SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 7
5. OUTLINES AND DIMENSIONS ························ 8
6. WIRING DIAGRAM ············································ 9
7. REFRIGERANT SYSTEM DIAGRAM ············· 10
8. PERFORMANCE CURVES ····························· 12
9. ACTUATOR CONTROL ··································· 21
10. SERVICE FUNCTIONS ···································· 22
11. TROUBLESHOOTING ····································· 22
12. DISASSEMBLY INSTRUCTIONS ···················· 39
Models
SPLIT-TYPE AIR CONDITIONERS
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
HFC
utilized
R410A
No. OBH635
OUTDOOR UNIT
PARTS CATALOG (OBB635)
MUZ-GF60VE
-
E1
MUZ-GF71VE
-
E1
Indoor unit service manual
MSZ-GF•VE Series (OBH634)
Vista de pagina 0
1 2 3 4 5 6 ... 41 42

Indice de contenidos

Pagina 1 - MUZ-GF71VE

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ··································· 32. PART NAMES AND FUNCTIONS ····················· 43. SPECIFICATION ··

Pagina 2

10REFRIGERANT SYSTEM DIAGRAM7MUZ-GF60VEUnit: mmOutdoorheatexchangerFlared connectionDefrostthermistorRT61DischargetemperaturethermistorRT62Flared conn

Pagina 3 - TECHNICAL CHANGES

11Max. Length AMax. HeightdifferenceBIndoorunitOutdoor unitMAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCERefrigerant piping: m P

Pagina 4 - PART NAMES AND FUNCTIONS

12The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi-tions vary according t

Pagina 5 - SPECIFICATION

13NOTE: The above broken lines are for the heating operation without any frost and defrost operation.0.80.91.01.11.21.3-10-5 0 5 1015202530354045Outdo

Pagina 6

148-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSORCorrection of Cooling capacityCapacity correction factorsCorrection of Cool

Pagina 7 - NOISE CRITERIA CURVES

1515 205025603070354.05.06.07.08.09.015 205025603070354.05.06.07.08.09.0MUZ-GF60VEMUZ-GF71VEAmbient temperature(°C) Ambient humidity(%)Ambient tempera

Pagina 8 - OUTLINES AND DIMENSIONS

16PERFORMANCE DATA COOL operation at Rated frequencyMUZ-GF60VECAPACITY: 6.1 kW SHF: 0.79 INPUT: 1790 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)21

Pagina 9 - WIRING DIAGRAM

17PERFORMANCE DATA COOL operation at Rated frequencyMUZ-GF60VECAPACITY: 6.1 kW SHF: 0.79 INPUT: 1790 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)35

Pagina 10 - REFRIGERANT SYSTEM DIAGRAM

18PERFORMANCE DATA COOL operation at Rated frequencyMUZ-GF71VECAPACITY: 7.1 kW SHF: 0.78 INPUT: 2130 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)21

Pagina 11

19PERFORMANCE DATA COOL operation at Rated frequencyMUZ-GF71VECAPACITY: 7.1 kW SHF: 0.78 INPUT: 2130 WINDOORDB (°C)INDOORWB (°C)OUTDOOR DB (°C)35

Pagina 12 - PERFORMANCE CURVES8

2Use the specifi ed refrigerant onlyNever use any refrigerant other than that specified.Doing so may cause a burst, an explosion, or fire when the unit

Pagina 13 - Total input (Cooling :

20PERFORMANCE DATA HEAT operation at Rated frequencyMUZ-GF60VECAPACITY: 6.8 kW INPUT: 1810 WINDOORDB (°C)OUTDOOR WB (°C)-10 -5 0 5 10 15 20Q INPUT Q

Pagina 14

21MUZ-GF60VE MUZ-GF71VE9-2. R.V. COIL CONTROLHeating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFFDry . . . . .

Pagina 15 - HEAT operation

2210-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> To change the defrost finish temperature, cut/solder the JS wire of

Pagina 16

23Outline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though LED indication listed on the tro

Pagina 17

24 2. Flow chart of the detailed outdoor unit failure mode recall function 2.Blinking pattern when outdoor unit is abnormal:ONOFFNo beepBeepsRepe

Pagina 18

253. Outdoor unit failure mode tableThe upper lamp of OPERATION INDICATOR lamp(Indoor unit) Abnormal point (Failure mode / protection) LED indication(

Pagina 19

11-3. TROUBLESHOOTING CHECK TABLENo. Symptom LED indication Abnormal point/ Condition Condition Remedy1Outdoor unit does not op-erate. 1-time fl ash e

