DATA BOOKAIR CONDITIONERSMODELPQHY-P Y(S)HM-APQRY-P Y(S)HM-A- For ground source application
- 6 -*1*2-plate type Heat exchangerOver-heat protectionAcrylic painted steel platelType x original chargeControl5.7627,100Circulating water°C connecta
- 96 -(10)-4 Connection with PWFY-P100VM-E-BU (Booster unit) + WCB Energy saving mode**For energy saving mode, set WCB DIP SW 6-5 ON.0.70.80.91.01.11.
- 97 -(11) Correction by water flow rate (For heat source unit)(11)-1 Connection with standard CITY MULTI indoor units(11)-2 Connection with PWFY-P100
- 98 -(12) Correction by indoor temperature(12)-1 Connection with standard CITY MULTI indoor units(12)-2 Connection with PWFY-P100/200VM-E-AU (HEX uni
- 99 -(13)-2 Connection with PWFY-P200VM-E-AU (HEX unit)(13)-3 Connection with PWFY-P100VM-E-BU (Booster unit)CoolingHeating1.0 1.5 2.0 2.5 3.0 3.5 4.
- 100 -(14) Water pressure drop correction by water volume (14)-1 Heat source unit correction(Connection with Standard CITY MULTI indoor units, PWFY-P
- 101 -(14)-4 Water pressure drop of strainer only (accessory for PWFY-P100VM-E-BU and PWFY-P100/200VM-E-AU)010203040Water flow rate [m3/h]Water-press
- 102 -(15) Operation temperature range(15)-1 Connection with standard CITY MULTI indoor unitsCoolingHeatingCombination of cooling/heating operation (
- 103 -((15)-3 Connection with PWFY-P100/200VM-E-AU (HEX unit)CoolingHeating0102030405032506886104122Heat source unit (WR2) circulating water temperat
- 104 -(16) Piping design(16)-1 R410A Piping material Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types
- 105 -(16)-2 PQRY-P200-300YHM Piping IF 16 ports or less are in use, i.e., if only one BC controller is in use with no sub BC controller(Connection w
- 7 -*1*2-plate type Heat exchangerOver-heat protectionAcrylic painted steel platelType x original chargeControl5.7632,300Circulating water°C connecta
- 106 -(16)-3 PQRY-P200-300YHM Piping IF more than 16 ports are in use, or if there is more than one BC controller in use for one Heat source unit(Con
- 107 -(16)-4 PQRY-P400YHM Piping IF more than 16 ports are in use, or if there is more than one BC controller in use for two heat source units (Conne
- 108 -(16)-5 Total piping length restrictions200300400500600700800900100010 20 30 40 50 60 70 80 90 100 110Distance between heat source unit and BC c
- 109 -(16)-6 Refrigerant charging calculationSample connection (with 3 BC controller and 6 indoor units)Amount of additional refrigerant to be charge
DATA BOOK PQHY-P Y(S)HM-APQRY-P Y(S)HM-A- For ground source applicationMEE09K040New publication effective Sep.2010Specifications subject to change wi
- 8 -*1*2Heat Source Twinning kit: CMY-Y100VBK29.52(3/8) Brazed-1.05.01.0Over-heat protection, Over-current protection Over-heat protection, Over-curr
- 9 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping diam
- 10 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 11 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 12 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 13 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 14 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 15 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
iPrefaceDATABOOK describes the technical specifications of MITSUBISHI ELECTRIC Corp.'s CITYMULTI air conditioning system products.In this DATABOO
- 16 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 17 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 18 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 19 -(1)-2 System specification for closed control system (PFD-P250/500VM-E)IndoorHeat sourceHeating31.5kW8.01kW14.6 / 13.8 / 13.4 A-kWAm / min3Pa
- 20 -IndoorHeat sourceHeating63.0kW16.02kW28.1 / 26.6 / 25.7 A-kWAm / min3PakWmmLiquid pipeGas pipemdB(A)kgHeatingIndoor : 15°CDB ~ 28°CDBCirculating
- 21 -(2) External dimensionPQHY-P200,250,300YHM-AService space(front side)Service space(front side)Top view550606020741160(60)The space forcontrol bo
- 22 -PQHY-P400,450,500,550,600YSHM-A11005501780880 88020dcefTo indoor unitLiquid Twinning pipe <optional parts>Gas Twinning pipe <optional p
- 23 -PQHY-P650,700,750,800,850,900YSHM-AUnit : mmø34.93ø 19.05ø19.05PQHY-P250YHM-APQHY-P250YHM-APQHY-P700YSHM-APQHY-P750YSHM-APQHY-P250YHM-APQHY-P250
- 24 -(3) Center of gravityPQHY-P200,250,300YHM-AModel X Y Z418[16-8/16] 250[9-14/16]418[16-8/16] 250[9-14/16]532[21]532[21]PQHY-P200YHM-A[-BS]418[16-
- 25 -(4) Electrical wiring diagramPQHY-P200,250,300YHM-A~CNAC431CN83CNOUT2432165CNPW421753t TH312CN212t TH612t THINVCNTYP1blackLEVINVCNLVE123456LEV2b
Contents I Brine information1. Brine freezing temperature ...
