIn case of collective installation and continuous installation:: Wall height (H)(Unit :

Pagina 26 - 3-2. Piping Design

4. Outdoor InstallationDATA U10SYSTEM DESIGN 4 - 116S.D. H2i Y4-3. Piping direction4-3-1. Lifting method· When lifting the unit with ropes, run the ro

Pagina 27 - Trap (gas

4 - 1174. Outdoor InstallationDATA U10SYSTEM DESIGNS.D. H2i Y4-3-2. Installation30mm [1-3/16in]Install the unit in such a way that the corner of the a

Pagina 28 - 3. Piping Design

4. Outdoor InstallationDATA U10SYSTEM DESIGN 4 - 118S.D. H2i Y4-3-5. Refrigerant pipe routing4-3-4. InstallationInstallation base perpendicular to the

Pagina 29 - 4. Outdoor Installation

4 - 1194. Outdoor InstallationDATA U10SYSTEM DESIGNS.D. H2i Y4-3-6. Twinning on the outdoor unit sideReducer±15°The tilt angle of the reducer should b

Pagina 30

4. Outdoor InstallationDATA U10SYSTEM DESIGN 4 - 120S.D. H2i YField pipingField pipingTwinning kitThe length of the straight pipe must be 500 mm [19 i

Pagina 31

4 - 1214. Outdoor InstallationDATA U10SYSTEM DESIGNS.D. H2i Y4-4. Weather countermeasure• Snow hoodCountermeasure to windOutletInletReferring to the f

Pagina 32

4. Outdoor InstallationDATA U10SYSTEM DESIGN 4 - 122S.D. H2i Y4-5. Caution on selecting outdoor unitsConsult your dealer when the following issues on

Pagina 33

4 - 1235. Installation informationDATA U10SYSTEM DESIGNS.D. H2i Y5. Installation in formation5-1. General precautions5-1-1. UsageThe air-conditioning

Pagina 34 - Fill the gap at the site

1. Electrical workDATA U10SYSTEM DESIGN 4 - 88S.D. H2i YSymbols: MCA : Minimum Circuit Ampacity (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Moto

Pagina 35 - 200mm [7 in.]

5. Installation informationDATA U10SYSTEM DESIGN 4 - 124S.D. H2i Y5-1-6. Unit installationYour local distributor or a qualified technician must read

Pagina 36

4 - 1255. Installation informationDATA U10SYSTEM DESIGNS.D. H2i Y5-3. Precautions for Outdoor unit/Heat source unit5-3-1. Installation environmentOut

Pagina 37

5. Installation informationDATA U10SYSTEM DESIGN 4 - 126S.D. H2i Y5-4. Precautions for Control-related items5-4-1. Product specificationTo introduce

Pagina 38

4 - 1276. Caution for refrigerant leakageDATA U10SYSTEM DESIGNS.D. H2i Y6. Caution for refrigerant leakageThe installer and/or air conditioning system

Pagina 39 - 5-1-5. Relevant equipment

4 - 891. Electrical workDATA U10SYSTEM DESIGNS.D. H2i Y1-3. Power cable specificationsPUHY-HP-T(S)JMUSymbols: MCA : Minimum Circuit AmpacitySC :

Pagina 40 - 5. Installation information

1. Electrical workDATA U10SYSTEM DESIGN 4 - 90S.D. H2i Y1-4. Power supply examplesNote4Note3To *1 or *2*1*2Note8Connector CN41 CN40Power supply3-pha

Pagina 41 - 5-3-4. Relevant equipment

4 - 911. Electrical workDATA U10SYSTEM DESIGNS.D. H2i YPower supply3-phase 3-wire208-230V 60HzNote11,13Breakers forcurrent leakageSwitchPower supply3-

Pagina 42 - 5-4-1. Product specification

2. M-NET controlDATA U10SYSTEM DESIGN 4 - 92S.D. H2i Y2. M-NET control2-1. Transmission cable length limitationLong transmission cable causes voltage

Pagina 43 - 6-1. Refrigerant property

4 - 932. M-NET controlDATA U10SYSTEM DESIGNS.D. H2i Y2-2. Transmission cable specificationsType of cableCable sizeRemarksSheathed 2-core cable (unshie

Comentarios a estos manuales

Sin comentarios