R2-SERIES (Feb. 2009)
R2-1
R2-SERIES
DATA U4
1. SPECIFICATIONS ...................................................................................................................................................... R2-2
1-1. PURY-P72~240T(S)HMU-A (-BS) 208 / 230V Specifications ...................................................................... R2-2
1-2. PURY-P72~240Y(S)HMU-A (-BS) 460V Specifications ............................................................................... R2-9
1-3. Energy Efficiencies .................................................................................................................................... R2-16
2. EXTERNAL DIMENSIONS ....................................................................................................................................... R2-17
3. CENTER OF GRAVITY ............................................................................................................................................ R2-31
4. ELECTRICAL WIRING DIAGRAMS .........................................................................................................................R2-32
5. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS .......................................................................R2-35
6. SOUND PRESSURE LEVELS ................................................................................................................................. R2-36
7. CAPACITY TABLES ..................................................................................................................................................R2-39
7-1. Correction by Temperature ......................................................................................................................... R2-39
7-2. Correction by Total Indoor .......................................................................................................................... R2-42
7-3. Correction by Refrigerant Piping Length ....................................................................................................R2-46
7-4. Correction at Frost and Defrost ..................................................................................................................R2-48
7-5. Operation Temperature Range ................................................................................................................... R2-48
8. OPTIONAL PARTS ................................................................................................................................................... R2-49
8-1. Joint ........................................................................................................................................................... R2-49
8-2. Twinning Kit ................................................................................................................................................R2-50
8-3. Joint Adapter Kit CMY-R160J for BC Controller .........................................................................................R2-51
R2-SERIES
OUTDOOR UNITS
Vista de pagina 0
1 2 3 4 5 6 ... 67 68

Indice de contenidos

Pagina 1 - OUTDOOR UNITS

R2-SERIES (Feb. 2009)R2-1R2-SERIESDATA U41. SPECIFICATIONS ...

Pagina 2

R2-10R2-SERIES (Feb. 2009)R2-SERIESDATA U4R2-SERIES (460V) Model PURY-P120YHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60HzCooling capacity (Nomin

Pagina 3

R2-SERIES (Feb. 2009)R2-11R2-SERIESDATA U4Model PURY-P144YSHMU-A(-BS)Power source3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal) *1 BTU / h144,

Pagina 4

R2-12R2-SERIES (Feb. 2009)R2-SERIESDATA U4R2-SERIES (460V)Model PURY-P168YSHMU-A(-BS)Power source3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal

Pagina 5

R2-SERIES (Feb. 2009)R2-13R2-SERIESDATA U4Model PURY-P192YSHMU-A(-BS)Power source3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal) *1 BTU / h192,

Pagina 6

R2-14R2-SERIES (Feb. 2009)R2-SERIESDATA U4R2-SERIES (460V)Model PURY-P216YSHMU-A(-BS)Power source3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal

Pagina 7

R2-SERIES (Feb. 2009)R2-15R2-SERIESDATA U4Model PURY-P240YSHMU-A(-BS)Power source3-phase 3-wire 460V 10% 60HzCooling capacity (Nominal) *1 BTU / h240,

Pagina 8

R2-16R2-SERIES (Feb. 2009)R2-SERIESDATA U41. SPECIFICATIONS1-3. ENERGY EFFICIENCIESModel Number Nominal Cooling CapacityCooling EER Heating 47º F COP

Pagina 9

R2-SERIES (Feb. 2009)R2-17R2-SERIESDATA U42. EXTERNAL DIMENSIONS(Mounting pitch)221 150146869290 771402217520118514514558217For wires(10-9/32)(9-7/16)

Pagina 10 - 1. SPECIFICATIONS

R2-18R2-SERIES (Feb. 2009)R2-SERIESDATA U42. EXTERNAL DIMENSIONS In case of single installation1.Required space around the unit When the height of

Pagina 11

R2-SERIES (Feb. 2009)R2-19R2-SERIESDATA U4(Mounting pitch)ø45 Knockout hole(Uses when twinning kit (optional parts) is mounted.)Front through holeø34

Pagina 12

R2-2R2-SERIES (Feb. 2009)R2-SERIESDATA U4R2-SERIES (208 / 230V) Model PURY-P72THMU-A(-BS) PURY-P96THMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 1

