Air-Conditioners For Building ApplicationINDOOR UNITPLFY-P·VBM-EINSTALLATION MANUALFor safe and correct use, read this manual and the outdoor unit ins
10GB● Each air conditioner has its own Address No. of indoor unit (Example below).● Address No. of indoor unit can be set ranging from "01"
11GB5.1. Checking the contents (Fig. 5-1)• This kit contains this manual and the following parts.Accessory name Q’ty RemarkGrille 1 950 × 950 (mm)
12GB5. Installing the grilleMain unitCorner drain pipe areaScrew with washer (for temporary use)GrilleScrew with washer SocketBell s
13GB5. Installing the grilleFig. 6-2Water supply pumpWater (about 1000cc)Drain plugPour water through outlet· Be carefule not to spray water
Please be sure to put the contact address/telephone number on this manual before handing it to the customer.This product is designed and intended for
2GB► Before installing the unit, make sure you read all the “Safety precau-tions”.► Please report to your supply authority or obtain their consent be
3GBFig. 2-215016016016016090860-91020-45(7.5)(7.5)20-45 20-4520-45810950187.584084013517+5 017+5 0* 50-70*10535CDMin. 2500Min. 500860-9109506
4GB17105(240)+5 0Min. 30A=17+5 0 Suspension bolt Ceiling Nut Washer (with insulation) Mounting plate Washer (without insul
5GB3.3. Indoor unit (Fig. 3-3)Heat insulation for refrigerant pipes:1 Wrap the enclosed large-sized pipe cover around the gas pipe, making sure that
6GB4. Electrical work4.1. Indoor unit (Fig. 4-1)1. Remove the electrical wiring service panel.2. Remove the electrical box cover.3. Remove the MA R
7GB4.5. Setting addresses (Fig. 4-4)(Be sure to operate with the main power turned OFF.)• There are 2 types of rotary switch setting available: setti
8GB4. Electrical work4.8. How to set the fixed up/down air direction (Only for wired remote controller) Explanation of word • "Address No. of in
9GB< Process for setting >[1] To turn off air conditioner and change the remote controller to "Fixed airflow direction mode"1.Press ON/