Air-ConditionersSUZ- KA25, KA35, KA50, KA60, KA71VAEnglishINSTALLATION MANUALFor safe and correct use, read this manual and the indoor unit installati
2Contents1. The following should always be observed for safety ... 22. Selecting the installation location ...
33. Installation diagram4.1. AccessoriesCheck the following parts before installation.<Outdoor unit>1 Drain socket (for VA type only) 13 Drain c
4adcbef90°dcbabaabebcdcA5.2. Flaring work• Main cause of gas leakage is defect in flaring work.Carry out correct flaring work in the following procedu
5• Apply a thin coat of refrigeration oil on the seat surface of pipe. (Fig. 5-8)• For connection first align the center, then tighten the first 3 to
6• Perform wiring as shown in the diagram to the lower left. (Procure the cable locally)(Fig. 6-2)Make sure to use cables of the correct polarity only
77. Maintenance7.1. Gas charge (Fig. 7-1)1. Connect gas cylinder to the service port of stop valve (3-way).2. Execute air purge of the pipe (or hose)
Please be sure to put the contact address/telephone number onthis manual before handing it to the customer.HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI