TECHNICAL & SERVICE MANUALMultiple Split type Air-Conditioners <Indoor unit>ModelsCeiling Concealed (Fresh Air Intake type)Series PEFYPEFY-P
9PEFY-P200· 250VMH-E-FUnit : mm213Note1.Use M10 screw for the lifting bolt (field supply). 2.Keep the service space for the maintenance from the bo
105WIRING DIAGRAMPEFY-P80·140VMH-E-Fattachment to alter the external static pressure on the fanPE❈NOTE 1,2❈NOTE 1❈NOTE 1❈A connector is attached to
PEFY-P200· 250VMH-E-F11BREAKER*NOTE 1*NOTE 1,2*A connector is attached to the drain lift up mechanism, which is an optional part.*NOTE 1 Switch (for
12REFRIGERANT SYSTEM DIAGRAM6Strainer (#100 mesh)Strainer (#100 mesh)Heat exchangerOutdoor air temperature thermistor TH24 Gas pipe thermistor TH23Liq
137TROUBLE SHOOTING7-1. How to check the partsOutdoor air temperature thermistor (TH24)Liquid pipe thermistor(TH22)Gas pipe thermistor(TH23)TransFan
147-2. Setting of address switchMake sure that power source is turning off.ONOFF12345678910SW1Indoor unit control board< At delivery (All models)&g
157-3. Setting of Dip-switch (at delivery)7-4. Attention for test run123SW45123SW45SWA1SWCStandardIndicateModels Dip-SWONOFF220V240VSW5PEFY-P140VMH-E-
168DISASSEMBLY PROCEDUREOPERATING PROCEDURE PHOTOSModels 80·1401.Removing the control box cover (1) Remove the fixing screws (two) of the control box
17OPERATING PROCEDURE PHOTOSBe careful on removing heavy parts.Fig.4Fig.5Models 200· 2501.Removing the control box cover (1) Remove the fixing screws
18Fig.1Fig.2Fig.3Fig.48-2. FAN and FAN MOTOROPERATING PROCEDURE PHOTOSModels 80 •140 1.Removing the control box.(1) Remove the control box cover and
1SAFETY PRECAUTIONSand install the unit at the specified place.- Improper installation may cause the unit to topple and result ininjury.• Always use a
19(A)(D)Arrow 1Motor (A)OPERATING PROCEDURE PHOTOS(4) Slide the motor (A) with motor base (D) in direction of allow1. (Fig. 5)Model 140 *Motor maint
20Fig.7Fig.8Fig.9Fig.10OPERATING PROCEDURE PHOTOSModels 200· 2501.Removing the control box.(1) Remove the control box cover1 with procedure 8-1.(2) R
21OPERATING PROCEDURE PHOTOS(3) After removing the fixing screws (H) (as shown models80, 140) of the front fan case (B) and remove the fan.Pull the
228-3.LEV,THERMISTOR (Liquid/Gas piping temperature detection)OPERATING PROCEDURE PHOTOSModels 80 •1401.Removing the LEV.(1) Remove the control box c
238-4. HEAT EXCHANGEROPERATING PROCEDURE PHOTOSModels 80 •1401.Removing the heat exchanger.(1) Remove the heat exchanger cover with procedure 8-3-1.(
24OPERATING PROCEDURE PHOTOS(4) Remove the maintenance cover.(fixing screws : two) (Fig. 4)(5) Remove the heat exchanger.(fixing screws : four) (Fig.
25Bottom plateDrainpanFixing screwsOPERATING PROCEDURE PHOTOSModels 200· 2501.Removing the heat exchanger.(1) Remove the refrigerant piping and drain
26OPERATING PROCEDURE PHOTOS(7) Remove the fixing screws (three) of the heat exchangercover, and remove the cover. Remove the fixing screws(four) of t
278-5. CONTROL BOX INSIDE LAYOUTModels 80·140Models 200·250X06 X05 X04CN42CN81FAN2FAN3CNPCNT CNDCN3TCN2MCN20CN60LEV1SW4SW3SW2CN60CN27CN52CN25CN51CN4
288-6. SENSOR POSITION●PEFY-P80VMH-E-F●PEFY-P250VMH-E-FLiquid sensorLiquid sensorGas sensorGas sensor●PEFY-P140VMH-E-FGas sensor●PEFY-P200VMH-E-FLiqui
22. Precautions for devices that use R410A or R407C refrigerantCaution:• Do not use the existing refrigerant piping.- The old refrigerant and refri
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANIssued in Sep. 2004 MEE04K286 New publication, effective Sep.
3PEFY-P80VMH-E-FPEFY-P140VMH-E-FPEFY-P200VMH-E-FPEFY-P250VMH-E-F9.0 / 8.516.0 / 15.122.4 / 21.228.0 / 26.5FEATURES1Indoor unitCeiling ConcealedSeries
4PART NAMES AND FUNCTIONS2● Indoor (Main) Unit● Remote controller[Operation buttons] [PAR-20MAA]● Once the controls are set, the same operation mode c
5[Display]ON/OFF CENTRALLY CONTROLLEDERROR CODECLOCKON OFF˚CCHECKCHECK MODEFILTERTEST RUNFUNCTION˚C1Hr.NOT AVAILABLESTAND BY DEFROSTTEMP.ABCDEFHIKLJMP
BTU/h❇ 1BTU/h❇ 1❇ 1❇ 13SPECIFICATION3-1. SpecificationPEFY-P80VMH-E-F PEFY-P140VMH-E-F PEFY-P200VMH-E-F PEFY-P250VMH-E-F9.0 16.0 22.4 28.08.530,70029,
7LEVC1MF1,23-2. Electrical parts specificationsModelPartsnameTranrsformer T (Primary) 50/60Hz 220-240V (Secondry) (23.5V 0.9A)TH22 Resistance 0˚C/15
84OUTLINES AND DIMENSIONSUnit : mmPEFY-P80·140VMH-E-F Terminal block(Transmission) Terminal block(Power source) 150~2007005050LAccess door625 Note 2Re