Pagina 2 - Safety Precautions

- 1 -I General Eq uipment Descriptio ns (PEFY- AF1200CFM R) I General Equipment Descriptions1. Unit configuration table*PFD-type indoor units c

Pagina 3

- 2 -When using a PFD-P500VM-E as an indoor unit, connect 2 PUHY-P250YJM-A/PQHY-P250YHM-A outdoor units to an indoor unit and operate with a built-in

Pagina 4

- 3 -2. Operable temperature rangePFD unit + PUHY-P250YJM-A, PUHY-P500YSJM-APFD unit + PQHY-P250YHM-A* The height between the Outdoor PUHY-P-YJM-A and

Pagina 5 - Before installing the unit

- 4 -II Product Specifications (PEF Y-AF1200CFMR) II Product Specifications1. Specifications(1) Indoor unit(2) Outdoor unit/Heat source unit3N~3

Pagina 6

- 5 -56.0 63.03N ~ 380/400/415V 50/60HzCapacityModel namekWPower source*1*2kWAm3/minkWkWkWmmdB(A)kgPower inputCurrentSet ModelFanAirflow rateType x Q

Pagina 7 - Before the test run

- 6 -2. External Dimensions(1) Indoor unitPFD-P250VM-EUnit : mm3905050100Note 1. Be sure to set up a trap for Emergency drain piping. (Trap heigh

Pagina 8 - CONTENTS

- 7 -PFD-P500VM-E50100140505039010068124135Note 1. Be sure to set up a trap for Emergency drain piping. (Trap height:beyond 100mm) (Trap is no

Pagina 9

- 8 -(2) Outdoor unit/Heat source unitPUHY-P250YJM-A(-BS)Unit : mmFor transmission cablesFor wiresFor pipesSpecificationsUsageNO.<Accessories>C

Pagina 10 - 1. Unit configuration table

- 9 -PUHY-P500YSJM-A(-BS)Unit : mmø9.52 ø22.2(60) 16501710IntakeairOutdoor unit 2Outdoor unit 1IntakeairIntakeairLeft viewTo indoor unitFront viewcdba

Pagina 11

- 10 -PQHY-P250YHM-AUnit : mmService space(front side)Service space(front side)Top viewThe space forcontrol boxreplacement4506001703507256004501701100

Pagina 12 - 2. Operable temperature range

Safety PrecautionsBefore installing the unit, thoroughly read the following safety precautions.Observe these safety precautions for your safety.WAR

Pagina 13 - 1. Specifications

- 11 -3. Center of Gravity(1) Indoor unitPFD-P250VM-EPFD-P500VM-EYLXZYLXZModel L X Y ZPFD-P500VM-E 580 967 270 714Model L X Y ZPFD-P250VM-E 580 581 22

Pagina 14

- 12 -(2) Outdoor unit/Heat source unitPUHY-P250YJM-A (-BS)PQHY-P250YHM-AModel X Y ZPUHY-P250YJM-A (-BS) 334 329 652110060550880506YXZ116080720Model

Pagina 15 - 2. External Dimensions

- 13 -4. Electrical Wiring Diagrams(1) Indoor unitPFD-P250VM-EuNote: 1. The dotted lines show field wiring. 2. The address setting of the indoor unit

Pagina 16

- 14 -PFD-P500VM-Etttttttt1. The dotted lines show field wiring.2. It is wiring for single refrigerant system at the time of shipping. Chan

Pagina 17 - PUHY-P250YJM-A(-BS)

- 15 -(2) Outdoor unit/Heat source unitPUHY-P250YJM-A (-BS)+-++++21+++++3322Heat exchanger capacity controlCooling/Heating switching21S4b63HS1SV9SV5b

Pagina 18 - Discharge air

- 16 -PQHY-P250YHM-A~CNAC431CN83CNOUT2432165CNPW421753tTH312CN212t TH612t THINVCNTYP1blackLEVINVCNLVE123456LEV2bCNLVC red123456CN510yellowCN509blue3CN

Pagina 19 - Fig. BFig. A

- 17 -5. Optional Parts(1) Outdoor unitOutdoor twinning kitThe following optional Outdoor Twinning Kit is needed to use to combine multiple refrigeran

Pagina 20 - 3. Center of Gravity

- 18 -III Product Data (PEFY-A F1200CFMR ) III Product Data1. Capacity Curves(1) Correction by temperaturePUHY-P250YJM-A, PUHY-P500YSJM-APQHY-P2

Pagina 21

- 19 -(2) Part Load PerformancePFD unit +PUHY-P250YJM-A, PUHY-P500YSJM-APFD unit +PQHY-P250YHM-A10HP SystemIndoor Unit : PFD-P250VM-EOutdoor Unit

Pagina 22 - 4. Electrical Wiring Diagrams

- 20 -(3) Correction by refrigerant piping lengthTo obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by th

