Mitsubishi Electric PUHY-500YMF-B Especificaciones

Busca en linea o descarga Especificaciones para Acondicionadores de aire del sistema de división Mitsubishi Electric PUHY-500YMF-B. Mitsubishi Electric PUHY-500YMF-B Specifications Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 178
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
AIR CONDITIONERS CITY MULTI
Models PUHY-200YMF-B, 250YMF-B
PUHY-P200YMF-B, P250YMF-B
PUY-200YMF-B, 250YMF-B
PURY-200YMF-B, 250YMF-B
PURY-P200YMF-B, P250YMF-B
CMB-P104, P105, P106, P108, P1010V-D
CMB-P104, P105, P106, P108, P1010, P1013, P1016V-E
Service Handbook
Service Handbook PUHY-200YMF-B, 250YMF-B
PUHY-P200YMF-B, P250YMF-B
PUY-200YMF-B, 250YMF-B
PURY-200YMF-B, 250YMF-B
PURY-P200YMF-B, P250YMF-B
CMB-P104, P105, P106, P108, P1010V-D
CMB-P104, P105, P106, P108, P1010, P1013, P1016V-E
HEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI TOKYO 100-0005 TELEX J24532 CABLE MELCO TOKYO
Issued in June 1999 MEE98K028
Printed in Japan
New publication effective June 1999
Specifications subject to change without notice.
Service Handbook PUHY, PUY, PURY-200·250YMF-B/PUHY, PURY-P200·P250YMF-B/CMB-P-V-D, CMB-P-V-E
Vista de pagina 0
1 2 3 4 5 6 ... 177 178

Indice de contenidos

Pagina 1 - Service Handbook

AIR CONDITIONERS CITY MULTIModels PUHY-200YMF-B, 250YMF-BPUHY-P200YMF-B, P250YMF-BPUY-200YMF-B, 250YMF-BPURY-200YMF-B, 250YMF-BPURY-P200YMF-B, P250YMF

Pagina 2

–8–22222 COMPONENT OF EQUIPMENT[1] Appearance of ComponentsOutdoor unit• PU(H)Y-200, 250YMF-BRearPUHY-YMF-B PUY-YMF-BPropeller fanFan motorHeat exchan

Pagina 3

–98–Judgment Methods and Likely Failure ModeCaution:The specifications of the outdoor unit (outdoor LEV) and outdoor units (indoor LEV) differ. For th

Pagina 4

–99–Outdoor LEV (SLEV) Coil Removal Procedure (configuration)As shown in the figure, the outdoor LEV is made in such a way that the coils and the body

Pagina 5 - [2] Piping Machining

–100–Check Valves Block (PURY-(P)200·250YMF-B)The refrigerant flow in the pipe 6, 7, 8 and 9 are depend on ON/OFF of the SV3, 4, 5 and 6.Please confir

Pagina 6

–101–Power transistorMeasure resistances between each terminal of transistor module with tester, and use the results for troubleshooting.Specified res

Pagina 7 - [4] Brazing

–102–Thyristor module (SCRM)<Judgment Method> Measure the resistance between each of the SCRM pins and judge if there is a failure or not bythe

Pagina 8 - [6] Vacuuming

–103–(5) Trouble and remedy of remote controllerSymptom Cause Checking method & countermeasure12Despite pressing ofremote controllerswitch, operat

Pagina 9 - [8] Dryer

–104–Symptom Cause3 “HO” display on re-mote controller doesnot disappear andswitch is ineffective.(Without using MELANS)1) Outdoor unit address is set

Pagina 10 - 2 COMPONENT OF EQUIPMENT

–105–Symptom Cause Checking method & countermeasure4 “88” appears on re-mote controller at theregistration andaccess remotecontrollera) Confirm th

Pagina 11 - • PUHY-P200·250YMF-B

–106–Transmission Power Circuit (30 V) Check ProcedureIf “” is not displayed by the remote control, investigate the points of the trouble by the follo

Pagina 12 - • PURY-P200·250YMF-B

–107–(6) Investigation of transmission wave shape/noiseControl is performed by exchanging signals between outdoor unit, indoor unit and remote control

Pagina 13 - Terminal Box

–9–• PUHY-P200·250YMF-BPropeller fanFan motorHeat exchanger (front)Heat exchanger (rear)Noise filterTerminal BoxCompressorDrierAccumulator Control Box

Pagina 14 - Controller Box

–108–3) Checking and measures to be taken(a) Measures against noiseCheck the items below when noise can be confirmed on wave shape or the error code i