Pagina 13

R2-20R2-SERIES (Feb. 2009)R2-SERIESDATA U4 In case of single installation1.Required space around the unit When the height of the walls on the front

Pagina 14

R2-SERIES (Feb. 2009)R2-21R2-SERIESDATA U4Twinning pipe ~ Outdoor unitUnit modelP72d or fc or eLow pressureHigh pressureTwinning pipe (High pressure)&

Pagina 15

R2-22R2-SERIES (Feb. 2009)R2-SERIESDATA U4P96P72Twinning pipe ~ Outdoor unitc or ed or fHigh pressureLow pressureUnit modelTwinning pipe (Low pressure

Pagina 16 - 1-3. ENERGY EFFICIENCIES

R2-SERIES (Feb. 2009)R2-23R2-SERIESDATA U4P96P120Unit modelLow pressureHigh pressureTwinning pipe ~ Outdoor unitOutdoor unit 1Outdoor unit 2Front view

Pagina 17 - 2. EXTERNAL DIMENSIONS

R2-24R2-SERIES (Feb. 2009)R2-SERIESDATA U42. EXTERNAL DIMENSIONS(Mounting pitch)221 150146869290 771402217520118514514558217ø45 Knockout hole(Uses whe

Pagina 18

R2-SERIES (Feb. 2009)R2-25R2-SERIESDATA U4 In case of single installation1.Required space around the unit When the height of the walls on the front

Pagina 19

R2-26R2-SERIES (Feb. 2009)R2-SERIESDATA U4(Mounting pitch)ø45 Knockout hole(Uses when twinning kit (optional parts) is mounted.)Front through holeø34

Pagina 20

R2-SERIES (Feb. 2009)R2-27R2-SERIESDATA U4 In case of single installation1.Required space around the unit When the height of the walls on the front

Pagina 21

R2-28R2-SERIES (Feb. 2009)R2-SERIESDATA U4High pressureLow pressurec or ed or fP72Unit modelTwinning pipe ~ Outdoor unitTwinning pipe (High pressure)&

Pagina 22

R2-SERIES (Feb. 2009)R2-29R2-SERIESDATA U4Unit modelLow pressureHigh pressured or fc or eTwinning pipe ~ Outdoor unitP72P96Twinning pipe (Low pressure

Pagina 23 - Unit : mm(in)

R2-SERIES (Feb. 2009)R2-3R2-SERIES Model PURY-P120THMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity (Nominal) *1 BTU / h 120

Pagina 24

R2-30R2-SERIES (Feb. 2009)R2-SERIESDATA U4Twinning pipe ~ Outdoor unitc or ed or fHigh pressureLow pressureUnit modelP120P96Outdoor unit 1Outdoor unit

Pagina 25

R2-SERIES (Feb. 2009)R2-31R2-SERIESDATA U43. CENTER OF GRAVITYPURY-P72THMU-A (-BS)PURY-P72YHMU-A (-BS)PURY-P96, 120THMU-A (-BS)PURY-P96, 120YHMU-A (-B

Pagina 26

R2-32R2-SERIES (Feb. 2009)R2-SERIESDATA U44. ELECTRICAL WIRING DIAGRAMSLGGroundGHeat exchanger low pressurebypassSV5cExplanationSymbol1SV5bX0536CN5066

Pagina 27

R2-SERIES (Feb. 2009)R2-33R2-SERIESDATA U44. ELECTRICAL WIRING DIAGRAMSGSV1aGGroundGHeat exchanger low pressurebypassExplanationSymbolLED1:Normal oper

Pagina 28

R2-34R2-SERIES (Feb. 2009)R2-SERIESDATA U44. ELECTRICAL WIRING DIAGRAMSGGGGroundpurpleX11X123561CN509blue1CN510yellowX09X10356CN508blackUnit addressse

Pagina 29

R2-SERIES (Feb. 2009)R2-35R2-SERIESDATA U45. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS63HS1O/STH4CJ2SV1aCP1CJ121S4aST3ST163LSCV8aCV6aTH7TH3SV4a

Pagina 30

R2-36R2-SERIES (Feb. 2009)R2-SERIESDATA U46. SOUND PRESSURE LEVELSMeasurement conditionPURY-P72THMU/YHMUMeasurement location3-1/4' [1m]Ref.:PURY_