- 26 -(5) Sound levels1m1mMeasurementlocationMeasurement conditionPQHY-P200,250,300YHM-A63 125 250 500 1k 2k 4k 8k dB(A)Standard50/60Hz 65.0 55.5 49.0
- 27 -1m1mMeasurementlocationMeasurement conditionPQHY-P400,450,500,550,600YSHM-A63 125 250 500 1k 2k 4k 8k dB(A)Standard50/60Hz 64.0 57.0 51.0 46.5 4
- 28 -MeasurementlocationMeasurement conditionPQHY-P650, 700, 750, 800, 850YSHM-A1m1m63 125 250 500 1k 2k 4k 8k dB(A)Standard50/60Hz 65.5 58.5 52.5 48
- 29 -MeasurementlocationMeasurement conditionPQHY-P900YSHM-A1m1m63 125 250 500 1k 2k 4k 8k dB(A)Standard50/60Hz 70.0 60.5 54.0 49.0 43.5 44.5 48.5 41
- 30 -(6) Capacity tables with indoor units(6)-1 Cooling capacity with standard indoor unitsPEFY-P-VMH-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(
- 31 -PEFY-P-VMR-E-L/RCA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64
- 32 -PEFY-P-VMS1(L)-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64
- 33 -PEFY-P-VMA(L)-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°
- 34 -PMFY-P-VBM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 35 -PLFY-P-VLMD-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FW
3. PQRY-P-Y(S)HM-A ... 63(1)Specific
- 36 -PLFY-P-VCM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 37 -PLFY-P-VBM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 38 -PCFY-P-VKM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 39 -PKFY-P-VBM-E,VHM-E,VKM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°
- 40 -PFFY-P-VKM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 41 -PFFY-P-VLEM-E,VLRM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB
- 42 -PFFY-P-VLRMM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°F
- 43 -(6)-2 Heating capacity with standard indoor unitsSHC:Sensible Heat Capacity(kW) SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.
- 44 -(7) Correction by total indoorCapacity(kW)Input(kW)Total capacity of indoor units100 200 300 400100 200 300 400Total capacity of indoor unitsTot
- 45 -Capacity(kW)Input(kW)Total capacity of indoor unitsTotal capacity of indoor unitsTotal capacity of indoor unitsCapacity(kW)Input(kW)Total capaci
- 1 - I Brine information1.Brine freezing temperatureBrine concentration is decided by the freezing temperature. First, it is necessary to deci
- 46 -(8) Correction by refrigerant piping lengthCoolingPiping equivalent length (m)1.000.900.800.950.850.750.650.70Cooling capacity correction factor
- 47 -Piping equivalent length (m)Cooling capacity correction factorPQHY-P650YSHM-APiping equivalent length (m)Cooling capacity correction factorPQHY-
- 48 -HeatingPiping equivalent length (m)1.000.900.800.950.850.750.650.70Cooling capacity correction factor0 20406080100120140160180PQHY-P200YHM-APipi
- 49 -(9) Correction by water temperature (For heat source unit)(9)-1 Connection with standard CITY MULTI indoor units(9)-2 Connection with PWFY-P100
- 50 -(9)-3 Connection with PFD-P250/500VM-ECoolingHeat source unit (WY) inlet-water temp. [°C]Ratio of Heat source unit cooling capacity/inputCapacit
- 51 -(10) Correction by water flow rate (For heat source unit)(10)-1 Connection with standard CITY MULTI indoor units(10)-2 Connection with PWFY-P100
- 52 -(11) Correction by indoor temperature(11)-1 Connection with standard CITY MULTI indoor units(11)-2 Connection with PWFY-P100/200VM-E-AU (HEX uni
- 53 -(12) Correction by water flow rate (For PWFY-P100/200VM-E-AU (HEX unit))(12)-1 Connection with PWFY-P100VM-E-AU (HEX unit)(12)-2 Connection with
- 54 -(13) Water pressure drop correction by water volume (13)-1 Heat source unit correction (Connection with Standard CITY MULTI indoor units, PWFY-
- 55 -(14) Operation temperature range(14)-1 Connection with standard CITY MULTI indoor unitsCoolingHeating(14)-2 Connection with PWFY-P100/200VM-E-AU
- 2 -2.Capacity correction by brine concentration (For heat source unit)Depending on the freezing temperature and brine concentration, the ratio of un
- 56 -(14)-3 Connection with PFD-P250/500VM-ECoolingHeating3025201510867768595041 5-10 -5 0 5 10 15 20 25 30 35 40 45 50Indoor temperatureHeat source
- 57 -(15) Piping design(15)-1 R410A Piping material Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types.