Pagina 15 - MAIN board

–109–4) Treatment of Inverter and Compressor TroublesIf the compressor does not work when error codes 4210, 4240, 4310 or 4340 are detected, determine

Pagina 16

–110–5) Treatment of Fan Motor Related TroublesCondition Possible Cause Check Method and Treatment1 It won’t run for 20 minutesor longer when the AKva

Pagina 17 - INV board

–111–6) Troubleshooting at breaker trippingCheck items Measures to be taken 1 Check the breaker capacity. 2 Check the a short circuit or grounding in

Pagina 18 - FANCON board

–112–7) Individual Parts Failure Judgment Methods.Part Name Judgment MethodDiode Stack (DS) Refer to “Judging Diode Stack Failure.”Transistor Module (

Pagina 20 - 1PUHY-200YMF-B, 250YMF-B

–114–(8) Troubleshooting the major components of the BC controller1) Pressure sensorPressure sensor troubleshooting flowCheck on the LED monitor dis-p

Pagina 21 - 2PUY-200YMF-B, 250YMF-B

–115–Note 1 :• Symptoms of incorrect connection of BC controller pressure sensor to the boardNote 2 :• Check using LED monitor display switch (outdoor

Pagina 22 - ➂PUHY-P200YMF-B, P250YMF-B

–116–2) Temperature SensorThermistor troubleshooting flowStartDisconnect applicable thermistorconnector from the board.Measure temperature of applicab

Pagina 23 - ➃PURY-200YMF-B, 250YMF-B

–117–Note 1 :• Board connector CN10 corresponds to TH11 through TH14, while connectorCN11 corresponds to TH15 through TS15. Remove the applicable conn

Pagina 24 - ➄PURY-P200YMF-B, P250YMF-B

–10–• PURY-P200·250YMF-BPropeller fanSolenoid Valves(SV) BlockFan motorHeat exchanger(rear)AccumulatorCompressorTerminal BoxCheck Valves(CV) BlockDrie

Pagina 25 - [3] Equipment Composition

–118–3) LEV, Solenoid Valve Troubleshooting FlowNo coolingNo heatingCheck disconnection or loosenessof connectors.Is there a problem?Operate in coolin

Pagina 26

–119–1 LEVNote 1 :• Symptoms of incorrect connection to BC controller LEV boardImproper installation is the same for 1 and 2, so it is omitted here. *

Pagina 27 - ‘ m ‘ shnm

–120–665432154321251346BrownRedBlueOrangeYellowWhiteBrownRedBlueOrangeYellowWhiteToLEV10kΩ LED(Self-diagnostic monitor)Measured Data Signal OUTDOOR MA

Pagina 28

–121–2 Solenoid ValveChange thesolenoid valve.Change the controlboard.220-240V output?With the solenoid valve con-nector is disconnected from theboard

Pagina 29 - <SYMBOL EXPLANATION>

–122–1BASolenoid Valves (SVA, SVB, SVC, SVM)Coordination signals output from the board and solenoid valve operations.Note 1 : (SVA, SVB, SVC)SVA, SVB

Pagina 30

–123–[2] BC Controller Disassembly Procedure(1) Service PanelBe careful on removing heavy parts.Procedure Photos & Illustrations1. Remove the two

Pagina 31

–124–(2) Control BoxBe careful on removing heavy parts.Procedure Photos<CMB-P104, 105, 106V-D>1. Removing the single screw that secures the elec

Pagina 32

–125–PS3PS1(3) Thermistor (Liquid and gas piping temperature detection)Be careful when removing heavy parts.Procedure Photos1. Remove the service pane

Pagina 33

–126–(5) LEVBe careful on removing heavy parts.Procedure Photos1. Remove the service panel. See (1)-1.2.3.4.2. Replace the applicable LEV.Important!1

Pagina 34 - CMB-P1010V-E

–127–Check Code ListCheck Code Check Content0403 Serial transmission abnormality0900 Trial operation1102 Discharge temperature abnormality1111 Low pre

Pagina 35 - 8 CMB-P1013V-E

–11–Noise Filter BoxTerminal BoxNoise filterTerminal block TB3TransmissionTerminal block TB1Power sourceTerminal block TB7Transmission (Centralized co

Pagina 36 - 9 CMB-P1016V-E

–128–Check Code Check Content6606 Communications with transmission processor abnormality6607 No ACK abnormality6608 No response abnormality7100 Total

