Air-Conditioners For Building ApplicationINDOOR UNITPFFY-P•VKM-E (2)INSTALLATION MANUALFor safe and correct use, read this manual and the outdoor unit
Please be sure to put the contact address/telephone number on this manual before handing it to the customer.This product is designed and intended for
GB2► Before installing the unit, make sure you read all the “Safety precau-tions”.► Please report to your supply authority or obtain their consent bef
GB33. Installing the indoor unit3.1. Indoor unit mounting bracket installation• Install the bracket firmly to the wall structure (stud, etc.). (Fig.
GB43. Installing the indoor unit2) For right downward or left downward piping (Fig. 3-8)(The following figure is a view of the bottom of the indoor u
GB54. Refrigerant pipe1) For right downward piping (Fig. 4-3)2) For piping other than right downward (Fig. 4-4) A Bands B Pipe covers C Remove the cov
GB65. Drainage piping work• Insert the drain hose all the way to the base of the drain pan. (Fig. 5-4) Make sure that the drain hose is securely caug
GB7M1M2STB2 TB5L N7. Electrical work7.2. Power supply wiring• Wiring size must comply with the applicable local and national codes.•
GB812345678910ONOFFSW1SW5220V 240VCN82CN43SW14SWC./.(BRANCH No.)0123456789ABCDEFSW11SW1201234567890123456789(10ths DIGIT)(1s DIGIT)Fig. 7-47.5. Setti
GB9DisplayActual1234gniwS).ziroH(123 4(Horiz.) Swing8. Test run• The lower air outlet damper automatically opens and closes according to the piping te