Pagina 23

WARNINGSecurely attach the terminal block cover (panel) to the unit.If the terminal block cover (panel) is not installed properly, dust and/or water m

Pagina 24 - <Symbol explanation>

- 21 -(5) SHF Curves0.40.50.60.70.80.9130 40 50 60 70 80RH (%)SHF130% 120%110% 100% 90% 80% 70%Standard Capacity Ratio Standard Capacity Ratio0.930.40

Pagina 25

- 22 -2. Sound Levels(1) Measurement condition1m1mSeriesSound pressure level(dB [Type A])PFD-P250VM-E 59PFD-P500VM-E 63SeriesSound pressure level(dB [

Pagina 26 - CMY-Y100VBK2

- 23 -(2) NC Curves102030405060708090Octave band sound level (dB)PUHY-P500YSJM-A63 125 250 500 1k 2k 4k 8kNC-40NC-30NC-20NC-60NC-50NC-70Octave band ce

Pagina 27 - III Product Data

- 24 -3. Fan Characteristics CurvesB52B481170B55B491140B54B501080B54B511040B55B52973B56B54930B60B54845B59B57797-B56748Note1 Pulley and V-belt is procu

Pagina 28 - (2) Part Load Performance

- 25 -NominalDiameter (A)<Ø>Motor pulleyOutsideDiameter (C)<Ø>(D)<Ø>(E)<mm>Bore (B)<Ø>1601651701801601651701801711761811

Pagina 29

- 26 -Horizontal pulley alignment and proper belt tension1) The fan pulley and the motor pulley must be aligned to meet the criteria shown in Fig. 3

Pagina 30 - Outdoor : 35°CDB /

- 27 -IV Piping Desi gn (PEFY-AF1200C FMR) IV System Design1. Piping Design(1) PFD-P250VM-ENote1. If the PUHY system is designed to use cooling mo

Pagina 31 - Heat source unit

- 28 -(2) PFD-P500VM-E (two refrigerant circuit system)Table: IV-1-(2)-2. Bent equivalent length "M"M (m/bent)Outdoor ModelPQHY-P250 0.42Ta

Pagina 32 - (2) NC Curves

- 29 -(3) PFD-P500VM-E (single refrigerant circuit system)IUOutdoor Twinning KitCMY-Y100VBK2Note1. If the A/C system is designed to use cooling mode

Pagina 33 - 3. Fan Characteristics Curves

- 30 -(4) Refrigerant charging calculationCAUTIONCharge Liquid RefrigerantFilling the equipment with gas refrigerant will result in a power loss due t

Pagina 34 - (keyway)

Precautions for handling units for use with R410ACAUTIONDo not use the existing refrigerant piping.A large amount of chlorine that may be contained

Pagina 35 - C:Center distance (mm)

- 31 -2. Designing of water circuit system(1) Example of basic water circuitThe water circuit of the water heat source CITY MULTI connects the heat so

Pagina 36 - IV System Design

- 32 -(2) Cooling towera) Types of cooling towerThe cooling towers presently used include the open type cooling tower, open type cooling tower + heat

Pagina 37

- 33 -(3) Auxiliary heat source and heat storage tankWhen the heating load is larger than the cooling load, the circulation water temperature lowers

Pagina 38 - Fig.IV-1-(3)A: Piping scheme

- 34 -When heat storage tank is not used HQ1T • ( 1 - ) - 860 x Pw x T2 QH =

Pagina 39 - Charge Liquid Refrigerant

- 35 -b) Heat storage tankHeat storage tank can be classified by types into the open type heat storage tank exposed to atmosphere, and the closed type

Pagina 40

- 36 -(4) Piping systemThe following items should be kept in your mind in planning / designing water circuits.a) All units should be constituted in a

Pagina 41 - Air-cooled type

- 37 -(5) Practical System Examples and Circulation Water ControlSince the water heat source CITY MULTI is of water heat source system, versatile sys

Pagina 42

- 38 -Example-2 Combination of closed type cooling tower and hot water heat storage tankIn the summer, as the circulation water temperature rises exce

Pagina 43 - ( 1

- 39 -Example-3 Combination of closed type cooling tower and boilerIn the summer, as the circulation water temperature rises exceeding the set tempera

Pagina 44

- 40 -Example-4 Combination of closed type cooling tower and heat exchanger (of other heat source)In the summer, as the circulation water temperature

Pagina 45

Before installing the unitWARNINGDo not install the unit where a gas leak may occur.If gaseous refrigerant leaks and piles up around the unit, it may

Pagina 46

- 41 -(6) Pump interlock circuitOperating the heat source unit without circulation water inside the water piping can cause a trouble.Be sure to provid

Pagina 47

- 42 -3. Water piping workAlthough the water piping for the CITY MULTI WY system does not differ from that for ordinary air conditioning systems, pay

Pagina 48

- 43 -4. Control WiringRestrictions when the PFD-type indoor units are connected (related to the system) The PFD-type indoor units cannot be connecte

Pagina 49

- 44 -5. Types of switch settings and setting methodsWhether a particular system requires switch settings depends on its components. Refer to the sect

Pagina 50 - (6) Pump interlock circuit

- 45 -(2) Power supply switch connector connection on the outdoor unit(Factory setting: The male power supply switch connector is connected to CN41.)

