Mitsubishi Electric PUHY-RP350YJM-A Manual de instalación

Busca en linea o descarga Manual de instalación para Acondicionadores de aire del sistema de división Mitsubishi Electric PUHY-RP350YJM-A. Mitsubishi Electric PUHY-RP350YJM-A Installation manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 306
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente

Indice de contenidos

Pagina 1 - Service Handbook

Service HandbookService HandbookService HandbookPUHY-RP200, RP250, RP300, RP350YJM-BPUHY-RP400, RP450, RP500, RP550, RP600, RP650YSJM-BPUHY-RP700, RP7

Pagina 2 - Safety Precautions

- 1 -HWE10130 GBI Read Before Servicing[1] Read Before Servicing...

Pagina 3

[ VII Control ] - 91 -HWE10130 GB1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF f

Pagina 4

[ VII Control ]- 92 -HWE10130 GB2. Function of the switch (Indoor unit)(1) Dipswitches1) SW1,32) SW2SW3-1OFFOFFOFFONONONOFFONOFFONOFFONOFFONVery

Pagina 5 - Before installing the unit

[ VII Control ] - 93 -HWE10130 GB(2) Address switchActual indoor unit address setting varies in different systems. Refer to the installation manual f

Pagina 6

[ VII Control ]- 94 -HWE10130 GB(2) ME remote controller (PAR-F27MEA)Set the address of the remote controller with the rotary switch.To set addresse

Pagina 7 - Before the test run

[ VII Control ] - 95 -HWE10130 GB[2] Controlling the Outdoor Unit-1- Outline of Control MethodThe outdoor units are designated as OC, OS1 and OS2 in

Pagina 8 - CONTENTS

[ VII Control ]- 96 -HWE10130 GB-5- Bypass ControlBypass solenoid valves (SV1(a,b)), which bypass the high- and low- pressure sides, perform the foll

Pagina 9

[ VII Control ] - 97 -HWE10130 GB-6- Compressor Frequency Control Depending on the capacity required, the frequency of the compressor is controlled

Pagina 10 - I Read Before Servicing

[ VII Control ]- 98 -HWE10130 GB-9- Controlling the plate heat exchanger 2 (Solenoid valve (SV3))(Opens when ON)The valve positions in different mod

Pagina 11

[ VII Control ] - 99 -HWE10130 GB(3) Stopping the defrost operation1) When SW3-4 is set to OFFThe defrost cycle ends when 12 minutes have passed s

Pagina 12 - [1] Read Before Servicing

[ VII Control ]- 100 -HWE10130 GB30 minutes have passed since the completion of previous refrigerant recovery.When the unit keeps running for 3 min

Pagina 14 - [4] Pipe Processing

[ VII Control ] - 101 -HWE10130 GB(2) RP400, RP450, RP500, RP550, RP600, RP650 models*1 Qj:Total capacity (model name) codeRefer to VII [1] 2. (1)

Pagina 15 - [5] Brazing

[ VII Control ]- 102 -HWE10130 GB(3) RP700, RP750, RP800, RP850, RP900 models*1 Qj:Total capacity (model name) codeRefer to VII [1] 2. (1) Dipswit

Pagina 16 - [6] Air Tightness Test

[ VII Control ] - 103 -HWE10130 GB-16- Emergency Operation Mode1. Problems with the outdoor unitEmergency operation mode is a temporary operation mo

Pagina 17

[ VII Control ]- 104 -HWE10130 GB(2) Ending the emergency operation1) End conditionsWhen one of the following conditions is met, emergency operati

Pagina 18 - [8] Refrigerant Charging

[ VII Control ] - 105 -HWE10130 GBEmergency operation pattern (2 outdoor units)Emergency operation pattern (3 outdoor units)(3) Ending the emergency

Pagina 19

[ VII Control ]- 106 -HWE10130 GB-18- DEMAND ControlCooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units

Pagina 20

[ VII Control ] - 107 -HWE10130 GB[3] Operation Flow Chart1. Mode determination flowchart (1) Indoor unit (cooling, heating, dry, fan mode)*Note 1.

Pagina 21 - [ I Read Before Servicing ]

[ VII Control ]- 108 -HWE10130 GB(2) Outdoor unit (cooling and heating modes)*Note 1. For about 3 minutes after power on, search for the indoor unit

Pagina 22 - II Restrictions

[ VII Control ] - 109 -HWE10130 GB2. Operations in each mode(1) Cooling operation*Note 1. The indoor fan operates at the set notch under cooling mod

Pagina 23

[ VII Control ]- 110 -HWE10130 GB(2) Heating operation1) When outdoor unit starts defrosting, it transmits defrost operations command to indoor uni

Pagina 24 - [1] System configuration

[ I Read Before Servicing ] - 3 -HWE10130 GBI Read Before Servicing[1] Read Before Servicing1. Check the type of refrigerant used in the system to b

Pagina 25

[ VII Control ] - 111 -HWE10130 GB(3) Dry operationDry operation *Note 1 *Note 2 YES YES NO NO 4-way valve OFF 1. Outdoor unit (compressor) inte

Pagina 26

- 112 -[ VII Control ]GBHWE10130

Pagina 27 - [ II Restrictions ]

- 113 -HWE10130 GBVIII Test Run Mode[1] Items to be checked before a Test Run...

Pagina 28

- 114 -

Pagina 29

[ VIII Test Run Mode ] - 115 -HWE10130 GBVIII Test Run Mode[1] Items to be checked before a Test Run(1) Check for refrigerant leak and loose cables a

Pagina 30

[ VIII Test Run Mode ]- 116 -HWE10130 GB[2] Test Run MethodThe figure shows an MA remote controller (PAR-21MAA). PAR-21MAAON/OFF FILTERCHECKOPERATION

Pagina 31

[ VIII Test Run Mode ] - 117 -HWE10130 GB[3] Operating Characteristic and Refrigerant AmountIt is important to have a clear understanding of the char

Pagina 32

[ VIII Test Run Mode ]- 118 -HWE10130 GB3. Amount of refrigerant to be addedThe amount of refrigerant that is shown in the table below is factory-ch

Pagina 33

[ VIII Test Run Mode ] - 119 -HWE10130 GB(2) Example: PUHY-P500YSHM-A(3) Sample calculation[3/4"][98 ft] [3/4"] [32 ft] [1/2"][32 ft

Pagina 34 - Terminal

[ VIII Test Run Mode ]- 120 -HWE10130 GB[5] Refrigerant Amount Adjust Mode1. Procedures Follow the procedures below to adjust refrigerant charge as n

Pagina 35 - Example of wiring connection

[ I Read Before Servicing ]- 4 -HWE10130 GB[2] Necessary Tools and MaterialsPrepare the following tools and materials necessary for installing and se

Pagina 36

[ VIII Test Run Mode ] - 121 -HWE10130 GBSet SW4-3 to ON to start the refrigerant charge adjustment mode.Connect a refrigerant cylinder, and open its

