Mitsubishi Electric MSZ-HJ50VA Manual de servicio

Busca en linea o descarga Manual de servicio para Acondicionadores de aire del sistema de división Mitsubishi Electric MSZ-HJ50VA. Mitsubishi Electric MSZ-HJ50VA Service manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 32
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 5
4. NOISE CRITERIA CURVES ······························ 6
5. OUTLINES AND DIMENSIONS ························ 7
6. WIRING DIAGRAM ············································ 7
7. REFRIGERANT SYSTEM DIAGRAM ··············· 8
8. SERVICE FUNCTIONS ····································· 9
9. MICROPROCESSOR CONTROL ····················11
10. TROUBLESHOOTING ····································· 15
11. DISASSEMBLY INSTRUCTIONS ···················· 27
MSZ-HJ25VA
-
E1
MSZ-HJ35VA
-
E1
MSZ-HJ50VA
-
E1
Outdoor unit service manual
MUZ-HJ·VA Series (OBH648)
SERVICE MANUAL
No. OBH647
REVISED EDITION-A
INDOOR UNIT
PARTS CATALOG (OBB647)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
SPLIT-TYPE AIR CONDITIONERS
Models
Revision A:
• MSZ-HJ50VA-
E1
has been added.
Please void OBH647.
Vista de pagina 0
1 2 3 4 5 6 ... 31 32

Indice de contenidos

Pagina 1 - SERVICE MANUAL

CONTENTS1. TECHNICAL CHANGES ··································· 32. PART NAMES AND FUNCTIONS ····················· 43. SPECIFICATION ················

Pagina 2 - Revision A:

10NOTE:• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote controller.• If main powe

Pagina 3 - TECHNICAL CHANGES

11NOTE : Last setting will be stored after the unit is turned OFF with the remote controller. Indoor unit receives the signal of the remote controller

Pagina 4 - PART NAMES AND FUNCTIONS

129-2. DRY ( ) OPERATION(1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.(2) Select DRY

Pagina 5 - SPECIFICATION

13(5) STOP (operation OFF) and ON TIMER standbyIn the following cases, the horizontal vane returns to the closed position.(a) When OPERATE/STOP (ON/OF

Pagina 6 - NOISE CRITERIA CURVES

14EMERGENCY OPERATION switch9-6. EMERGENCY/TEST OPERATIONIn case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the r

Pagina 7 - WIRING DIAGRAM

153. Troubleshooting procedure1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality. To make

Pagina 8 - REFRIGERANT SYSTEM DIAGRAM

1610-2. FAILURE MODE RECALL FUNCTIONOutline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even thoug

Pagina 9 - SERVICE FUNCTIONS

172. Indoor unit failure mode tableUpper lamp of OP-ERATION INDICA-TOR lampAbnormal point (Failure mode) Condition Remedy Not lighted Normal — —1-ti

Pagina 10 - Indoor electronic

1810-3. INSTRUCTION OF TROUBLESHOOTINGIndoor unit oper-ates.Outdoor unit does not operate.If blinking of OPERATION INDI-CATOR lamp cannot be checked,

Pagina 11 - MICROPROCESSOR CONTROL

1910-4. TROUBLESHOOTING CHECK TABLEBefore taking measures, make sure that the symptom reappears for accurate troubleshooting.When the indoor unit has

Pagina 12 - 9-4. AUTO VANE OPERATION

2<Preparation before the repair service> Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stoppi

Pagina 13 - Horizontal

2010-5. TROUBLE CRITERION OF MAIN PARTSMSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VAPart name Check method and criterion Figure Room temperaturethermistor (RT11

Pagina 14 - 9-6. EMERGENCY/TEST OPERATION

2110-6. TROUBLESHOOTING FLOW A Check of indoor fan motor The indoor fan motor error has occurred, and the indoor fan does not operate.Turn OFF the po

Pagina 15 - TROUBLESHOOTING

22 B Check of remote controller and indoor electronic control P.C. board Check if the remote controller is exclusive for this air conditioner.Does th

Pagina 16

23 C Check of indoor P.C. board and indoor fan motorTurn OFF the power supply.Remove indoor fan motor connector CN211 from indoor power P.C. board an

Pagina 17

24 D How to check miswiring and serial signal errorAReinstall ei-ther the unit or the light away from each other.Attach a fi lter on remote control r

Pagina 18

25 E Electromagnetic noise enters into TV sets or radiosYesIs the unit earthed?NoEarth the unit.YesIs the distance between the antennas and the indoo

Pagina 19 - OPERATION INDICATOR

26Room temperature thermistor (RT11)Indoor coil thermistor (RT12, RT13)Temperature (°C)Resistance (kΩ)Fuse (F11)T3.15AL250VVaristor (NR11)Connector to

Pagina 20 - (Part temperature 10 ~ 30°C)

OPERATING PROCEDURE PHOTOS1. Removing the panel(1) Remove the screw caps on the panel and remove the screws of the panel.(2) Pull the panel slightly t

Pagina 21 - A Check of indoor fan motor

OPERATING PROCEDURE PHOTOS2. Removing the indoor power P.C. board and the electrical box(1) Remove the panel. (Refer to 1.) Remove the right corner bo

Pagina 22

OPERATING PROCEDURE PHOTOS3. Removing the indoor electronic control P.C. board(1) Remove the panel. (Refer to 1.) Remove the right corner box.(2) Disc

Pagina 23

31TECHNICAL CHANGESMSZ-HJ25VA -E1MSZ-HJ35VA -E1MSZ-HJ50VA -E1 1. New modelOBH647A

Pagina 24 - Figure 1

OPERATING PROCEDURE PHOTOS5. Removing the indoor fan motor, the indoor coil thermistor and the line flow fan(1) Remove the panel. (Refer to 1.) Remove

Pagina 25

31Fixing the indoor coil thermisor There are 2 forms of parts for fixing the indoor coil thermistor.NOTE: Take care to avoid loss and accidental fall

Pagina 26 - 1. Indoor power P.C. board

© Copyright 2012 MITSUBISHI ELECTRIC CORPORATIONDistributed in Mar. 2013. No. OBH647 REVISED EDITION-ADistributed in Dec. 2012. No. OBH647Made in Ja

Pagina 27 - DISASSEMBLY INSTRUCTIONS

4Operation indicator lampRemote control receiving sectionEmergencyoperation switch Horizontal vaneAir inletAir filterFront panelAir outletHeat exchange

Pagina 28 - OPERATING PROCEDURE PHOTOS

53SPECIFICATIONIndoor model MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VAPower supply Single phase 230 V, 50 HzBreaker Capacity A1012Electrical dataPower input 1

Pagina 29

690807060504030201063 125 250 500 1000 2000 4000 8000NC-60NC-50NC-40NC-30NC-20NC-70OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BARBAND CENTER

Pagina 30

7MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VAUnit : mmMSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA5OUTLINES AND DIMENSIONS6WIRING DIAGRAM23256941799785 729012063049578042

Pagina 31 - Holder shapeClip shape

8MSZ-HJ25VA MSZ-HJ35VAIndoorheatexchangerFlared connectionRoom temperaturethermistorRT11Flared connectionRefrigerant flow in coolingRefrigerant flow

Pagina 32

98-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATIONA maximum of 4 indoor units with wireless remote controllers can be used in a room.In this case,

Comentarios a estos manuales

Sin comentarios