EnglishDeutschNederlandsEspañolItalianoÏÏËÓÈοPortuguêsDanskSvenskaEnglishEspañolINSTALLATION MANUALFor safe and correct use, read this manual and the
107. Test run7.2. Test run7.2.1. Using SW4 in outdoor unit1) PUH Type, PUZ TypeSW4-1 ONCooling operationSW4-2 OFFSW4-1 ONHeating operationSW4-2 ON2) P
113-15/16 (7-7/8)7-7/8 (11-13/16)3-15/16 (7-7/8)3-15/16 (5-29/32)7-7/8 (11-13/16)39-3/8Max. 19-11/1619-11/16 (39-3/8)3-15/16 (5-29/32)19-11/16 (39-3/8
3400 Lawrenceville Suwanee Road ● Suwanee, Georgia 30024 Toll Free: 800-433-4822 ● Toll Free Fax: 800-889-9904 www.mrslim.com Specifications ar
21.2. Before installation (relocation) Caution:• Be extremely careful when transporting the units. Two or more persons areneeded to handle the unit, a
32. Installation location1. Safety precautions1.3. Before electric work Caution:• Be sure to install circuit breakers. If not installed, electric shoc
4B2. Installation locationAB2.4. Ventilation and service space2.4.1. Windy location installationWhen installing the outdoor unit on a rooftop or other
54. Installing the refrigerant pipingA Flare cutting dimensionsB Flare nut tightening torque90° ±0.5°øAR1/64 to R1/32A45°±2°BCDFig. 4-14.1. Precaution
64.4. Refrigerant pipe airtight testing method(1) Connect the testing tools.• Make sure the stop valves A B are closed and do not open them.• Add pres
74. Installing the refrigerant piping4.7. For twin/triple combinationRefrigerant piping limitation of length, height difference are shown in the figur
8 A12, A18CORD COVERCONDUIT COVERCABLE STRAPTERMINAL BEDSERVICE PANELCONDUIT PLATE : accessory GRL2L1 S1 S2 S3 A24–42 BG79U896H01_en 05.12.20, 11:03
9Outdoor unit modelOutdoor unit power supplyBreaker sizeMinimum circuit ampacityMaximum rating of overcurrent protective deviceOutdoor unit power supp