Pagina 37

[ VIII Test Run Mode ]- 122 -HWE10130 GB[6] The following symptoms are normal.SymptomsRemote controller displayCauseThe indoor unit does not start af

Pagina 38 - [4] Sample System Connection

[ VIII Test Run Mode ] - 123 -HWE10130 GB[7] Standard Operation Data (Reference Data)1. Single unit(1) Cooling operationOperationOutdoor unit modelPU

Pagina 39 - Group Group

[ VIII Test Run Mode ]- 124 -HWE10130 GBOperationOutdoor unit modelPUHY-RP300YJM-B PUHY-RP350YJM-BOperating conditionsAmbient tempera-tureIndoorDB/WB

Pagina 40

[ VIII Test Run Mode ] - 125 -HWE10130 GB(2) Heating operationOperationOutdoor unit modelPUHY-RP200YJM-B PUHY-RP250YJM-BOperating conditionsAmbient t

Pagina 41

[ VIII Test Run Mode ]- 126 -HWE10130 GBOperationOutdoor unit modelPUHY-RP300YJM-B PUHY-RP350YJM-BOperating conditionsAmbient tempera-tureIndoorDB/WB

Pagina 42

[ VIII Test Run Mode ] - 127 -HWE10130 GB2. 2-unit combination(1) Cooling operationOperationOutdoor unit modelPUHY-RP400YSJM-BPUHY-RP200YJM-B PUHY-RP

Pagina 43 - M1 M2 M1 M2

[ VIII Test Run Mode ]- 128 -HWE10130 GBOperationOutdoor unit modelPUHY-RP450YSJM-BPUHY-RP250YJM-B PUHY-RP200YJM-BOperating conditionsAmbient tempera

Pagina 44

[ VIII Test Run Mode ] - 129 -HWE10130 GBOperationOutdoor unit modelPUHY-RP500YSJM-BPUHY-RP250YJM-B PUHY-RP250YJM-BOperating conditionsAmbient temper

Pagina 45 - M1 M2 M1 M2 M1 M2 M1 M2

[ VIII Test Run Mode ]- 130 -HWE10130 GBOperationOutdoor unit modelPUHY-RP550YSJM-BPUHY-RP300YJM-B PUHY-RP250YJM-BOperating conditionsAmbient tempera

Pagina 46

[ I Read Before Servicing ] - 5 -HWE10130 GB[3] Storage of Piping1. Storage locationStore the piping materials indoors until they are ready to be ins

Pagina 47 - GBHWE10130

[ VIII Test Run Mode ] - 131 -HWE10130 GBOperationOutdoor unit modelPUHY-RP600YSJM-BPUHY-RP300YJM-B PUHY-RP300YJM-BOperating conditionsAmbient temper

Pagina 48

[ VIII Test Run Mode ]- 132 -HWE10130 GBOperationOutdoor unit modelPUHY-RP650YSJM-BPUHY-RP350YJM-B PUHY-RP300YJM-BOperating conditionsAmbient tempera

Pagina 49

[ VIII Test Run Mode ] - 133 -HWE10130 GB(2) Heating operationOperationOutdoor unit modelPUHY-RP400YSJM-BPUHY-RP200YJM-B PUHY-RP200YJM-BOperating con

Pagina 50

[ VIII Test Run Mode ]- 134 -HWE10130 GBOperationOutdoor unit modelPUHY-RP450YSJM-BPUHY-RP250YJM-B PUHY-RP200YJM-BOperating conditionsAmbient tempera

Pagina 51

[ VIII Test Run Mode ] - 135 -HWE10130 GBOperationOutdoor unit modelPUHY-RP500YSJM-BPUHY-RP250YJM-B PUHY-RP250YJM-BOperating conditionsAmbient temper

Pagina 52

[ VIII Test Run Mode ]- 136 -HWE10130 GBOperationOutdoor unit modelPUHY-RP550YSJM-BPUHY-RP300YJM-B PUHY-RP250YJM-BOperating conditionsAmbient tempera

Pagina 53

[ VIII Test Run Mode ] - 137 -HWE10130 GBOperationOutdoor unit modelPUHY-RP600YSJM-BPUHY-RP300YJM-B PUHY-RP300YJM-BOperating conditionsAmbient temper

Pagina 54

[ VIII Test Run Mode ]- 138 -HWE10130 GBOperationOutdoor unit modelPUHY-RP650YSJM-BPUHY-RP350YJM-B PUHY-RP300YJM-BOperating conditionsAmbient tempera

Pagina 55

[ VIII Test Run Mode ] - 139 -HWE10130 GB3. 3-unit combination(1) Cooling operationOperationOutdoor unit modelPUHY-RP700YSJM-BPUHY-RP250YJM-BPUHY-RP2

Pagina 56 - (Equivalent length 150 [492]

[ VIII Test Run Mode ]- 140 -HWE10130 GBOperationOutdoor unit modelPUHY-RP750YSJM-BPUHY-RP250YJM-BPUHY-RP250YJM-BPUHY-RP250YJM-BOperating conditionsA

Pagina 57

[ I Read Before Servicing ]- 6 -HWE10130 GB[5] BrazingNo changes have been made in the brazing procedures. Perform brazing with special care to keep

Pagina 58 - 100 [328] or less

[ VIII Test Run Mode ] - 141 -HWE10130 GBOperationOutdoor unit modelPUHY-RP800YSJM-BPUHY-RP300YJM-BPUHY-RP250YJM-BPUHY-RP250YJM-BOperating conditions

Pagina 59

[ VIII Test Run Mode ]- 142 -HWE10130 GBOperationOutdoor unit modelPUHY-RP850YSJM-BPUHY-RP300YJM-BPUHY-RP300YJM-BPUHY-RP250YJM-BOperating conditionsA

Pagina 60 - (Note 2)

[ VIII Test Run Mode ] - 143 -HWE10130 GBOperationOutdoor unit modelPUHY-RP900YSJM-BPUHY-RP300YJM-BPUHY-RP300YJM-BPUHY-RP300YJM-BOperating conditions

Pagina 61

[ VIII Test Run Mode ]- 144 -HWE10130 GB(2) Heating operationOperationOutdoor unit modelPUHY-RP700YSJM-BPUHY-RP250YJM-BPUHY-RP250YJM-BPUHY-RP200YJM-B

Pagina 62

[ VIII Test Run Mode ] - 145 -HWE10130 GBOperationOutdoor unit modelPUHY-RP750YSJM-BPUHY-RP250YJM-BPUHY-RP250YJM-BPUHY-RP250YJM-BOperating conditions

Pagina 63

[ VIII Test Run Mode ]- 146 -HWE10130 GBOperationOutdoor unit modelPUHY-RP800YSJM-BPUHY-RP300YJM-BPUHY-RP250YJM-BPUHY-RP250YJM-BOperating conditionsA

Pagina 64 - III Outdoor Unit Components

[ VIII Test Run Mode ] - 147 -HWE10130 GBOperationOutdoor unit modelPUHY-RP850YSJM-BPUHY-RP300YJM-BPUHY-RP300YJM-BPUHY-RP250YJM-BOperating conditions

Pagina 65

[ VIII Test Run Mode ]- 148 -HWE10130 GBOperationOutdoor unit modelPUHY-RP900YSJM-BPUHY-RP300YJM-BPUHY-RP300YJM-BPUHY-RP300YJM-BOperating conditionsA

Pagina 66

- 149 -HWE10130 GBIX Troubleshooting[1] Error Code Lists...