Pagina 31 - 3. CENTER OF GRAVITY

R2-SERIES (Feb. 2009)R2-37R2-SERIESDATA U4Measurement conditionPURY-P144TSHMU/YSHMUMeasurement locationRef.:PURY_THMU_NCC_USDB_R33-1/4' [1m]3-1/4

Pagina 32 - 4. ELECTRICAL WIRING DIAGRAMS

R2-38R2-SERIES (Feb. 2009)R2-SERIESDATA U46. SOUND PRESSURE LEVELSMeasurement conditionPURY-P192,216,240TSHMU/YSHMUMeasurement locationRef.:PURY_THMU_

Pagina 33 - PURY-P96,120THMU-A(-BS)

R2-SERIES (Feb. 2009)R2-39R2-SERIESDATA U47. CAPACITY TABLES7-1. Correction by TemperatureCITY MULTI could have varied capacity at different design te

Pagina 34

R2-4R2-SERIES (Feb. 2009)R2-SERIESDATA U4R2-SERIES (208 / 230V)Model PURY-P144TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capa

Pagina 35

R2-40R2-SERIES (Feb. 2009)R2-SERIESDATA U47. CAPACITY TABLESRatio of cooling capacity and power input Outdoor temperatureRatio of heating capacity and

Pagina 36 - 6. SOUND PRESSURE LEVELS

R2-SERIES (Feb. 2009)R2-41R2-SERIESDATA U4Ratio of cooling capacity and power input Outdoor temperatureRatio of heating capacity and power input Outdo

Pagina 37

R2-42R2-SERIES (Feb. 2009)R2-SERIESDATA U47. CAPACITY TABLESCITY MULTI systems have different capacities and inputs when different combinations of ind

Pagina 38

R2-SERIES (Feb. 2009)R2-43R2-SERIESDATA U4Capacity(kW)Input(kW)Total capacity of indoor units30.040.050.060.070.00.010.00 200100 300 400Total capacity

Pagina 39 - 7. CAPACITY TABLES

R2-44R2-SERIES (Feb. 2009)R2-SERIESDATA U4Capacity(BTU/h)Input(kW)Total capacity of indoor units40,00060,00080,000100,000120,0000.05.010.0050 100 150

Pagina 40

R2-SERIES (Feb. 2009)R2-45R2-SERIESDATA U4Capacity(BTU/h)Input(kW)Total capacity of indoor units50,000100,000150,000200,000250,0000.010.020.00 200100

Pagina 41

R2-46R2-SERIES (Feb. 2009)R2-SERIESDATA U47. CAPACITY TABLESCITY MULTI systems can have extended piping lengths if certain limitations are followed, b

Pagina 42

R2-SERIES (Feb. 2009)R2-47R2-SERIESDATA U47-3-2. Heating Capacity Correction7. CAPACITY TABLES0.80500 100 150 200 250 300 350 400 450 500 550 600Heati

Pagina 43

R2-48R2-SERIES (Feb. 2009)R2-SERIESDATA U47. CAPACITY TABLESCorrection Factor Table when Frost and Defrost OccursWBWB7-4. Correction at Frost and Defr

Pagina 44

R2-SERIES (Feb. 2009)R2-49R2-SERIESDATA U41/2"5/8"7/8"7/8"1-1/8"3/4"5/8"3/4"3/4"1"1"3/4"1&

Pagina 45

R2-SERIES (Feb. 2009)R2-5R2-SERIESDATA U4Model PURY-P168TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity (Nominal) *1 BTU

Pagina 46

R2-50R2-SERIES (Feb. 2009)R2-SERIESDATA U48. OPTIONAL PARTSRef: CMY_R100VBK_EXD_EUDB_SI<Deformed pipe(Accessory)><Low-pressure pipe twinning

Pagina 47

R2-SERIES (Feb. 2009)R2-51R2-SERIESDATA U48. OPTIONAL PARTS8-3. Joint Adapter Kit CMY-R160J for BC ControllerJoint Adapter Kit CMY-R160J for BC Contro

Pagina 49 - 8. OPTIONAL PARTS

S-SERIES (Feb. 2009)S-1S-SERIESDATA U4 1. SPECIFICATIONS ...