Pagina 37 - [5] Standard Operation Data

–129–Checking code Meaning, detecting method Cause Checking method & CountermeasureSerialtransmissionabnormality0403If serial transmission cannot

Pagina 38 - Pressure

–130–Checking code Meaning, detecting method Cause Checking method & CountermeasureDischargetemperatureabnormality(Outdoor unit)11021. When 140˚C

Pagina 39

–131–Checking code Meaning, detecting method Cause Checking method & CountermeasureLowpressuresaturationtempera-turesensorabnormal-ity (TH2)Liquid

Pagina 40

–132–Checking code Meaning, detecting method Cause Checking method & Countermeasure13011302Low pressureabnoramlityHigh pressureabnoramlity 1(Outdo

Pagina 41

–133–Checking code Meaning, detecting method Cause Checking method & Countermeasure130213681370LiquidsideIntermedi-ate sideHigh pressure abnoramli

Pagina 42

–134–Checking code Meaning, detecting method Cause Checking method & Countermeasure15001501Insufficient refrigerant abnormality1.When liquid level

Pagina 43

–135–Checking code Meaning, detecting method Cause Checking method & Countermeasure1505250025022503SuctionpressureabnormalityLeakage (water)abnorm

Pagina 44

–136–Checking code Meaning, detecting method Cause Checking method & Countermeasure41034115Reverse phaseabnormalityPower supplysync signalabnoraml

Pagina 45 - 1 PU(H)Y-200·250YMF-B

–137–Checking code Meaning, detecting method Cause Checking method & Countermeasure41164200Fan speedabnormality(motorabnoramlity)VDC·IDCsensor/cir

Pagina 46 - 2 PUHY-P200·250YMF-B

–12–Controller BoxFANCON boardChoke coil (L2)INV boardMAIN boardThyristor module (SCRM)Diode stack (DS)Transistor module (TRM)Capacitor (C2, C3)(Smoot

Pagina 47 - 3 PURY-200·250YMF-B

–138–Checking code Meaning, detecting method Cause Checking method & Countermeasure42104220Breaking ofovercurrentBus voltageabnormality1 If IDC

Pagina 48 - 4 PURY-P200·250YMF-B

–139–Checking code Meaning, detecting method Cause Checking method & Countermeasure42304240Radiator paneloverheatprotectionOvercurrentprotectionIf

Pagina 49 - Cooling capacity saving

–140–Checking code Meaning, detecting method Cause Checking method & Countermeasure4260510151025103510451055106510751085109511051125111Cooling fan

Pagina 50

–141–Checking code Meaning, detecting method Cause Checking method & Countermeasure5201520152035301Pressuresensorabnormality(outdoor unit)IDC sens

Pagina 51 - 3 TEST RUN

–142–Checking code Meaning, detecting method Cause Checking method & Countermeasure7130 Differentindoor modelconnectedabnormalityAn exclusive R22

Pagina 52 - Insulation pipe

–143–(2) Communication/systemCheckingcode66006602Multiple address errorTransmission from units with thesame address is detected.Note:The address/attri

Pagina 53

–144–Transmission processor hardwareerrorTransmission circuit bus-busy er-ror1 Collision of data transmission:Transmission can not be per-formed for 4

Pagina 54

–145–Checkingcode6606Meaning, detecting method Cause Checking method & Countermeasure1) Data is not properly transmitted dueto casual errouneous o

Pagina 55

–146–Checkingcode6607Meaning, detecting methodNo ACK error When no ACK signal is detected in 6 continuous times with 30 second interval bytransmissio

Pagina 56 - [2] Test Run Method

–147–Checkingcode6607(continued)Meaning, detecting methodSystemcompo-sitionGeneratingunit addressDisplay oftroubleDetectingmethodCause Checking method

Pagina 57 - (1) Switch function

–13–MAIN board• PUHYCN51Indication distance3-4 CompressorON/OFF3-5 TroubleLD1Service LEDCNRS3Serial transmission toINV boardCN3DCooling/Heating autoch

Pagina 58

–148–Checkingcode6607(continued)Meaning, detecting methodSystemcompo-sitionGeneratingunit addressDisplay oftroubleDetectingmethodCause Checking method

Pagina 59 - Group setting mode

–149–Checkingcode6607(continued)Meaning, detecting methodSystemcompo-sitionGeneratingunit addressDisplay oftroubleDetectingmethodCause Checking method