Pagina 68 - <HIGH VOLTAGE WARNING>

[ I Read Before Servicing ] - 7 -HWE10130 GB[6] Air Tightness TestNo changes have been made in the detection method. Note that a refrigerant leak det

Pagina 69

[ IX Troubleshooting ] - 151 -HWE10130 GBIX Troubleshooting[1] Error Code ListsError CodePrelimi-nary error codeError (prelim-inary) detail codeError

Pagina 70 - 2. M-NET board

[ IX Troubleshooting ]- 152 -HWE10130 GB5102 1217 -Temperature sensor faultIndoor unit pipe tempera-ture (TH22)OOA processing unit pipe temperature (

Pagina 71

[ IX Troubleshooting ] - 153 -HWE10130 GBThe last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indica

Pagina 72 - 4. Fan board

[ IX Troubleshooting ]- 154 -HWE10130 GB[2] Responding to Error Display on the Remote Controller1. Error CodeSerial communication error2. Error defin

Pagina 73 - 5. Noise Filter

[ IX Troubleshooting ] - 155 -HWE10130 GB1. Error CodeDischarge temperature fault 2. Error definition and error detection method1) If the discharge

Pagina 74 - IV Remote Controller

[ IX Troubleshooting ]- 156 -HWE10130 GB1. Error CodeLow pressure fault 2. Error definition and error detection methodWhen starting the compressor fr

Pagina 75

[ IX Troubleshooting ] - 157 -HWE10130 GB1. Error CodeHigh pressure/intermediate pressure fault 1 (outdoor unit)2. Error definition and error detecti

Pagina 76

[ IX Troubleshooting ]- 158 -HWE10130 GB1. Error CodeHigh pressure fault 2 (Outdoor unit)2. Error definition and error detection methodIf the pressur

Pagina 77

[ IX Troubleshooting ] - 159 -HWE10130 GB1. Error CodeDrain sensor submergence (Models with a drain sensor)2. Error definition and error detection me

Pagina 78

[ IX Troubleshooting ]- 160 -HWE10130 GB1. Error CodeDrain sensor submergence (Models with a float switch)2. Error definition and error detection met

Pagina 79 - [ IV Remote Controller ]

[ I Read Before Servicing ]- 8 -HWE10130 GB[7] Vacuum Drying (Evacuation)1. Vacuum pump with a reverse-flow check valve (Photo1)To prevent the vacuu

Pagina 80

[ IX Troubleshooting ] - 161 -HWE10130 GB1. Error CodeDrain pump fault (Models with a drain sensor)2. Error definition and error detection method1)

Pagina 81

[ IX Troubleshooting ]- 162 -HWE10130 GB1. Error CodeDrain pump fault (Models with a float switch)2. Error definition and error detection method1)

Pagina 82

[ IX Troubleshooting ] - 163 -HWE10130 GB1. Error CodeDrain sensor (Thd) fault2. Error definition and error detection methodIf the open or short cir

Pagina 83

[ IX Troubleshooting ]- 164 -HWE10130 GB1. Error CodeWater leakage from humidifier2. Error definition and error detection method1) If the float swi

Pagina 84 - V Electrical Wiring Diagram

[ IX Troubleshooting ] - 165 -HWE10130 GB1. Error CodeWater supply cutoff2. Cause, check method and remedy2601Cause Check method and remedy(1) The

Pagina 85

[ IX Troubleshooting ]- 166 -HWE10130 GB1. Error CodeOpen phase2. Error definition and error detection methodAn open phase of the power supply (L1 p

Pagina 86 - <Symbol explanation>

[ IX Troubleshooting ] - 167 -HWE10130 GB1. Error Code<Transmission power supply fault Error detail code FF (Outdoor unit)>2. Error definition

Pagina 87

[ IX Troubleshooting ]- 168 -HWE10130 GB1. Error CodePower supply signal sync error2. Error definition and error detection methodThe frequency cannot

Pagina 88 - VI Refrigerant Circuit

[ IX Troubleshooting ] - 169 -HWE10130 GB1. Error CodeAbnormal bus voltage drop (Detail code 108)2. Error definition and error detection methodIf Vdc

Pagina 89

[ IX Troubleshooting ]- 170 -HWE10130 GB1. Error CodeAbnormal bus voltage rise (Detail code 109)2. Error definition and error detection methodIf Vdc

Pagina 90 - (1) PUHY-RP200 model

[ I Read Before Servicing ] - 9 -HWE10130 GB[8] Refrigerant Charging1. ReasonsR410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F],

Pagina 91

[ IX Troubleshooting ] - 171 -HWE10130 GB1. Error CodeLogic error (Detail code 111)2. Error definition and error detection methodH/W errorIf only the

Pagina 92 - 273 t

[ IX Troubleshooting ]- 172 -HWE10130 GB1. Error CodeLow bus voltage at startup (Detail code 131)2. Error definition and error detection methodWhen V

Pagina 93

[ IX Troubleshooting ] - 173 -HWE10130 GB1. Error CodeOverload protection2. Error definition and error detection methodIf the output current of &quo

Pagina 94

[ IX Troubleshooting ]- 174 -HWE10130 GB1. Error CodeACCT overcurrent relay trip (Detail code 102)DCCT overcurrent relay trip (Detail code 103) Overc

Pagina 95

[ IX Troubleshooting ] - 175 -HWE10130 GB1. Error CodeOvercurrent error due to short-circuited motor (Detail code 105)2. Error definition and error d

Pagina 96 - VII Control

[ IX Troubleshooting ]- 176 -HWE10130 GB1. Error CodeReturn air temperature sensor (TH21) fault (Indoor unit)Return air temperature sensor (TH4) faul

Pagina 97

[ IX Troubleshooting ] - 177 -HWE10130 GB1. Error CodeHIC bypass circuit outlet temperature sensor (TH2) fault (Outdoor unit)Heat exchanger outlet te

Pagina 98

[ IX Troubleshooting ]- 178 -HWE10130 GB1. Error CodeHeatsink temperature sensor (THHS) fault (Detail code 01)2. Error definition and error detection

Pagina 99

[ IX Troubleshooting ] - 179 -HWE10130 GB1. Error CodeACCT sensor fault (Detail code 115)2. Error definition and error detection methodWhen the formu

Pagina 100 - HWE10130 GB

[ IX Troubleshooting ]- 180 -HWE10130 GB1. Error CodeACCT sensor circuit fault (Detail code 117)2. Error definition and error detection methodWhen an

Pagina 101 - Initial vane position

[ I Read Before Servicing ]- 10 -HWE10130 GB[10] Characteristics of the Conventional and the New Refrigerants1. Chemical propertyAs with R22, the new

