SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················2
3. INDOOR/OUTDOOR
CORRESPONDENCE TABLE ···························3
4. INDOOR UNITS COMBINATION ·······················4
5. SPECIFICATION·················································8
6. NOISE CRITERIA CURVES······························ 9
7. OUTLINES AND DIMENSIONS ······················ 10
8. WIRING DIAGRAM···········································11
9. REFRIGERANT SYSTEM DIAGRAM··············12
10. PERFORMANCE CURVES······························13
11. MICROPROCESSOR CONTROL·····················19
12. TROUBLESHOOTING······································25
13. DISASSEMBLY INSTRUCTIONS·····················37
14. PARTS LIST······················································40
15. OPTIONAL PARTS···········································43
Inverter-controlled multi system
Models
MXZ-32SV -
MXZ-32SV -
E2
E1
No. OB254
REVISED EDITION-B
This manual describes technical data of outdoor unit.
For indoor unit, refer to the service manuals No. OB229, OB227, OB252, OB212, OB239 and OC165.
Model indication
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
Please void OB254 REVISED EDITION-A.
Revision B:
“Check of HPS” and PARTS LIST have been
corrected.
OB254-1.qxp 06.6.7 10:51 AM Page 1
Vista de pagina 0
1 2 3 4 5 6 ... 43 44

Indice de contenidos

Pagina 1 - MXZ-32SV

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ····································22. PART NAMES AND FUNCTIONS······················23. INDOOR/OUTDOOR CO

Pagina 2 - TECHNICAL CHANGES

10OUTLINES AND DIMENSIONS7MXZ-32SV -MXZ-32SV -E2E1Unit: mmOUTDOOR UNIT2310 353209008846050900350.0480.8531.33172333Handle formovingAir inIndoor and ou

Pagina 3 - E1 , MXZ-32SV- E2

11WIRING DIAGRAM8POWER SUPPLY~/N 220-240V 50HzINDOORUNIT (A)CIRCUIT BREAKERTB2TB3BLUREDTB4X64GRN/YLWGRNCN720CN60104X64LD62CN913CN791CN9016 42CN902CN85

Pagina 4 - INDOOR UNITS COMBINATION

12REFRIGERANT SYSTEM DIAGRAM9Unit:mm● Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refe

Pagina 5

1310The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,since operating con

Pagina 6

1410-3-.2.Capacity and input correction by inverter output frequency (OUTDOOR UNIT:MXZ-32SV)The dotted line on graphs connects the frequency range in

Pagina 7

0 5 10 15 20 2545678910Ambient temperature(:)45HzOutdoor unit current (A)Ambient temperature(:)/ Ambient humidity(%)Ambient temperature(:)/ Ambient hu

Pagina 8 - SPECIFICATION

162. 09-class unit in single operationNOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).The conve

Pagina 9 - NOISE CRITERIA CURVES6

173. 12-class unit in single operationNOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).The conve

Pagina 10 - OUTLINES AND DIMENSIONS

184. 18-class unit in single operationNOTE:The unit of pressure has been changed to MPa on the international system of units(SI unit system).The conve

Pagina 11 - WIRING DIAGRAM

19MICROPROCESSOR CONTROL11CompressorpowerfactorIndoor unitmicroprocessorSSR61DrivecircuitTransistormoduleIndoor UnitAIndoor UnitDIndoor UnitCIndoor Un

Pagina 12 - REFRIGERANT SYSTEM DIAGRAM

PART NAMES AND FUNCTIONS2OUTDOOR UNITAir inletAir outlet(back and side)Model indicationMXZ-32SV-MXZ-32SV-E2E12TECHNICAL CHANGES1MXZ-32RV - ➔ MXZ-32SV

Pagina 13 - PERFORMANCE CURVES

20• The standard opening is on the straight line, which connects each standard point in the section where divided into seven according to the operatio

Pagina 14 - (OUTDOOR UNIT:MXZ-32SV)

21(1) LEV opening correction by suction superheat (COOL, DRY)(Suction superheat) = (Minimum gas pipe temperature) - (Evaporation temperature)When COOL

Pagina 15 - (MPa•Gauge)

2211-2.Operational frequency range(3) LEV opening correction by discharge temperatureWhen LEV correction output is 0 pulse by the suction superheat at

Pagina 16

2311-3.Heat defrosting control(1) Conditions to enter defrosting mode1. When temperature of defrosting thermistor is -3; or less.2.When specified non-

Pagina 17

24<Control status>The control performs when the following status are satisfied everything;• When there is 1 unit or more not operating indoor un

Pagina 18

2512 TROUBLESHOOTING3. Troubleshooting procedure1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate

Pagina 19 - MICROPROCESSOR CONTROL

26Outdoor power system abnor-malityWhen the compressor operation has been interrupted by overcurrentprotection continuously three times within 1 minut

Pagina 20 - 11-1.LEV control

27Frequency drop by currentprotectionWhen the outdoor unit input current exceeds 22.5 A, the compressoroperates at reduced frequency.These symptoms do

Pagina 21

28Part name Check method and criterionMeasure the resistance using a tester.(Part temperature -10°C ~ 40°C)Defrost thermistor Evaporation / Gas pipete

Pagina 22

29BBCheck of serial signalTurn on power supply.NoYesYesNoNoYesNoYesStartCheck the connecting of main circuit parts and connectors (CN501: I.P.M P. C.