Pagina 60 - CENTRALLY CONTROLLED

–150–1) Total capacity of indoor units in thesame refrigerant system exceedsthe following:2) Erroneous setting of OC model se-lector switch (SW3-10).1

Pagina 61 - (Alternative

–151–Checkingcode71027105710771117130Meaning, detecting method Cause Checking method & CountermeasureConnected unit count overAddress setting erro

Pagina 62

–152–[4] LED Monitor Display(1) How to read LED for service monitorBy setting of DIP SW1-1 ~ 1-8, the unit operating condition can be observed with th

Pagina 63 - 5 CONTROL

–153–1 PU(H)Y-(P)200·250YMF-BE: E2 Contents stored in the E2PROM; M: Monitored by the IC through communications; E*: Stored in service memory.No SW1 I

Pagina 64

–154–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8212223242526272829303132333435363738394041424344454647484950511010100000011

Pagina 65

–155–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8525354555657585960616263646566676869707172737475767778798081820010110000101

Pagina 66

–156–When there is an error stop with No95-121,the data on error stops or the data immediately before the error postpone-ment stop, which is stored in

Pagina 67

–157–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8112113114115116117118119120121122123124125126127128129130131132133134135136

Pagina 68

–14–MAIN board• PURYCN51Indication distance3-4 CompressorON/OFF3-5 TroubleLD1Service LEDCNRS3Serial transmission toINV boardCNTR CNFC1CNVCC4Power sour

Pagina 69

–158–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8140141142143144145146147148149150151152153154155156157158159160161162163164

Pagina 70 - [2] Control of BC Controller

–159–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8166167168169170171172173174175176177178179180181182183184185186187188189190

Pagina 71 - [3] Operation Flow Chart

–160–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8200201202203204205206207208209210211212213214215216217218219220221222223224

Pagina 72 - Trouble observed

–161–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8229230231232233234235236237238239240241242243244245246247248249250251252253

Pagina 73 - (3) Indoor unit

–162–2 PURY-(P)200·250YMF-BE: E2 Contents stored in the E2PROM; M: Monitored by the IC through communications; E*: Stored in service memory.No SW1 Ite

Pagina 74 - Test run

–163–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8212223242526272829303132333435363738394041424344454647484950511010100000011

Pagina 75 - Defrosting operations

–164–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8525354555657585960616263646566676869707172737475767778798081820010110000101

Pagina 76 - Thermostat ON

–165–When there is an error stop with No95-121,the data on error stops or the data immediately before the error postpone-ment stop, which is stored in

Pagina 77

–166–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8112113114115116117118119120121122123124125126127128129130131132133134135136

Pagina 78

–167–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8140141142143144145146147148149150151152153154155156157158159160161162163164

Pagina 79 - 0/100=3460

–15–INV boardCN3 CN2-1 CN2-2 CN2-3Output to transistor module (INVERTER)CNL2Choke coilCNTHCN30VCNVCC1Power supply1-2 30V, 1-3 30V4-6 12V, 5-6 5VCNVCC2

Pagina 80

–168–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8166167168169170171172173174175176177178179180181182183184185186187188189190

Pagina 81

–169–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8200201202203204205206207208209210211212213214215216217218219220221222223224

Pagina 82

–170–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8229230231232233234235236237238239240241242243244245246247248249250251252253

Pagina 83 - 123456 7 8910

–171–8 PREPARATION, REPAIRS AND REFRIGERANT REFILLING WHEN REPAIRINGLEAKS[1] Location of leaks: Extension piping or indoor units (when cooling)<PU(

Pagina 84

–172–2-1 Check the Tc and TH7 data (PUHY-P200·250YMF-B).(The self-diagnosis switch (SW1) on the MAIIN board of the outdoor unit can be used to display

Pagina 85

–173–[4] Location of leaks: Outdoor unit (when heating)1 Remove any refrigerant from the entire system (outdoor unit, extension piping and indoor unit

Pagina 86 - Charge with small amounts of

–174–YESYESYESYESYESNONONONONOStartTest run all indoor units.Is the refrigerantcomposition of αOCcorrect? (Note 2)Finished checking thecomposition.Che

Pagina 87 - After adjusting the refriger

–175–1ON234567891012345678910ONNote 1 Wait until the units stabilize as described in the refrigerant amount adjustment procedure in “Chapter 6”.Note 2

Pagina 88

AIR CONDITIONERS CITY MULTIModels PUHY-200YMF-B, 250YMF-BPUHY-P200YMF-B, P250YMF-BPUY-200YMF-B, 250YMF-BPURY-200YMF-B, 250YMF-BPURY-P200YMF-B, P250YMF