Pagina 102 - Switch setting timing

[ IX Troubleshooting ] - 181 -HWE10130 GB1. Error CodeDCCT sensor circuit fault (Detail code118)2. Error definition and error detection methodWhen an

Pagina 103 - Rotary switch

[ IX Troubleshooting ]- 182 -HWE10130 GB1. Error CodeOpen-circuited IPM/Loose ACCT connector (Detail code 119)2. Error definition and error detection

Pagina 104 - -4- Control at Start-up

[ IX Troubleshooting ] - 183 -HWE10130 GB1. Error CodeLoose float switch connector2. Error definition and error detection methodDetection of the disc

Pagina 105 - -5- Bypass Control

[ IX Troubleshooting ]- 184 -HWE10130 GB1. Error CodeIndoor unit cleaning operation error2. Error definition and error detection methodThis error is

Pagina 106

[ IX Troubleshooting ] - 185 -HWE10130 GB1. Error CodePolarity setting error2. Error definition and error detection methodThe error detected when tra

Pagina 107

[ IX Troubleshooting ]- 186 -HWE10130 GB1. Error CodeTransmission processor hardware error2. Error definition and error detection methodAlthough &quo

Pagina 108 - 30 seconds

[ IX Troubleshooting ] - 187 -HWE10130 GB1. Error CodeTransmission line bus busy error 2. Error definition and error detection methodGenerated error

Pagina 109

[ IX Troubleshooting ]- 188 -HWE10130 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknowl

Pagina 110 - [ VII Control ]

[ IX Troubleshooting ] - 189 -HWE10130 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknow

Pagina 111

[ IX Troubleshooting ]- 190 -HWE10130 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknowl

Pagina 112 - -16- Emergency Operation Mode

ii HWE10130 GBSafety PrecautionsBefore installing the unit, thoroughly read the following safety precautions.Observe these safety precautions for yo

Pagina 113

[ I Read Before Servicing ] - 11 -HWE10130 GB[11] Notes on Refrigerating Machine Oil1. Refrigerating machine oil in the HFC refrigerant systemHFC ty

Pagina 114 - -17- Operation Mode

[ IX Troubleshooting ] - 191 -HWE10130 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknow

Pagina 115 - -18- DEMAND Control

[ IX Troubleshooting ]- 192 -HWE10130 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknowl

Pagina 116 - [3] Operation Flow Chart

[ IX Troubleshooting ] - 193 -HWE10130 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknow

Pagina 117

[ IX Troubleshooting ]- 194 -HWE10130 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknowl

Pagina 118 - (1) Cooling operation

[ IX Troubleshooting ] - 195 -HWE10130 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknow

Pagina 119 - Stopping the

[ IX Troubleshooting ]- 196 -HWE10130 GB1. Error CodeNo response error 2. Error definition and error detection methodWhen no response command is ret

Pagina 120 - Test run mode

[ IX Troubleshooting ] - 197 -HWE10130 GB1. Error CodeMA controller signal reception error (No signal reception)2. Error definition and error detecti

Pagina 121

[ IX Troubleshooting ]- 198 -HWE10130 GB1. Error CodeMA remote controller signal transmission error (Synchronization error)2. Error definition and er

Pagina 122 - VIII Test Run Mode

[ IX Troubleshooting ] - 199 -HWE10130 GB1. Error CodeMA remote controller signal transmission error (Hardware error)2. Error definition and error de

Pagina 123

[ IX Troubleshooting ]- 200 -HWE10130 GB1. Error CodeMA controller signal reception error (Start bit detection error)2. Error definition and error de

Pagina 124

- 12 -[ I Read Before Servicing ]GBHWE10130

Pagina 125 - [2] Test Run Method

[ IX Troubleshooting ] - 201 -HWE10130 GB1. Error CodeTotal capacity error2. Error definition and error detection methodThe model total of indoor uni

Pagina 126

[ IX Troubleshooting ]- 202 -HWE10130 GB1. Error CodeCapacity code setting error2. Error definition and error detection method Connection of incompat

Pagina 127

[ IX Troubleshooting ] - 203 -HWE10130 GB1. Error CodeWrong number of connected units2. Error definition and error detection method The number of con

Pagina 128 - Liquid

[ IX Troubleshooting ]- 204 -HWE10130 GB1. Error CodeAddress setting error2. Error definition and error detection methodErroneous setting of OC unit

Pagina 129

[ IX Troubleshooting ] - 205 -HWE10130 GB1. Error CodeConnection information signal transmission/reception error2. Error definition and error detecti

Pagina 130 - (Note 1)

[ IX Troubleshooting ]- 206 -HWE10130 GB1. Error CodeFunction setting error 2. Error source, cause, check method and remedy1. Error CodeREPLACE unit

Pagina 131

[ IX Troubleshooting ] - 207 -HWE10130 GB1. Error CodeIncompatible unit combination 2. Error definition and error detection methodThe check code will

Pagina 132

[ IX Troubleshooting ]- 208 -HWE10130 GB-1- Troubleshooting according to the remote controller malfunction or the external input errorIn the case of

Pagina 133

[ IX Troubleshooting ] - 209 -HWE10130 GBIn the case of MA remote controller2. PhenomenaWhen the remote controller operation SW is turned on, the ope

Pagina 134

[ IX Troubleshooting ]- 210 -HWE10130 GBIn the case of MA remote controller3. Phenomena"HO" or "PLEASE WAIT" display on the remot

Pagina 135

- 13 -HWE10130 GBII Restrictions[1] System configuration ...

Pagina 136

[ IX Troubleshooting ] - 211 -HWE10130 GBFlow chartEven if the operation button on the remote controller is pressed, the indoor and the outdoor units

Pagina 137

[ IX Troubleshooting ]- 212 -HWE10130 GBIn case of ME remote controller1. PhenomenaEven if the operation button on the remote controller is pressed,

Pagina 138

[ IX Troubleshooting ] - 213 -HWE10130 GBIn case of ME remote controller2. PhenomenaWhen the remote controller operation SW is turned on, a temporary

Pagina 139

[ IX Troubleshooting ]- 214 -HWE10130 GBIn case of ME remote controller3. Phenomena"HO" display on the remote controller does not disappear

Pagina 140

[ IX Troubleshooting ] - 215 -HWE10130 GBIn case of ME remote controller4. Phenomena"88" appears on the remote controller when the address

Pagina 141

[ IX Troubleshooting ]- 216 -HWE10130 GBBoth for MA remote controller and ME remote controller1. PhenomenaAlthough cooling operation starts with the

Pagina 142

[ IX Troubleshooting ] - 217 -HWE10130 GBCause Check method and remedy4. Long piping lengthThe cooling capacity varies greatly depending on the press

Pagina 143

[ IX Troubleshooting ]- 218 -HWE10130 GB2. PhenomenaAlthough heating operation starts with the normal remote controller display, the capacity is not