Pagina 50

S-2S-SERIES (Feb. 2009)S-SERIESDATA U4Model PUMY-P36NHMU(-BS) PUMY-P48NHMU(-BS)Power source 1-phase 208 / 230 V 60HzCooling capacity (Nominal) *1BTU /

Pagina 51

S-SERIES (Feb. 2009)S-3S-SERIESDATA U42. EXTERNAL DIMENSIONSPUMY-P36,48NHMU(-BS)Ref. : PUMY_NHMU_EXD_USDB_P36-48Unit : mm(in)Min.500mm<19-11/16>

Pagina 52

S-4S-SERIES (Feb. 2009)S-SERIESDATA U43. CENTER OF GRAVITYYGGZXPUMY-P36,48NHMURef. : PUMY_ NHMU_COG_USDB_P36-48ModelUnit : mm[in.]XYZ590(23-1/4) 185(7

Pagina 53 - S-SERIES

S-SERIES (Feb. 2009)S-5S-SERIESDATA U4PUMY-P36,48NHMU(-BS)Ref. : PUMY-NHMU_EWD_USDB_P36-48_212345678[Example]When the compressor and SV1 are turned du

Pagina 54

S-6S-SERIES (Feb. 2009)S-SERIESDATA U4PUMY-P36,48NHMU(-BS)Ref. : PUMY-NHMU_EWD_USDB_P36-48_1CNDC(PIN)CNAF(WHT)CN2(WHT)CN3(WHT)CN4(WHT)CN5(RED)CNAC2(RE

Pagina 55 - ( )

S-SERIES (Feb. 2009)S-7S-SERIESDATA U45. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORSRefrigerant Gas pipe<5/8 inch>Refrigerant Liquid pipe&l

Pagina 56

R2-6R2-SERIES (Feb. 2009)R2-SERIESDATA U4R2-SERIES (208 / 230V)Model PURY-P192TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capa

Pagina 57

S-8S-SERIES (Feb. 2009)S-SERIESDATA U46. SOUND PRESSURE LEVELS3-1/4ft. (1m) 4-7/8ft. (1.5m)Measurement location UNITGROUNDMeasurement conditionPUMY-P

Pagina 58

S-SERIES (Feb. 2009)S-9S-SERIESDATA U4CITY MULTI systems could have various capacities at different design temperatures. Using the nominal cooling/hea

Pagina 59 - PUMY-P36,P48-NHMU(-BS)

S-10S-SERIES (Feb. 2009)S-SERIESDATA U47. CAPACITY TABLES7-2. Correction by Total IndoorCITY MULTI systems have different capacities and inputs when d

Pagina 60

S-SERIES (Feb. 2009)S-11S-SERIESDATA U4Total capacityof Indoor units*Cooling Heating Cooling Heating Cooling Heating Cooling Heating24 24,000 26,900 2

Pagina 61

S-12S-SERIES (Feb. 2009)S-SERIESDATA U4CITY MULTI systems can have extended piping lengths if certain limitations are followed, but cooling/heating ca

Pagina 62

S-SERIES (Feb. 2009)S-13S-SERIESDATA U4Due to frost on the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the out

Pagina 63

S-14S-SERIES (Feb. 2009)S-SERIESDATA U48. OPTIONAL PARTS1. SpecificationFor gas pipe:For liquid pipe: Reducer (Accessory):CMY-Y62-G2. External drawing

Pagina 64

S-SERIES (Feb. 2009)S-15S-SERIESDATA U48. OPTIONAL PARTS1. SpecificationFor gas pipe:For liquid pipe: Reducer (Accessory):CMY-Y64-G2. External drawing

Pagina 66

R2-SERIES (Feb. 2009)R2-7R2-SERIESDATA U4Model PURY-P216TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capacity (Nominal) *1 BTU

Pagina 67

R2-8R2-SERIES (Feb. 2009)R2-SERIESDATA U4R2-SERIES (208 / 230V)Model PURY-P240TSHMU-A(-BS)Power source 3-phase 3-wire 208 / 230V 10% 60HzCooling capa

Pagina 68

R2-SERIES (Feb. 2009)R2-9R2-SERIESDATA U4 Model PURY-P72YHMU-A(-BS) PURY-P96YHMU-A(-BS)Power source 3-phase 3-wire 460V 10% 60Hz 3-phase 3-wire 460V