Pagina 20

No. Symptom LED indication Abnormal point/ Condition Condition Remedy19Outdoor unit operates. 8-time fl ash 2.5 seconds OFFZero cross detecting circui

Pagina 21 - ACTUATOR CONTROL

2811-5. TROUBLESHOOTING FLOWAre the voltages balanced?Disconnect the connector between compressor and the IGBT module (IC700).Replace the inverter P.C

Pagina 22 - SERVICE FUNCTIONS

29 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time●Disconnect the connector between the comp

Pagina 23 - Outline of the function

3MUZ-GF60VE -E1MUZ-GF71VE -E1 1. New modelTECHNICAL CHANGES1OBH635

Pagina 24 - Operational procedure

30 G Check of outdoor thermistors H Check of R.V. coilReplace the thermistor except RT64.When RT64 is abnormal, replace the inverter P.C. board.Repl

Pagina 25

31 I Check of outdoor fan motorIs the resistance between each ter-minal of outdoor fan motor normal? (Refer to 11-4.)Disconnect CN932 from the invert

Pagina 26

32 J Check of power supplyIs there voltage 230 VAC between the indoor terminal block S1 and S2?NoYesReplace the indoor electronic control P.C. board.

Pagina 27 - MUZ-GF60VE MUZ-GF71VE

33Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor

Pagina 28 - C Check of compressor

34Check the outdoor fan motor. (Refer to 11-5. .)Is the fuse (F901) blown on the in-verter P.C. board?Check the connection of the connectors (CN931, C

Pagina 29

35 M How to check miswiring and serial signal errorTurn the power supply OFF.Is there rated voltage in the power supply?YesNoCheck for incorrect indo

Pagina 30 - H Check of R.V. coil

36 N Electromagnetic noise enters into TV sets or radiosYesIs the unit earthed?NoEarth the unit.YesIs the distance between the antennas and the indoo

Pagina 31

371. Inverter P.C. board11-6. TEST POINT DIAGRAM AND VOLTAGEMUZ-GF60VE MUZ-GF71VE-20 -10 0 10 20 30 400102030405060708090100Temperature( )Defrost t

Pagina 32 - J Check of power supply

382. Relay P.C. boardMUZ-GF60VE MUZ-GF71VETo inverter P.C. board CN681 (CN680)CN60L68B(-)L68A(+)10 VDCOBH635

Pagina 33

3912-1. MUZ-GF60VE MUZ-GF71VE NOTE: Turn OFF power supply before disassembly.OPERATING PROCEDUREPHOTOS1. Removing the cabinet(1) Remove the scr

Pagina 34

4PART NAMES AND FUNCTIONS2ACCESSORIES Model MUZ-GF60/71VEDrain socket 1MUZ-GF60VE MUZ-GF71VEPipingAir outletDrain outletAir inlet(back and side)Drain

Pagina 35

OPERATING PROCEDUREPHOTOS2. Removing the inverter assembly, inverter P.C. board and relay P.C. board(1) Remove the cabinet and panels. (Refer to 1.)(2

Pagina 36

OPERATING PROCEDURE PHOTOS4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera-ture thermistor and amb

Pagina 37

© Copyright 2013 MITSUBISHI ELECTRIC CORPORATIONDistributed in Mar. 2013. No. OBH635Made in JapanNew publication, effective Mar. 2013Specifications a

Pagina 38

5SPECIFICATION3Outdoor model MUZ-GF60VE MUZ-GF71VEPower supply Single phase, 230 V, 50 HzCapacity Rated frequency (Min. - Max.)CoolingkW6.1 (1.4 - 7

Pagina 39 - DISASSEMBLY INSTRUCTIONS

6Specifi cations and rated conditions of main electric partsModel Item MUZ-GF60VE MUZ-GF71VESmoothing capacitor(CB1, CB2, CB3) 560 μF 450 VFuse (F601,

Pagina 40 - OPERATING PROCEDURE

7NOISE CRITERIA CURVES4MUZ-GF60VE MUZ-GF71VETest conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temper

Pagina 41 - OPERATING PROCEDURE PHOTOS

8Unit: mmOUTLINES AND DIMENSIONS5MUZ-GF60VE MUZ-GF71VE417.54042Drain hole17550033050Air inAir out2-holes 10 2136084010981880452Service panel99.5164

Pagina 42 - Made in Japan

9WIRING DIAGRAM6MUZ-GF60VE MUZ-GF71VEOBH635