Pagina 144

[ IX Troubleshooting ] - 219 -HWE10130 GBCause Check method and remedy2. Indoor unit LEV malfunctionInsufficient refrigerant flows due to LEV malfunc

Pagina 145

[ IX Troubleshooting ]- 220 -HWE10130 GB3. PhenomenaOutdoor unit stops at times during operation.(1) Cause, check method and remedyCause Check metho

Pagina 147

[ IX Troubleshooting ] - 221 -HWE10130 GB[3] Investigation of Transmission Wave Shape/Noise1. M-NET transmissionControl is performed by exchanging si

Pagina 148

[ IX Troubleshooting ]- 222 -HWE10130 GB(3) Check method and remedy1) Measures against noiseCheck the followings when noise exists on the wave or

Pagina 149

[ IX Troubleshooting ] - 223 -HWE10130 GB2. MA remote controller transmissionThe communication between the MA remote controller and the indoor unit

Pagina 150

[ IX Troubleshooting ]- 224 -HWE10130 GB[4] Troubleshooting Principal Parts-1- High-pressure sensor (63HS1) and intermediate-pressure sensor (63HS2)1

Pagina 151

[ IX Troubleshooting ] - 225 -HWE10130 GB-2- Low-Pressure Sensor (63LS)1. Compare the pressure that is detected by the low pressure sensor, and the

Pagina 152

[ IX Troubleshooting ]- 226 -HWE10130 GB-3- Solenoid ValveCheck whether the output signal from the control board and the operation of the solenoid va

Pagina 153

[ IX Troubleshooting ] - 227 -HWE10130 GB(3) SV1a and SV1b (bypass valve)This solenoid valve turns on when energized (when the relay is on).1) Thi

Pagina 154

[ IX Troubleshooting ]- 228 -HWE10130 GB-5- LEVLEV operationLEV (Indoor unit: Linear expansion valve), SLEV, LEV1, LEV2a, and LEV2b (Outdoor unit: Li

Pagina 155

[ IX Troubleshooting ] - 229 -HWE10130 GB(2) Outdoor LEV (SLEV, LEV1)The valve opening changes according to the number of pulses.1) Connections be

Pagina 156

[ IX Troubleshooting ]- 230 -HWE10130 GB(3) Judgment methods and possible failure modeThe specifications of the outdoor unit (outdoor LEV) and the i

Pagina 157

[ II Restrictions ] - 15 -HWE10130 GBII Restrictions[1] System configuration1. Table of compatible indoor unitsThe table below summarizes the types

Pagina 158 - IX Troubleshooting

[ IX Troubleshooting ] - 231 -HWE10130 GB(4) Outdoor unit LEV (LEV1) coil removal procedure1) LEV componentAs shown in the figure, the outdoor LEV

Pagina 159

[ IX Troubleshooting ]- 232 -HWE10130 GB(5) Outdoor unit LEV (LEV2a,2b) coil removal procedureNotes on the procedure1) Do not put undue pressure on

Pagina 160 - Remote controller

[ IX Troubleshooting ] - 233 -HWE10130 GBReplacement procedure1) Stop the air conditioner. After checking that the air conditioner is stopped, turn

Pagina 161

[ IX Troubleshooting ]- 234 -HWE10130 GB-6- InverterReplace only the compressor if only the compressor is found to be defective. Replace only the f

Pagina 162

[ IX Troubleshooting ] - 235 -HWE10130 GBError display/failure condition Measure/inspection item[1] Inverter related errors4250, 4255, 4220, 4225, 42

Pagina 163

[ IX Troubleshooting ]- 236 -HWE10130 GB(2) Inverter output related troublesItems to be checked Phenomena Remedy[1]Check the INV board er-ror detecti

Pagina 164

[ IX Troubleshooting ] - 237 -HWE10130 GBItems to be checked Phenomena Remedy[3]Check whether the inverter is damaged.(No load)(1) Disconnect the inv

Pagina 165

[ IX Troubleshooting ]- 238 -HWE10130 GB[6]Check the fan inverter board failure.(1) Check the fan output wir-ing.Connector contact failureBoard sid

Pagina 166 - +0,-0.15

[ IX Troubleshooting ] - 239 -HWE10130 GB(3) Trouble treatment when the main power breaker is tripped(4) Trouble treatment when the main power eart

Pagina 167

[ IX Troubleshooting ]- 240 -HWE10130 GB(5) Simple checking procedure for individual components of main inverter circuitBefore inspecting the inside

Pagina 168

[ II Restrictions ]- 16 -HWE10130 GB[2] Types and Maximum allowable Length of Cables1. Wiring work (1) Notes1) Have all electrical work performed b

Pagina 169

[ IX Troubleshooting ] - 241 -HWE10130 GBINV board external diagramJudgment value (reference)Black ( + )SC-P1 FT-N SC-L1 SC-L2 SC-L3Red (-)SC-P1 - -

Pagina 170

[ IX Troubleshooting ]- 242 -HWE10130 GB-7- Control Circuit(1) Control power source function blockOutdoor unit Power source system (AC 380 / 415 V)Co

Pagina 171

[ IX Troubleshooting ] - 243 -HWE10130 GB(2) Troubleshooting transmission power circuit of outdoor unitCheck the voltage between No.1 and No.2 pins

Pagina 172

[ IX Troubleshooting ]- 244 -HWE10130 GB[5] Refrigerant Leak1. Leak spot: In the case of extension pipe for indoor unit (Cooling season)1) Mount a

Pagina 173

[ IX Troubleshooting ] - 245 -HWE10130 GB2) Therefore, if the power source is turned off within 30 minutes, the lev remains fully closed and the re

Pagina 174

[ IX Troubleshooting ]- 246 -HWE10130 GB[6] Compressor Replacement Instructions Follow the procedures below (Steps 1 through 6) to remove the comp

Pagina 175

[ IX Troubleshooting ] - 247 -HWE10130 GB Compressor cover (top) 4. Remove the compressor cover (top). 5. Remove the compressor wires, compressor

Pagina 176

[ IX Troubleshooting ]- 248 -HWE10130 GB1. Plate heat exchanger ASSY replacement instructions* Following instructions show procedures for replacing

Pagina 177

[ IX Troubleshooting ] - 249 -HWE10130 GB[7] Troubleshooting Using the Outdoor Unit LED Error DisplayIf the LED error display appear as follows while

Pagina 178

- 250 -[ IX Troubleshooting ]GBHWE10130

Pagina 179

[ II Restrictions ] - 17 -HWE10130 GB2) Remote controller wiring*1 MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA

Pagina 180

- 251 -HWE10130 GBX LED Monitor Display on the Outdoor Unit Board[1] How to Read the LED on the Service Monitor ...