Pagina 89

–16–FANCON boardCNFC2CNUCNWCNV

Pagina 90 - 1 Flow chart

–17–BC controllerCNTRCN02M-NETtransmissionCN03CN12Powersupply1 EARTH3 N5 LSW4 SW2 SW1

Pagina 92

–18–TH1TH6TH7TH8TH5TH3TH4TH2Indoor unitsCJ1O/S63HSCJ1CompHEX2HEX1SCCLEV1ST7BV2ST2BV1ST1CJ2CV1ST6SV1CP1SV2ST5CP2CP4ST3ST4SLEVSAMACP363H6-227840 6CH93 8

Pagina 93

–19–TH1TH6TH7TH8TH5TH3TH4TH2Indoor unitsCJ1O/S63HSCJ1CompHEX2HEX1SCCLEV1ST7BV2ST2BV1ST1CJ2CV1ST6SV1CP1SV2ST5CP2CP4ST3ST4SLEVSAMACP363H627840C93*Operat

Pagina 94 - Piping length (m)

–20–SCC11 085 7021.9(2.15)21.4(2.10)96 78111 8734 363.93 3.6719 -30.23 0.28-1 -342 -1CH82785 0LEV1HEX f HEX bTH6CS-CircuitSV2CP1CJ1CJ263HSSV1ST6CV1C

Pagina 95 - 7 TROUBLESHOOTING

–21–: Solenoid valve: Orifice: Capillary: Check valve : Thermal sensor: Strainer SP : Service port ACC : Accumulator➃PURY-200YMF-B, 250

Pagina 96 - 12345678

–22–TH1TH9DrierTH5TH3TH4TH2O/S63HS63LSSP1CompBV2BV1ST1SP2CS(Composition Sensing) circuitCV1ST6SV1CP1SV2ST5CP2CP3ST3ST4SLEVSAMACP363HTH10TH6HEXbCV7HEXf

Pagina 97

–23–ON/OFF –STAND BY DEFROSTERROR CODEOA UNIT ADDRESS NO.CENTRALLY CONTROLLEDCLOCKONOFF˚C1Hr.NOT AVAILABLE˚CCHECK MODEFILTERCHECKTEST RUNONOFFCLOCKFI

Pagina 98

–24–[4] Electrical Wiring Diagram1 PU(H)Y-(P)200·250YMF-BkQrlQlPkPPmkRod@@ioQqUkdc@|TQfjfjfjfjfjfjbmlevfQtjPtfQrbqltfPttjQvjPvjQvvfPujPufPujQufQutkPqk

Pagina 99

–25–sgTfkduPsgQqsgWfsgVvWQPneeFOnmFPPmDQmDPTmDPSmDPQmDPOmDWmDUmDSmDPUmDPmDPRm DPPmDXmDVmDTmDRmDQ mDTmDX mDPR m DPUmDUmDPO m DPSmDVmDPPmDP mDS mDWmDPQ

Pagina 100 - Caution:

–26–CNTR(3P)CN3(6P)CNL2(2P)CN30V(2P)MF1PurpleR7FB6BlackYellowOrangeL2Power circuit board(INV board)BOX BODYInverterController BoxRedBrownBlackPurpleBl

Pagina 101

–27–FLAG8 always lights atmicrocomputer powerON(Front)InverterControllerBoxTH4TH3ACCUMULATOR63LSSV1SV2TH10BlownOilseparator21S463H63HSTH1SLEVMCFLAG8Ch

Pagina 102

–1–11111 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANTCautionDo not use the existing refrigerant piping.• The old refrigerant and refrigerator oi

Pagina 103 - (See figure below)

–28–Symbol explanationPE321321EARTHTerminal block(for Transmission)TB02Terminal block(for power source)TB01Note:TB02 is terminal block for transmissio

Pagina 104 - AK2 AK2 AK2

–29–4 CMB-P105V-DCMB-P105V-ESymbol explanationPE321321EARTHTerminal block(for Transmission)TB02Terminal block(for power source)TB01Note:TB02 is termin

Pagina 105

–30–5 CMB-P106V-DCMB-P106V-EPE321321EARTHNote:TB02 is terminal block for transmission. Never connect power line to it.Transmission lineShield wire

Pagina 106 - In case no MELANS used

–31–6 CMB-P108V-DCMB-P108V-E* Only for CMB-P-V-EPE321321EARTH}Power source}}LNPower source /N 220V 240V 50HzNote:TB02 is terminal block for tran