Pagina 23 - 11-3.Heat defrosting control

33INDOOR / OUTDOOR CORRESPONDENCE TABLE❈There is no combination other than this table.MXZ-32SV- E1 , MXZ-32SV- E2OUTDOOR UNITCombination of the con

Pagina 24 - 11-7.Outdoor fan control

30CCCheck of R. V. coilNoYesNoYesNoYesNoYesNoYesStart1. Disconnect the lead wire leading to the compressor.2. Turn on power supply to the indoor and

Pagina 25 - 12 TROUBLESHOOTING

31DDCheck of LEVNoYesNoYesStartTurn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.Is "click - c

Pagina 26

32FFCheck of thermistorNormalYesNoAbnormalReconnect the connectors (CN661, CN662 and CN663) and disconnect the lead wire leading to the compressor. Tu

Pagina 27

HHCheck of HPSInfinity0"YesNoStart1. Disconnect the connector CN722 in the electronic control P. C. board.2. Check the resistance of HPS after 1

Pagina 28

34TEST POINT DIAGRAM AND VOLTAGEMXZ-32SV -, MXZ-32SV -Electronic control P.C.boardE2E1Gas pipe temperature thermistorEvaporation temperature thermisto

Pagina 29 - Check of power supply

35Noise filter P.C.boardMXZ-32SV -E1{220V-240V ACOUTPUT{220V-240V AC INPUT{OUTDOOR FAN 220V-240V AC{REVERSING VALVE 220V-240V ACMXZ-32SV -E2{OUTDOOR F

Pagina 30 - Check of R. V. coil

36I.P.M P.C.boardMXZ-32SV -MXZ-32SV -E2E1Relay P.C.boardMXZ-32SV -MXZ-32SV -E2E1{{{{Short12V DCHigh pressure switch12V DC{12V DC{12V DC{320V DCOB254-2

Pagina 31 - Check of inverter/ compressor

37OPERATING PROCEDURE PHOTOS1.Removing the compressor(1)Remove the screws of the service panel, and remove it.Release refrigerant gas.(2)Remove the sc

Pagina 32 - Check of fan motor

38OPERATING PROCEDURE PHOTOS3.Removing the 4-way valve(1)Remove the screws of the top panel, and remove it.(See Photo 1.)(2)Remove the service panel,

Pagina 33 - The other cases

39OPERATING PROCEDURE PHOTOS5.Removing the reactor(1)Remove the screws of the top panel, and remove it.(See Photo 1.)(2)Disconnect the reactor lead w

Pagina 34 - Electronic control P.C.board

40709121807+0707+0907+1207+1809+0909+1209+1812+1212+1818+1807+07+0707+07+0907+07+1207+07+1807+09+0907+09+1207+09+1807+12+1207+12+1807+18+1890909090909

Pagina 35

4014Part numbers that are circled are not shown in the illustration.12345678910111213141516171819202122M21 17A 501T2W E40 301T2W E40 452M21 17A

Pagina 36

14-2. OUTDOOR UNIT STRUCTURAL PARTSMXZ-32SV -MXZ-32SV -E2E1416103119161217 144 513 12158When servicing , cut the tube to the proper length as shown in

Pagina 37 - DISASSEMBLY INSTRUCTIONS

421No. Parts NameSymbolin WiringDiagramParts No.Q'ty / unitRemarksE1MXZ-32SVT2W E59 704DRAIN SOCKET ASSEMBLY1DRAIN SOCKET O1DRAIN CAP O2E2114-3.

Pagina 38 - OPERATING PROCEDURE PHOTOS

4315-1. Different-diameter pipeUnit : mm (inch)For different-diameterpipesMXZ-32SVMAC-454JPMAC-455JPMAC-456JPModel name51H-45451H-455516456Model codeC

Pagina 39

New publication, effective Jun. 2006Specifications subject to change without notice.CCCopyright 2000 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistribute

Pagina 40 - PARTS LIST

5Indoor unitscombinationUnit A Unit B Unit C Unit DCooling capacity (kW)TotalOutdoor unitpower consumption(kW)Current(A)Powerfactor(%)220V 240V9090909

Pagina 41

6NOTE: Electrical data is for outdoor unit only.0709121807+0707+0907+1207+1809+0909+1209+1812+1212+1818+1807+07+0707+07+0907+07+1207+07+1807+09+0907+0

Pagina 42 - 14-3. ACCESSORY PARTS

7Indoor unitscombinationUnit A Unit B Unit C Unit DHeating capacity (kW)TotalOutdoor unitpower consumption(kW)Current(A)Powerfactor(%)220V 240V9090909

Pagina 43 - OPTIONAL PARTS

85SPECIFICATIONOutdoor modelIndoor units numberIndoor units total capacity (Connectable)indoor units total capacity (Simultaneous operation)Piping tot

Pagina 44

9NOISE CRITERIA CURVES690807060504030201063 125 250 500 1000 2000 4000 8000APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISENC-60NC-50NC-40NC-30NC-20N