Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
Unit Designation: Schedule No.:
GENERAL FEATURES
• Compact side discharge
outdoor unit
• Wireless or wired remote
controller, depending on the
indoor units used
• Quiet operation—both indoor
and outdoor units
Automatic fan speed control
Auto restart following a power
outage
• Self-check function—integrated
diagnostics
Advanced microprocessor control
• Limited warranty: one year on parts and
defects and six years on compressor
OPTIONAL OUTDOOR UNIT ACCESSORY
Air Outlet Guide (MAC-889SG)
Cooling*
Rated Capacity (Non-ducted/Ducted) ...20,000 Btu/h / 20,000 Btu/h
Minimum Capacity (Non-ducted/Ducted) ..7,800 Btu/h / 7,800 Btu/h
Total Input (Non-ducted/Ducted) ..............2,150 W / 2,150 W
Heating at 47°F*
Rated Capacity (Non-ducted/Ducted) ...22,000 Btu/h / 22,000 Btu/h
Minimum Capacity (Non-ducted/Ducted) ..8,500 Btu/h / 8,500 Btu/h
Total Input (Non-ducted/Ducted) ..............1,780 W / 1,780 W
Heating at 17°F*
Rated Capacity (Non-ducted/Ducted)..14,500 Btu/h / 12,500 Btu/h
Total Input (Non-ducted/Ducted).............1,500 W / 1,430 W
* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB / 67ºF (19ºC) WB.
Outdoor: 95ºF (35ºC) DB / 75ºF (24ºC) WB.
(Heating) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 47ºF (8ºC) DB /
43ºF (6ºC) WB.
(Heating at 17ºF) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 17ºF
(-8ºC) DB / 15ºF (-9ºC) WB.
Electrical Requirements
Power Supply ....................208 / 230V, 1-Phase, 60 Hz
Breaker Size........................................20 A
MCA ............................................ . 15 A
Voltage
Indoor - Outdoor S1-S2 ......................AC 208 / 230V
Indoor - Outdoor S2-S3 ........................DC 12 - 24V
OPERATING RANGE
Indoor Intake Air Temp. Outdoor Intake Air Temp.
Cooling
Maximum 95ºF (35ºC) DB, 71ºF (22ºC) WB 115ºF (46ºC) DB
Minimum 67ºF (19ºC) DB, 57ºF (14ºC) WB 14ºF (-10ºC) DB
Heating
Maximum 80ºF (27ºC) DB, 67ºF (19ºC) WB 75ºF (24ºC) DB, 65ºF (18ºC) WB
Minimum 70ºF (21ºC) DB, 60ºF (16ºC) WB 14ºF (-10ºC) DB, 12ºF (-11ºC) WB
Compressor ..................DC Inverter-driven Twin Rotary
Fan Motor .................................... 0.96 F.L.A.
Sound Pressure Level
Cooling ...................................... . . 49 dB(A)
Heating ....................................... . 51 dB(A)
DIMENSIONS INCHES / MM
W 33-1/16 / 840
D 13 / 330
H 27-15/16 / 710
Weight ...................................130 lbs. / 59 kg
Refrigerant Type .................................. R410A
Refrigerant Pipe Size O.D. ― Two Ports
Gas Side............................. A, B: 3/8" / 9.52 mm
Liquid Side ................................1/4" / 6.35 mm
Max. Refrigerant Pipe Length.....................164' / 50 m
Max. Refrigerant Pipe Height Difference
If Indoor Unit is Above Outdoor Unit ............... 49' / 15 m
If Indoor Unit is Below Outdoor Unit ................ 33' / 10 m
Connection Method ................................Flared
SUBMITTAL DATA: MXZ-2A20NA MULTI-INDOOR INVERTER HEAT-PUMP SYSTEM
Remote Controller PAR-21MAA -
Packaged with SEZ
COMPATIBLE INDOOR UNITS AND ASSOCIATED REMOTE CONTROLLERS
Outdoor Unit: MXZ-2A20NA
Wireless Remote Controller -
Packaged with MSZ-A and MSZ-
FD (Optional Wired PAR-21MAA
Remote Controller)
Refer to the separate submittal forms for the SEZ and MSZ Indoor Units.
MXZ-2A20NA ENERGY EFFICIENCIES
Indoor Unit Type SEER HSPF
Non-ducted 16 8.5
Ducted and Non-ducted 15.5 8.5
Ducted 15.5 8.5
SYSTEM COMPONENTS
Outdoor Unit…………..MXZ-2A20NA
Indoor Unit………...Two Indoor Units
Necessary (Select Style as Installation Requires)
Wall-mounted Indoor Units: MSZ-FD09, 12NA
Wall-mounted Indoor Units: MSZ-A09, 12, 15, 17NA
Horizontal-ducted Indoor Units: SEZ-KD09, 12, 15, 18NA
Indoor Unit
(Unit A + Unit B) Combinations
Cooling Capacity (Btu/h)
Power Usage (W)Heating Capacity (Btu/h)
Unit A Unit B Total
9 + 9
9,000 9,000 18,000 1,740 - 1,780
10,900 10,900 21,800 1,820
9 + 12
8,500 11,500
20,000
22,000
2,150 - 2,190
1,780
9,500 12,500
9 + 15
7,500 12,500
8,250 13,750
12 + 12
10,000 10,000
11,000 11,000
MXZ-2A20 Combinations* (with wall-mounted and/or horizontal-ducted indoor units)
* Information provided at 208/230V.
(For data on specic indoor units [all ducted, all non-ducted, and both ducted
and non-ducted] combinations, see the MXZ Technical and Service Manual.)
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - Purchaser: Engineer:

Job Name: Location: Date:Purchaser: Engineer:Submitted to: For Reference Approval ConstructionUnit Designation: Schedule No.:

Pagina 2 - 

3400 Lawrenceville Suwanee RdSuwanee, GA 30024Tele: 678-376-2900 • Fax: 800-889-9904Toll Free: 800-433-4822 (#3)www.mehvac.com

Comentarios a estos manuales

Sin comentarios