Pagina 107

–32–7 CMB-P1010V-DCMB-P1010V-E* Only for CMB-P-V-EPE321321EARTH}Power source}}LNPower source /N 220V 240V 50HzNote:TB02 is terminal block for tr

Pagina 108

–33–8 CMB-P1013V-EPEEARTH123123TB02TB01NameSymbolTerminal block(for Transmission)Solenoid valveSolenoid valveSolenoid valveSolenoid valveTerminal bloc

Pagina 109 - HL = 2.0V or more

–34–9 CMB-P1016V-EPEEARTH123123TB02TB01NameSymbolTerminal block(for Transmission)Solenoid valveSolenoid valveSolenoid valveSolenoid valveTerminal bloc

Pagina 110

–35–[5] Standard Operation Data(1) Cooling operation1 PU(H)Y-200·250YMF-BOutdoor unitItemsPUHY-200YMF-BPUY-200YMF-BPUHY-250YMF-BPUY-250YMF-BIndoorOutd

Pagina 111

–36–PUHY-P200·250YMF-BOutdoor unitItemsPUHY-P200YMF-B PUHY-P250YMF-BIndoorOutdoorQuantityQuantity in operationModelMain pipeBranch pipeTotal piping le

Pagina 112

–37–380 415 380 415270/75 270/75 340/95 340/9515.1 13.8 19.0 17.4PURY-200·250YMF-BOutdoor unitItemsPURY-P200YMF-B PURY-P250YMF-BIndoorOutdoorQuantityQ

Pagina 113

–2–[1] Storage of Piping Material(1) Storage locationStore the pipes to be used indoors. (Warehouse at site or owner’s warehouse)Storing them outdoors

Pagina 114 - 2/T1 4/T2 6/T3

–38–PURY-P200·250YMF-BOutdoor unitItemsPURY-P200YMF-B PURY-P250YMF-BIndoorOutdoorQuantityQuantity in operationModelMain pipeBranch pipeTotal piping le

Pagina 115

–39–2 Heating operationPUHY-200·250YMF-BOutdoor unitItemsPUHY-200YMF-B PUHY-250YMF-BIndoorOutdoorQuantityQuantity in operationModelMain pipeBranch pip

Pagina 116 - Repair faulty connection

–40–PUHY-P200·250YMF-BOutdoor unitItemsPUHY-P200YMF-B PUHY-P250YMF-BIndoorOutdoorQuantityQuantity in operationModelMain pipeBranch pipeTotal piping le

Pagina 117

–41–PURY-200·250YMF-BOutdoor unitItemsPURY-200YMF-B PURY-250YMF-BIndoorOutdoorQuantityQuantity in operationModelMain pipeBranch pipeTotal piping lengt

Pagina 118 - 2) Temperature Sensor

–42–PURY-P200·250YMF-BOutdoor unitItemsPURY-P200YMF-B PURY-P250YMF-BIndoorOutdoorQuantityQuantity in operationModelMain pipeBranch pipeTotal piping le

Pagina 119

–43–[6] Function of Dip SW and Rotary SW(1) Outdoor unit1 PU(H)Y-200·250YMF-BSwitch FunctionFunction according to switch operation Switch set timingWh

Pagina 120

–44–2 PUHY-P200·250YMF-BSwitch FunctionFunction according to switch operation Switch set timingWhen off When on When off When onSWUSW1SW2SW3SW41~21~89

Pagina 121

–45–3 PURY-200·250YMF-BSwitch FunctionFunction according to switch operation Switch set timingWhen off When on When off When onSWUSW1SW2SW3SW41~21~89~

Pagina 122

–46–4 PURY-P200·250YMF-BSwitch FunctionFunction according to switch operation Switch set timingWhen off When on When off When onSWUSW1SW2SW3SW41~21~89

Pagina 123 - 2 Solenoid Valve

–47–(2) Indoor unitDIP SW1, 3Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to th

Pagina 124

–3–[2] Piping MachiningUse ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.Use only

Pagina 125

–48–Setting of DIP SW4 Setting of DIP SW5Model Circuit board usedSW41234––––ON ON ON OFFON OFF ON OFFOFF OFF OFF ONON OFF OFF ONOFF ON OFF ONOFF OFF O

Pagina 126 - Transformer

–49–33333 TEST RUN[1] Before Test Run(1) Check points before test run1 Neither refrigerant leak nor loose power source/ transmission lines should be

