Air Conditioners For Building Application
Outdoor Unit
For use with R410A
GBDFEIP
PUHY-RP200·250YJM-B(-BS)
PUHY-RP300·350YJM-B(-BS)
MINERAL OIL COLLECTION (REFRIGERANT OIL RECOVERY) INSTRUCTIONS MANUAL
ANLEITUNGSHANDBUCH FÜR DIE MINERALÖLSAMMLUNG
(KÄLTEMITTELÖLENTNAHME)
MANUEL D’INSTRUCTIONS POUR LA COLLECTE D’HUILE MINÉRALE
(RÉCUPÉRATION DE L’HUILE FRIGORIFIQUE)
MANUAL DE INSTRUCCIONES PARA LA RECOGIDA DE ACEITE MINERAL
(RECUPERACIÓN DE ACEITE REFRIGERANTE)
RACCOLTA DELL’OLIO MINERALE (RECUPERO DELL’OLIO REFRIGERANTE)
MANUALE DI ISTRUZIONI
MANUAL DE INSTRUÇÕES DE RECOLHA DE ÓLEO MINERAL
(RECUPERAÇÃO DO ÓLEO REFRIGERANTE)
WT06217X01_cv.fm Page 1 Tuesday, December 14, 2010 11:09 AM
Vista de pagina 0
1 2 3 4 5 6 7 8 9

Indice de contenidos

Pagina 1 - Outdoor Unit

Air Conditioners For Building ApplicationOutdoor UnitFor use with R410AGBDFEIPPUHY-RP200·250YJM-B(-BS)PUHY-RP300·350YJM-B(-BS)MINERAL OIL COLLECTION (

Pagina 2 - 1. Unit Components

2GB1. Unit ComponentsFigure 1 Top view of the refrigerant pipes inside an outdoor unitCJ5CJ2 CJ1CJ5CJ4CJ4CJ3BCAIHJGFDEFigure 2 Valve types allocations

Pagina 3 - LD6 LD7 LD8

3GB2. Refrigerant Oil Recovery Operation Flow2.1 Refrigerant oil recovery operation monitor display(*1) The initial remaining time that indicates the

Pagina 4 - 2Refrigerant charging

4GB2.2 Procedures for refrigerant oil recovery1Evacuating the existing pipes, and ensuring air tightness Charge airtight gas through the service port

Pagina 5 - 3Opening the valves

5GB3Opening the valves Open both the liquid and gas valves. (In a system with multiple outdoor units, open the liquid and gas valves on ALL outdoor un

Pagina 6

6GB6Refrigerant oil recovery operation Set the dipswitches 3-1 and 4-8 to ON in that order. The compressor turns on, and oil recovery operation starts

Pagina 7

7GBDisconnect the charging hose, which is connected to the refrigerant cylinder, from the refrigerant charge port (only for automatic charging), andco

Pagina 8 - 8Disconnecting the cylinder

8GB8Disconnecting the cylinder After completing the oil recovery operation, close the valve on the cylinder, and disconnect the cylinder within five m

Pagina 9 - WT06217X01

This product is designed and intended for use in the residential, commercial and light-industrial environment.The product at hand is based on the foll