- 58 -(15)-2 PQHY-P200-300YHM Piping (Connection with standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU)Table15-2-6. R410A Joint selection rule
- 59 -(15)-3 PQHY-P400-600YSHM Piping (Connection with standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU)Table15-3-6. R410A Joint selection rule
- 60 -(15)-4 PQHY-P650-900YSHM Piping (Connection with standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU)Table15-4-6. R410A Joint selection rule
- 61 -(15)-5 PQHY-P250/P250+P250YHM (Connection with PFD indoor unit)Note1. As bents cause pressure loss on transportation of refrigerant, fewer bents
- 62 -(15)-6 Refrigerant charging calculationSample connection(with 8 indoor units)Amount of refrigerant to be chargedRefrigerant for extended pipes (
- 63 -3.PQRY-P-Y(S)HM-A(1)Specification(1)-1 Heat source units specification for standard combination (Standard CITY MULTI indoor units, PWFY-P100VM
- 64 -*1*2 Optional parts RefrigerantACurrent inputkWAkWPOC kW / kWkWkcal / h*2 BTU / hPower inputkW / kWW.B.Sound pressure level (measured in anechoi
- 65 -*1*2 Optional parts RefrigerantACurrent inputkWAkWPOC kW / kWkWkcal / h*2 BTU / hPower inputkW / kWW.B.Sound pressure level (measured in anechoi
- 3 -3.Pressure drop correction by brine concentration (For heat source unit)Also, water pump is selected by the ratio of pressure drop of depending o
- 66 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 67 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 68 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 69 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 70 -*1*2Wkretaeh esaCWktuptuo rotoMin.ControlCirculating water°C Set Model Model connectableModel / Quantity heating Model Total capacity piping dia
- 71 -(2) External dimensionPQRY-P200,250,300YHM-AService space(front side) Service space(front side)Top view550606020741160(60)The space forcontrol b
- 72 -PQRY-P400,450,500,550,600YSHM-A11005501780880 88020cedTo BC controllerTo BC controllerbaTwinning pipe (High pressure)<optional parts>Twinn
- 73 -(3) Center of gravityPQRY-P200,250,300YHM-AModel X Y Z423(16-11/16) 253(10)423(16-11/16) 253(10)524(20-11/16)524(20-11/16)PQRY-P200YHM-A(-BS)423
- 74 -(4) Electrical wiring diagramPQRY-P200,250,300YHM-A~CNAC431CN83CNOUT2432165CNPW42175CN510yellowCN509blue3CNOUT1yellowblueyellowredorange41123456
- 75 -(5) Sound levels1m1mMeasurementlocationMeasurement conditionPQRY-P200,250,300YHM-A63 125 250 500 1k 2k 4k 8k dB(A)Standard50/60Hz 65.0 55.5 49.0
- 4 - II Heat source unit information1.General lineup of water-cooled heat source unitWY (Heat Pump) Series (8HP-36HP)PQHY-P YHM-APQHY-P YSHM-A
- 76 -1m1mMeasurementlocationMeasurement conditionPQRY-P400,450,500,550,600YSHM-A63 125 250 500 1k 2k 4k 8k dB(A)Standard50/60Hz 64.0 57.0 51.0 46.5 4
- 77 -(6) Capacity tables with indoor units(6)-1 Cooling capacity with standard indoor unitsPEFY-P-VMH-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(
- 78 -PEFY-P-VMR-E-L/RCA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64
- 79 -PEFY-P-VMS1(L)-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64
- 80 -PEFY-P-VMA(L)-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°
- 81 -PMFY-P-VBM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 82 -PLFY-P-VLMD-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FW
- 83 -PLFY-P-VCM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 84 -PLFY-P-VBM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 85 -PCFY-P-VKM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 5 -2.PQHY-P-Y(S)HM-A(1)Specification(1)-1 Heat source units specification for standard combination (Standard CITY MULTI indoor units, PWFY-P100/200
- 86 -PKFY-P-VBM-E,VHM-E,VKM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°
- 87 -PFFY-P-VKM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°FWB
- 88 -PFFY-P-VLEM-E,VLRM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB
- 89 -PFFY-P-VLRMM-ECA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.size 71°FDB / 59°FWB 73°FDB / 61°FWB 77°FDB / 64°F
- 90 -(6)-2 Heating capacity with standard indoor unitsSHC:Sensible Heat Capacity(kW) SHC:Sensible Heat Capacity(kW)ModelWater temp.Indoor air temp.
- 91 -(7) Correction by total indoorapaCytic)Wk(tupnI)Wk(Total capacity of indoor units100 200 300 400Total capacity of indoor unitsTotal capacity of
- 92 -(8) Correction by refrigerant piping lengthCoolingPiping equivalent length (m)1.000.900.800.950.850.750.650.70Cooling capacity correction factor
- 93 -Heating(9) Correction by port counts of the BC controller Indoor unit sizes P200 and P250 must be connected to 2 ports on the BC controller.Indo
- 94 -(10) Correction by water temperature (For heat source unit)(10)-1 Connection with standard CITY MULTI indoor units(10)-2 Connection with PWFY-P1
- 95 -(10)-3 Connection with PWFY-P100VM-E-BU (Booster unit)0.70.80.91.01.11.2-5 0 5 15 20 2510 30 35 40 45Heat source unit (WR2) inlet-water temp.[°C