Pagina 127

–50–(3) Check points for test run when mounting options(4) Attention for mounting drain water lifting-up mechanismCheck pointLocal remote controller d

Pagina 128

–51–

Pagina 129

–52–(5) Check points for system structureex. PURY-200YMF-BCheck points from installation work to test run.TroubleNot operate.Not cool (at cooling).Not

Pagina 130

–53–ClassificationTransmissionlineSystem setBefore startingPortion Check item1Limitation of transmission line length followed? Forexample, 200m or le

Pagina 131 - (1) Mechanical

–54–[2] Test Run MethodOperation procedure1Turn on universal power supply at least 12 hours before getting started → Displaying “HO” on display panel

Pagina 132

–55–4 GROUPING REGISTRATION OF INDOOR UNITS WITH REMOTE CONTROLLER(1) Switch function• The switch operation to register with the remote controller is

Pagina 133

–56–(2) Attribute display of unit• At the group registration and the confirmation/deletion of registration/connection information, the type (attribute

Pagina 134

–57–(3) Group registration of indoor unit1) Registration method• Group registration of indoor unit ...

Pagina 135

–4–[3] Necessary Apparatus and Materials and Notes on Their HandlingThe following tools should be marked as dedicated tools for R407C.<<Comparis

Pagina 136

–58–2) Method of retrieval/confirmation• Retrieval/confirmation of group registration information on indoor unit... 2The address of the i

Pagina 137

–59–3) Method of deletion• Deletion of group registration information of indoor unit ... 4[Operation procedure]1 Wi

Pagina 138

–60–4) Deletion of information on address not existing• Deletion of information on address not existing ...

Pagina 139

–61–55555 CONTROL[1] Control of Outdoor Unit(1) Initial processing• When turning on power source, initial processing of microcomputer is given top pri

Pagina 140

–62–(4) Frequency control• Depending on capacity required, capacity control change and frequency change are performed to keep constantevaporation temp

Pagina 141

–63–3-2 Back up of frequency control by bypass valve (PUHY-P200·250YMF-B, PURY-(P)200·250YMF-B)During 20Hz operations, frequency is backed up by turni

Pagina 142

–64–2 PURY-(P)200·250YMF-B1) Starting of defrost operations• After integrated 50 minutes of compressor operations, defrosting operations start when –8

Pagina 143

–65–2) Control of refrigerant amountCooling(a)Prohibition of liquid level detection• Liquid level is detected in normal conditions except for the foll

Pagina 144

–66–2 PURY-(P)200·250YMF-BJudge refrigerant amount by detecting refrigerant liquid surface accumulator.1) Judgement of accumulator liquid levelReturn

Pagina 145 - (2) Communication/system

–67–• When turning on liquid level trouble ignore switch (SW2-6), error stop is not observed, and 3 minutes restartprevention by intermittent fault ch

Pagina 146

–5–[4] BrazingNo changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt,etc.) does no

Pagina 147

–68–ModeConnection2000Superheatcontrol *16060 *4DifferentialPressure control*22000200060100060[2] Control of BC Controller(1) Control of SVA, SVB and

Pagina 148

–69–YESNOYESNOYESYESNONONormal operationsTrouble observedStopStartBreakerturned onSet indoor ad-dress No. to remotecontrollerOperationcommandOperation

Pagina 149

–70–(2) BC controller (for PURY)Note : 1 Two error modes include indoor unit side trouble, BC controller trouble, and outdoor unit side trouble. In th

Pagina 150

–71–(3) Indoor unitYESNOYESNOYESNOYESNOYESNOYESNOYESNOYESNONormal operationsTrouble observedStopStartBreakerturned onOperation SWturned on1. Protectio

Pagina 151

–72–(4) Cooling operationYESNOYESYESNONO1. Inverter output 0Hz2. Indoor unit LEV, oil return LEV,Subcool coil bypass LEV fullyclosed3. Solenoid valve

Pagina 152 - (3) System error

–73–YESYESNOYESYESNONONO(5) Heating operationNormal operationsDefrosting operationsStopTest run1. Indoor unit fan very low speedoperations2. Inverter

Pagina 153

–74–YESNOYESYESNO(6) Dry operationNormal operationsThermostat ONStop1. Indoor unit fan stop2. Inverter output 0Hz3. Indoor unit LEV, oil return LEVcl

Pagina 154 - [4] LED Monitor Display

–75–Low pressure shell scroll typewith capacity control mechanismWinding resistance:Each phase 0.388Ω (20˚C)Setting 30kg/cm2G(2.94MPa) OFFR120=7.465kΩ