Pagina 181

- 252 -

Pagina 182

[ X LED Monitor Display on the Outdoor Unit Board ] - 253 -HWE10130 GBX LED Monitor Display on the Outdoor Unit Board[1] How to Read the LED on the S

Pagina 183

[ X LED Monitor Display on the Outdoor Unit Board ]- 254 -HWE10130 GB3. Time data storage functionThe outdoor unit has a simple clock function that

Pagina 184

[ X LED Monitor Display on the Outdoor Unit Board ]- 255 -HWE10130ILED Monitor Di splay on the Outdoor Unit BoardLED monitor displayCurrent dataNo.SW

Pagina 185

[ X LED Monitor Display on the Outdoor Unit Board ]- 256 -HWE1013011 1101000000External signal(Open input contact point)Contact point de-mandLow-nois

Pagina 186

[ X LED Monitor Display on the Outdoor Unit Board ]- 257 -HWE1013024 0001100000Indoor unit thermo-statTop Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4

Pagina 187

[ X LED Monitor Display on the Outdoor Unit Board ]- 258 -HWE1013045 1011010000 TH4 -99.9 to 999.9 A A The unit is [°C]46 0111010000 TH3 -99.9 to 999

Pagina 188

[ X LED Monitor Display on the Outdoor Unit Board ]- 259 -HWE1013071 111000100072 000100100073 100100100074 010100100075 110100100076 001100100077 10

Pagina 189

[ X LED Monitor Display on the Outdoor Unit Board ]- 260 -HWE1013093 1011101000 All AK (OC+OS) 0000 to 9999 B94 0111101000 AK 0000 to 9999 A A95 1111

Pagina 190

[ II Restrictions ]- 18 -HWE10130 GB(3) Reusability check of the existing transmission lines for Replace Multi unitsCheck the existing wires for dama

Pagina 191

[ X LED Monitor Display on the Outdoor Unit Board ]- 261 -HWE10130117 1010111000COMP Operation timeUpper 4 digits0000 to 9999 A AThe unit is [ h ]118

Pagina 192

[ X LED Monitor Display on the Outdoor Unit Board ]- 262 -HWE10130138 0101000100139 1101000100140 0011000100141 1011000100142 0111000100143 111100010

Pagina 193

[ X LED Monitor Display on the Outdoor Unit Board ]- 263 -HWE10130166 0110010100 167 1110010100 168 0001010100 169 1001010100 170 0101010100 171 1101

Pagina 194

[ X LED Monitor Display on the Outdoor Unit Board ]- 264 -HWE10130178 0100110100 Error history 1 0000 to 9999 B B Address and error codes highlighted

Pagina 195

[ X LED Monitor Display on the Outdoor Unit Board ]- 265 -HWE10130Data before errorNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 LD3 LD4 LD

Pagina 196

[ X LED Monitor Display on the Outdoor Unit Board ]- 266 -HWE10130216 0001101100 TH4 -99.9 to 999.9 A A The unit is [°C]217 1001101100 TH3 -99.9 to 9

Pagina 197

[ X LED Monitor Display on the Outdoor Unit Board ]- 267 -HWE10130242 0100111100243 1100111100244 0010111100245 1010111100246 0110111100247 111011110

Pagina 198

[ X LED Monitor Display on the Outdoor Unit Board ]- 268 -HWE10130267 1101000010Fan inverter output fre-quency0000 to 9999 A ATwice the actual output

Pagina 199

[ X LED Monitor Display on the Outdoor Unit Board ]- 269 -HWE10130292 0010010010293 1010010010294 0110010010COMP number of start-stop eventsUpper 4 d

Pagina 200

[ X LED Monitor Display on the Outdoor Unit Board ]- 270 -HWE10130Current dataNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD6

Pagina 201

[ II Restrictions ] - 19 -HWE10130 GBTable AIs the 2-core cable used?Is the 2-core cable used?Is the 2-core cable used?YESNOYESNOYESYES YESNOYESNOYES

Pagina 202

[ X LED Monitor Display on the Outdoor Unit Board ]- 271 -HWE10130328 0001001010 329 1001001010 330 0101001010 331 1101001010 332 0011001010 333 1011

Pagina 203

[ X LED Monitor Display on the Outdoor Unit Board ]- 272 -HWE10130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 L

Pagina 204

[ X LED Monitor Display on the Outdoor Unit Board ]- 273 -HWE10130368 0000111010 IC18 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alt

Pagina 205

[ X LED Monitor Display on the Outdoor Unit Board ]- 274 -HWE10130396 0011000110 IC46 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alt

Pagina 206

[ X LED Monitor Display on the Outdoor Unit Board ]- 275 -HWE10130412 0011100110 IC5 Suction temperature -99.9 to 999.9 B The unit is [°C]413 1011100

Pagina 207

[ X LED Monitor Display on the Outdoor Unit Board ]- 276 -HWE10130436 0010110110 IC29 Suction temperature -99.9 to 999.9 B The unit is [°C]437 101011

Pagina 208

[ X LED Monitor Display on the Outdoor Unit Board ]- 277 -HWE10130464 0000101110 IC7 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]465 100

Pagina 209

[ X LED Monitor Display on the Outdoor Unit Board ]- 278 -HWE10130492 0011011110 IC35 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]493 10

Pagina 210

[ X LED Monitor Display on the Outdoor Unit Board ]- 279 -HWE10130Setting dataNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD6

Pagina 211

[ X LED Monitor Display on the Outdoor Unit Board ]- 280 -HWE10130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 L

Pagina 212

[ II Restrictions ]- 20 -HWE10130 GBReusability of Transmission lineIs the 2-core cable used?Is the shielded wiring used?Refer to Table A.Fix the gro

Pagina 213

[ X LED Monitor Display on the Outdoor Unit Board ]- 281 -HWE10130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 L

Pagina 214

[ X LED Monitor Display on the Outdoor Unit Board ]- 282 -HWE10130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD

Pagina 215

[ X LED Monitor Display on the Outdoor Unit Board ]- 283 -HWE10130600 0001101001 IC28SH -99.9 to 999.9 B The unit is [ °C ] 601 1001101001 IC29SH -99

Pagina 216

[ X LED Monitor Display on the Outdoor Unit Board ]- 284 -HWE10130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD

Pagina 217

[ X LED Monitor Display on the Outdoor Unit Board ]- 285 -HWE10130650 0101000101 IC28SC -99.9 to 999.9 B The unit is [ °C ] 651 1101000101 IC29SC -9

Pagina 218

[ X LED Monitor Display on the Outdoor Unit Board ]- 286 -HWE10130Setting dataNo.SW1ItemDisplayUnit(A, B)* 1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD6

Pagina 219 - Replace the ME remote

[ X LED Monitor Display on the Outdoor Unit Board ]- 287 -HWE10130688 0000110101 Current time 00:00 to 23:59 A A Hour: minute689 1000110101 Current

Pagina 220 - Flow chart

[ X LED Monitor Display on the Outdoor Unit Board ]- 288 -HWE10130702 0111110101 Time of error detection 7 00:00 to 23:59 A A Hour: minute703 111111

Pagina 221

[ X LED Monitor Display on the Outdoor Unit Board ]- 289 -HWE10130Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B)* 1Remarks1234567890 LD1 LD2 L

Pagina 222 - Connector contact failure

[ X LED Monitor Display on the Outdoor Unit Board ]- 290 -HWE10130741 1010011101 IC28 LEV opening 0000 to 9999 B Fully open: 2000742 0110011101 IC2