Pagina 51 - Equipment. (JRA GL02E-1994)

- 46 -6. Sample System Connection(1) System with MA remote controller1) Single refrigerant circuitControl Wiring DiagramNotes Maximum Allowable Length

Pagina 52 - 4. Control Wiring

- 47 -2) Two refrigerant circuitsControl Wiring DiagramNotes Maximum Allowable Length1. Assign a sequential number to the outdoor unit.2. Do not conne

Pagina 53

- 48 -3) System in which two MA remote controllers are connected to one indoor unitControl Wiring DiagramNotes Maximum Allowable Length1. Leave the ma

Pagina 54

- 49 -4) System in which two indoor units are grouped with the MA remote controllerControl Wiring DiagramNotes Maximum Allowable Length1. Leave the ma

Pagina 55 - Setting not required

- 50 -(2) System with MA remote controller and AG-150A1) System with multiple indoor units (10HP, 20HP)Control Wiring DiagramNotes Maximum Allowable

Pagina 56

Before installing the unit (moving and reinstalling the unit) and performing electrical workCAUTIONProperly ground the unit.Do not connect the ground

Pagina 57

- 51 -7. External input/output specifications(1) Input/output specificationsInput*1 Use minute-current contact (DC12V 1mA) Output* 20HP only Function

Pagina 58

- 52 -(2) WiringExternal input/output boardPower Source for DisplayNo.1 Operation StatusNo.1 Error Status* No.2 Operation Status* 20HP only* No.2 Erro

Pagina 59 - DC power supply line

- 53 -54321COMB2B1BCA2A1ACTB23TB21 TB22CN53 CN54External input-output boardShort-circuit plateExternal input-output board54321COMB2B1BCA2A1ACTB23TB21

Pagina 60 - (Pulse interval)

- 54 -(3) Wiring Method1) Check the indoor unit setting (Refer to 7-(2) Wiring )2) When using the external output function, connect each signal line t

Pagina 61 - Setting on the Indoor Unit

- 55 -(4) Switch settingThe suction/discharge air temperature control of the indoor unit.Either suction temperature control or discharge temperature c

Pagina 62

- 56 -8. System Rotation Control9. Notes on the use of optional accessoriesWARNINGOnly use optional parts recommended by Mitsubishi Electric. These pa

Pagina 63 - TB21 TB22

- 57 -10.Caution for refrigerant leakageThe installer and/or air conditioning system specialist shall secure safety against refrigerant leakage accord

Pagina 64

- 58 -V Wiring Design (PEFY-AF1200CFMR) V Air Conditioning the Computer Room1. Main Features of the Floor-Duct Air ConditionersThis system is ins

Pagina 65 - 8. System Rotation Control

- 59 -3. Step-by-Step Plan for the Implementation of the Air-ConditioningBasic ConditionsSecuring Necessary RoomsDecision to Install the Air-Condition

Pagina 66 - (1) Refrigerant property

- 60 -4. Conditions for the Installation of Computer-Room Air Conditioners(1) Outdoor Temperature and HumidityUsually, outdoor temperature/humidity co

Pagina 67 - Computer

Before the test runCAUTIONTurn on the unit at least 12 hours before the test run.Keep the unit turned on throughout the season. If the unit is turned

Pagina 68

- 61 -5. Setting the Air conditioners(1) Air-Conditioning Load1) Once the floor plan is made and the conditions for the air-conditioning system are se

Pagina 69

- 62 -(2-3) Calculating the Load and Selecting a ModelCalculate the temperature difference by setting the outdoor temperature; then, calculate hourly

Pagina 70

- 63 -6. Automatic Control of the Computer RoomExamplePFD-P500VM-E automatically controls the cooling temperature with a built-in controller.(suction

Pagina 71

- 64 -VI General E quipment Descriptions (PEFY -AF1200C FM) VI Maintenance/Inspection1. Maintenance/Inspection ScheduleHaving the units inspect

Pagina 72

- 65 -(3) Details of Maintenance/InspectionPartsFan motorBearingFan beltAir filterLinear expansion valveDisplay lamp(LED)Compressor Fan motorLinear e

Pagina 74

DATA BOOK PUHY-P250YJM-A (-BS)PUHY-P500YSJM-A (-BS)PQHY-P250YHM-APFD-P250VM-EPFD-P500VM-EMEE13K035New publication effective Mar. 2014Specifications s

Pagina 75

CONTENTS Safety Precautions I General Equipment Descriptions1. Unit configuration table.....

Pagina 76

CONTENTS7. External input/output specifications .........................