Pagina 155 - 1 PU(H)Y-(P)200·250YMF-B

–76–Name Application Specification Check method ObjectOutdoor unitSymbol(function)ThermistorSolenoidvalveLinearexpansionvalveLiquid leveldetectionheat

Pagina 156

–77–Name Application Specification Check method ObjectBC controllerSymbol(function)1273+tPressuresensorThermistorSolenoidvalveElectronicexpansionvalve

Pagina 157

–6–[5] Airtightness TestNo changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407Cleakage.Halide to

Pagina 158

–78–[5] Resistance of Temperature SensorThermistor for low temperatureThermistor Ro= 15kΩ ± 3% (TH3 ~ 9) Thermistor R120 = 7.465kΩ ± 2% (TH1, 10)Rt =

Pagina 159

–79–66666 REFRIGERANT AMOUNT ADJUSTMENTClarify relationship between the refrigerant amount and operating characteristics of CITY MULTI, and perform se

Pagina 160

–80–(2) Refrigerant Volume Adjustment Operation (PU(H)Y-(P)200·250YMF-B)1) Operating Characteristics Refrigerant VolumeCharacteristic items related to

Pagina 161

–81–b Cautions When Judging the Liquid LevelIf you are judging the liquid level, be sure to use it only after making sure the liquid level sensor func

Pagina 162

–82–3) Refrigerant Volume Adjustment Mode Operation2 ProcedureDepending on the operating conditions, it may be necessary either to charge with supplem

Pagina 163

–83–(3) Refrigerant adjustment in cooling season (When the high pressure is 14 kg/cm2G (1.37MPa) or greater)Caution :• Do not let the drained out refr

Pagina 164 - 2 PURY-(P)200·250YMF-B

–84–YESNOFlow Chart (When a high pressure cannot be maintained at 14 kg/cm2G (1.37MPa) in the intermediate period)Caution: (PUHY-P200·250YMF-B)Always

Pagina 165

–85–YESNO(4) Refrigerant adjustment in heating season* If adjustment of the refrigerant volume was done by heatingoperation, it is possible that accum

Pagina 166

–86–Note 1 If there are any units which are not operating, it will cause refrigerant to accumulate, so by all means operate allthe indoor units. Also,

Pagina 167

–87–(5) Refrigerant Amount Adjustment Mode Operations (PURY-(P)200·250YMF-B)1) ProcedureFollow the procedure shown below when needs to additionally re

Pagina 168

–7–[7] Charging of RefrigerantR407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.For a cylinder with a syphon a

Pagina 169

–88–YESNO2) Refrigerant adjustment in cooling season1 Flow chartCooling operations of all indoor unitsin test run mode.After compressor start, turn on

Pagina 170

–89–2 Additional replenishment amount and discharge amount of refrigerantTable-1 PURY-(P)250YMF-B (In case total capacity code is 40 or more and displ

Pagina 171

–90–3 Time required for recovering refrigerant from low pressure service port (minute)3.5~4.5 4.5~5.5 5.5 ~ 7.5(0.34~0.44) (0.44~0.54) (0.54~0.74)1 4.

Pagina 172

–91–3) Refrigerant adjustment in heating season1 Flow chart* Valid for only 2 hours in the test run mode. All work must therefore be carried out withi

Pagina 173

–92–Note :1. Be sure to operate all indoor units because refrigerant is accumulated in stopped unit. Change mode to test runmode for preventing stabil

Pagina 174 - 12345678910

–93–77777 TROUBLESHOOTING[1] Principal PartsPressure Sensor(1) Judging Failure1) Check for failure by comparing the sensing pressure according to the

Pagina 175

–94–* Connector connection specifications on the pressure sensor body side.The connector’s pin numbers on the pressure sensor body side differ from th

Pagina 176

–95–Solenoid Valve (SV1~6) (PURY-(P)200·250YMF-B)Check if the control board’s output signals and the operation of the solenoid valves match.Setting th

Pagina 177 - 2345678910

–96–(d) The refrigerant flow is as following figure. Hot gas (high pressured) flows in cooling mode and cool gas/liquid(low pressured) flows in heatin

Pagina 178

–97–Outdoor LEVThe valve opening angle changes in proportion to the number of pulses.(Connections between the outdoor unit’s MAIN board and SLEV, LEV1

Comentarios a estos manuales

Sin comentarios