Pagina 223

iiHWE10130 GBWARNINGSecurely attach the terminal block cover (panel) to the unit.If the terminal block cover (panel) is not installed properly, dust a

Pagina 224

[ II Restrictions ] - 21 -HWE10130 GB0501001502000 5 10 15 20 25 3230Number of indoor unitsLength of transmission line to the farthest unit (m)0.75mm

Pagina 225 - Evaporating temperature Te

[ X LED Monitor Display on the Outdoor Unit Board ]- 291 -HWE10130769 1000000011 IC6 Operation mode0000 : Stop 0001 : Ventilation 0002 : Cooling

Pagina 226

[ X LED Monitor Display on the Outdoor Unit Board ]- 292 -HWE10130797 1011100011 IC34 Operation mode0000 : Stop 0001 : Ventilation 0002 : Cooling

Pagina 227 - Condensing temperature Tc

[ X LED Monitor Display on the Outdoor Unit Board ]- 293 -HWE10130825 1001110011 IC12 filter 0000 to 9999 B Hours since last mainte-nance [ h ]826 0

Pagina 228

[ X LED Monitor Display on the Outdoor Unit Board ]- 294 -HWE10130853 1010101011 IC40 filter 0000 to 9999 B Hours since last mainte-nance [ h ]854

Pagina 229

[ X LED Monitor Display on the Outdoor Unit Board ]- 295 -HWE10130Other types of dataNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 LD3 LD4

Pagina 230 - [Without transmission]

[ X LED Monitor Display on the Outdoor Unit Board ]- 296 -HWE10130887 1110111011 888 0001111011 889 1001111011 890 0101111011 891 1101111011 892 0011

Pagina 231

Service HandbookService HandbookPUHY-RP250, RP300, RP350YJM-BPUHY-RP400, RP450, RP500, RP550, RP600, RP650YSJM-BPUHY-RP700, RP750, RP800, RP850, RP900

Pagina 232

[ II Restrictions ]- 22 -HWE10130 GB[3] Switch Settings and Address Settings1. Switch settingRefer to section "[5] An Example of a System to whi

Pagina 233 - Vout 0.5 ~ 3.5 V

[ II Restrictions ] - 23 -HWE10130 GB2. M-NET Address settings(1) Address settings tableThe need for address settings and the range of address setti

Pagina 234 - Vout 0.5 ~ 3.5 V

[ II Restrictions ]- 24 -HWE10130 GB(2) Power supply switch connector connection on the outdoor unit(Factory setting: The male power supply switch c

Pagina 235 - -3- Solenoid Valve

[ II Restrictions ] - 25 -HWE10130 GB(6) Miscellaneous settingsCooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 &

Pagina 236 - 12345678 9 10

[ II Restrictions ]- 26 -HWE10130 GBExample of wiring connection(1) CN51(2) CN3SCN51XYL1L2ecruos rewop pmaLDistant control boardRelay circuit Adapter

Pagina 237

[ II Restrictions ] - 27 -HWE10130 GB1. Demand control(1) General outline of controlDemand control is performed by using the external signal input to

Pagina 238 - 12345678

[ II Restrictions ]- 28 -HWE10130 GB3) 8-step demand control (When SW4-4 is set to ON on two outdoor units)Demand capacity is shown below.*1. The o

Pagina 239 - Linear Expansion Valve

[ II Restrictions ] - 29 -HWE10130 GB[4] Sample System ConnectionExamples of typical system connection are shown on pages [5] to [7]. Refer to the In

Pagina 240 - Lead wire

- 30 -[ II Restrictions ]GBHWE10130[5] An Example of a System to which an MA Remote Controller is connected1. System with one outdoor unit (automati

Pagina 241 - Molybdenum

iiiiii HWE10130 GBPrecautions for handling units for use with R410ACAUTIONUse refrigerant piping made of phosphorus deoxidized copper and copper alloy

Pagina 242

[ II Restrictions ] 31- 31 -HWE10130 GB(4) Wiring method1) Indoor/outdoor transmission lineDaisy-chain terminals M1 and M2 on the terminal block fo

Pagina 243 - -6- Inverter

- 32 -[ II Restrictions ]GBHWE101302. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected (manual address se

Pagina 244

[ II Restrictions ] 33- 33 -HWE10130 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 1.Shielded cable connectionSame as [5] 1.2)

Pagina 245

- 34 -[ II Restrictions ]GBHWE101303. Group operation of units in a system with multiple outdoor units(1) Sample control wiring(2) Cautions1) ME r

Pagina 246

[ II Restrictions ] 35- 35 -HWE10130 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 1.Only use shielded cables.Shielded cable c

Pagina 247

- 36 -[ II Restrictions ]GBHWE101304. A system in which a system controller is connected to the transmission line for centralized control and which

Pagina 248

[ II Restrictions ] 37- 37 -HWE10130 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 1.Only use shielded cables.Shielded cable co

Pagina 249

- 38 -[ II Restrictions ]GBHWE101305. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (exce

Pagina 250

[ II Restrictions ] 39- 39 -HWE10130 GB(4) Wiring method1) Indoor/outdoor transmission lineDaisy-chain terminals M1 and M2 on the terminal block fo

Pagina 251 - -7- Control Circuit

- 40 -[ II Restrictions ]GBHWE10130[6] An Example of a System to which an ME Remote Controller is connected(1) Sample control wiring(2) Cautions1)

Pagina 252

ivHWE10130 GBBefore installing the unitWARNINGDo not install the unit where a gas leak may occur.If gaseous refrigerant leaks and piles up around the

Pagina 253 - [5] Refrigerant Leak

[ II Restrictions ] 41- 41 -HWE10130 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 1.Shielded cable connectionSame as [5] 1.2)

Pagina 254

- 42 -[ II Restrictions ]GBHWE10130[7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected(1) Sample con

Pagina 255

[ II Restrictions ] 43- 43 -HWE10130 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 1.Shielded cable connectionSame as [5] 1.2)

Pagina 256

[ II Restrictions ]- 44 -HWE10130 GB[8] Restrictions on Pipe Length1. Determining the reusability of the existing pipingMitsubishi Electric Corporat

Pagina 257 - * Precautions for brazing

[ II Restrictions ] - 45 -HWE10130 GBCAUTIONCharge refrigerant in the liquid state.If gaseous refrigerant is drawn out of the cylinder first, the co

Pagina 258

[ II Restrictions ]- 46 -HWE10130 GBDetermining the reusability of the existing pipingYESYESYESYESYESYESYESYESNONONONONONOYESNONONODoes the piping di

Pagina 259

[ II Restrictions ] - 47 -HWE10130 GB2. Restrictions on pipe length(1) End branchingRP200, RP250, RP300, RP350 models1) Maximum allowable piping l

Pagina 260

[ II Restrictions ]- 48 -HWE10130 GBRP400, RP450, RP500, RP550 models1) Maximum allowable piping length depends on the total amount of refrigerant

Pagina 261

[ II Restrictions ] - 49 -HWE10130 GBRP600, RP650 models1) Maximum allowable piping length depends on the total amount of refrigerant in a given sy

Pagina 262 - 7SEG LED

[ II Restrictions ]- 50 -HWE10130 GBRP700, RP750, RP800, RP850, RP900 models1) Maximum allowable piping length depends on the total amount of refri

Pagina 263 - Day count

vv HWE10130 GBBefore installing the unit (moving and reinstalling the unit) and performing electrical workCAUTIONProperly ground the unit.Do not conne

Pagina 264 - Current data

[ II Restrictions ] - 51 -HWE10130 GB(2) Using a branch joint to merge the existing piping systems1) The maximum allowable piping length for the R

Pagina 265

[ II Restrictions ]- 52 -HWE10130 GB3. Refrigerant pipe size(1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdo

Pagina 266

[ II Restrictions ] - 53 -HWE10130 GB(3) Size of the refrigerant pipe between the branches for connection to indoor units (4) Size of the refrigera

Pagina 267

- 54 -[ II Restrictions ]GBHWE10130

Pagina 268

- 55 -HWE10130 GBIII Outdoor Unit Components[1] Outdoor Unit Components and Refrigerant Circuit ...

Pagina 270

[ III Outdoor Unit Components ] - 57 -HWE10130 GBIII Outdoor Unit Components[1] Outdoor Unit Components and Refrigerant Circuit1. Front view of an o

Pagina 271

[ III Outdoor Unit Components ]- 58 -HWE10130 GB2. Refrigerant circuit(1) PUHY-RP200, RP250, RP300, RP350YJM-BCheck valve(CV1)High-pressure switch(63

Pagina 272

[ III Outdoor Unit Components ] - 59 -HWE10130 GB[2] Control Box of the Outdoor Unit1) Exercise caution not to damage the bottom and the front pane

Pagina 273

[ III Outdoor Unit Components ]- 60 -HWE10130 GB[3] Outdoor Unit Circuit Board1. Outdoor unit control boardCN332 Output 18VDC GND (Fan boar

Pagina 274 - Data before error

viHWE10130 GBBefore the test runCAUTIONTurn on the unit at least 12 hours before the test run.Keep the unit turned on throughout the season. If the un

Pagina 275

[ III Outdoor Unit Components ] - 61 -HWE10130 GB2. M-NET board Power supply output for centralized control system Indoor/outdoor tr

Pagina 276 - The unit is [°C]

[ III Outdoor Unit Components ]- 62 -HWE10130 GB3. INV board1) Before inspecting the inside of the control box, turn off the power, keep the unit o

Pagina 277

[ III Outdoor Unit Components ] - 63 -HWE10130 GB4. Fan boardCNVDCBus voltage input N PCNINVInverter output W V UCN18V Input 18VDC

Pagina 278

[ III Outdoor Unit Components ]- 64 -HWE10130 GB5. Noise FilterCN4Output(Rectified L2-N current) P NCN5Output(Rectified L2-N current) P N

Pagina 279

- 65 -HWE10130 GBIV Remote Controller[1] Functions and Specifications of MA and ME Remote Controllers ...67[2] Group S

Pagina 281 - Data on indoor unit system

[ IV Remote Controller ] - 67 -HWE10130 GBIV Remote Controller[1] Functions and Specifications of MA and ME Remote ControllersThere are two types of

Pagina 282

[ IV Remote Controller ]- 68 -HWE10130 GB[2] Group Settings and Interlock Settings via the ME Remote Controller1. Group settings/interlock settings&l

Pagina 283

[ IV Remote Controller ] - 69 -HWE10130 GB<Entry found> <No entries found> (C) To return to the normal display When all the group setting

Pagina 284

[ IV Remote Controller ]- 70 -HWE10130 GB2. Remote controller function selection via the ME remote controller(A) To delete group settings(B) To dele

Pagina 285

CONTENTSHWE10130 GBI Read Before Servicing[1] Read Before Servicing...

Pagina 286

[ IV Remote Controller ] - 71 -HWE10130 GB[Lower limit temperature]: Appears in the preset temperature display window [Upper limit temperature: Appe

Pagina 287

[ IV Remote Controller ]- 72 -HWE10130 GB[3] Interlock Settings via the MA Remote Controller1. LOSSNAY interlock setting (Make this setting only whe

Pagina 288 - Setting data

[ IV Remote Controller ] - 73 -HWE10130 GB[4] Using the built-in Temperature Sensor on the Remote Controller1. Selecting the position of temperature

Pagina 289

- 74 -[ IV Remote Controller ]GBHWE10130

Pagina 290

- 75 -HWE10130 GBV Electrical Wiring Diagram[1] Electrical Wiring Diagram of the Outdoor Unit ...

Pagina 292

[ V Electrical Wiring Diagram ] - 77 -HWE10130 GBV Electrical Wiring Diagram[1] Electrical Wiring Diagram of the Outdoor Unit1. Electrical wiring di

Pagina 293

[ V Electrical Wiring Diagram ]- 78 -HWE10130 GB[2] Electrical Wiring Diagram of Transmission Booster100V/200VAC Terminal block for power supply (TB1

Pagina 294

- 79 -HWE10130 GBVI Refrigerant Circuit[1] Refrigerant Circuit Diagram ...

Pagina 296

HWE10130 GB

Pagina 297

[ VI Refrigerant Circuit ] - 81 -HWE10130 GBVI Refrigerant Circuit[1] Refrigerant Circuit Diagram1. Outdoor unit(1) PUHY-RP200 model(2) PUHY-RP250,

Pagina 298

[ VI Refrigerant Circuit ]- 82 -HWE10130 GB[2] Principal Parts and Functions1. Outdoor unitPart nameSymbols (functions)Notes Usage Specifications Che

Pagina 299

[ VI Refrigerant Circuit ] - 83 -HWE10130 GBThermis-torTH4(Discharge)1) Detects discharge air temper-ature2) Provides high-pressure pro-tectionDe

Pagina 300

[ VI Refrigerant Circuit ]- 84 -HWE10130 GBSole-noid valveSV1a, SV1bDischarge-suc-tion bypass1) High/low pressure bypass at start-up and stopping,

Pagina 301

[ VI Refrigerant Circuit ] - 85 -HWE10130 GB2. Indoor UnitPart Name Symbol (functions) Notes Usage Specification Check method Linear expan-sion valv

Pagina 302

[ VI Refrigerant Circuit ]- 86 -HWE10130 GB

Pagina 303

- 87 -HWE10130 GBVII Control[1] Functions and Factory Settings of the Dipswitches ...89[2] Contr

Pagina 305

[ VII Control ] - 89 -HWE10130 GBVII Control[1] Functions and Factory Settings of the Dipswitches1. Outdoor unit(1) Control board1) Unless otherwis

Pagina 306 - PUHY-RP250, RP300, RP350YJM-B

[ VII Control ]- 90 -HWE10130 GB1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF fo