TRANSISTORIZED INVERTERFR-F500INSTRUCTION MANUALOUTLINEPARAMETERSSPECIFICATIONSINSTALLATIONAND WIRINGPROTECTIVEFUNCTIONSChapter 6OPTIONSChapter 7Chapt

Pagina 2

1 CHAPTER 1OUTLINEThis chapter gives information on the basic "outline" of thisproduct.Always read the instructions in this chapter before u

Pagina 3 - 3. Injury Prevention

PARAMETERS87When 100 is set in Pr. 52, the monitored values during stop and during operation differ as indicated below:(The LED on the left of Hz fli

Pagina 4 - (4) Operation

PARAMETERS884.2.23 Monitoring reference (Pr. 55, Pr. 56)Pr. 55 "frequency monitoring reference"Pr. 56 "current monitoring reference&qu

Pagina 5 - (8) General instructions

PARAMETERS894.2.24 Automatic restart after instantaneous power failure(Pr. 57, Pr. 58, Pr. 162 to Pr. 165)Pr. 57 "restart coasting timePr. 58 &q

Pagina 6 - Contents

PARAMETERS90<Setting>Refer to the figures in the previous page and following table, and set the parameters:ParameterNumberSetting Description0F

Pagina 7

PARAMETERS914.2.25 Remote setting function selection (Pr. 59)Pr. 59 "remote setting function selection"If the operator panel is located awa

Pagina 8

PARAMETERS92Note: 1. The frequency can be varied by RH (acceleration) and RM (deceleration) between 0 and 120Hz.2. When the acceleration or decelerat

Pagina 9 - APPENDICES 195

PARAMETERS934.2.26 Intelligent mode selection (Pr. 60)Pr. 60 "intelligent mode selection"The inverter automatically sets appropriate parame

Pagina 10 - CHAPTER 1

PARAMETERS94Pr. 60 "intelligent mode selection"Related parameter4.2.27 Acceleration/deceleration reference current/lift mode startingfreque

Pagina 11 - 1.1 Pre-Operation Information

PARAMETERS954.2.28 Retry function (Pr. 65, Pr. 67 to Pr. 69)Pr. 65 "retry selection"Pr. 67 "number of retries at alarm occurrence"

Pagina 12 - 1.2 Basic Configuration

PARAMETERS96• Use Pr. 67 to set the number of retries at alarm occurrence.Pr. 67 Setting Number of Retries Alarm Signal Output0 Retry is not made.

Pagina 13 - 1.3 Structure

1.1 Pre-Operation InformationOUTLINE11 OUTLINE1.1 Pre-Operation Information1.1.1 Precautions for operationIncorrect handling might cause the inverter

Pagina 14 - Inverter

PARAMETERS974.2.29 Applied motor (Pr. 71)Pr. 71 "applied motor"Set the motor used.ParameterNumberFactorySettingSetting Range71 0 0, 1, 2<

Pagina 15

PARAMETERS984.2.30 PWM carrier frequency (Pr. 72, Pr. 240)Pr. 72 "PWM frequency selection"Pr. 240 "Soft-PWM setting"You can chang

Pagina 16

PARAMETERS99Pr. 22 "stall prevention operation level"Pr. 903 "frequency setting voltage gain"Pr. 905 "frequency setting curr

Pagina 17 - INSTALLATION AND WIRING

PARAMETERS1004.2.32 Input filter time constant (Pr. 74)Pr. 74 "filter time constant"You can set the input section's internal filter co

Pagina 18 - 2.1 Installation

PARAMETERS101How to make a restart after a stop made by the STOPRESET key from the PU duringexternal operation(1) Operation panel (FR-DU04)1) After c

Pagina 19

PARAMETERS102Pr. 79 "operation mode selection"Pr. 190 to Pr. 195 (multi-function outputs)Related parametersCAUTION Do not reset the inv

Pagina 20 - 2.2 Wiring

PARAMETERS1034.2.35 Parameter write inhibit selection (Pr. 77)Pr. 77 "parameter write disable selection"You can select between write-enable

Pagina 21

PARAMETERS1044.2.36 Reverse rotation prevention selection (Pr. 78)Pr. 78 "reverse rotation prevention selection"This function can prevent a

Pagina 22

PARAMETERS1054.2.37 Operation mode selection (Pr. 79)Pr. 79 "operation mode selection"Used to select the operation mode of the inverter.You

Pagina 23

PARAMETERS106(1) Switch-over modeYou can select between PU operation, external operation and computer link operation (when FR-A5NR optionis used).Ope

Pagina 24 - Notes on Grounding

1.2 Basic ConfigurationOUTLINE21.2 Basic Configuration1.2.1 Basic configurationThe following devices are required to operate the inverter. Proper peri

Pagina 25

PARAMETERS107<Function/operation changed by switching on-off the X12 (MRS) signal>Operating ConditionOperationmodeStatusX12 (MRS)SignalOperatio

Pagina 26

PARAMETERS1084.2.38 V/F control frequency (voltage) (Pr. 100 to Pr. 109)Pr. 100 "V/F1 (first frequency)"Pr. 101 "V/F1 (first frequency

Pagina 27

PARAMETERS109(2) Set the desired frequencies and voltages in Pr. 100 to Pr. 109.• The setting must satisfy the following relationship: F1≠F2≠F3≠F4≠F5

Pagina 28

PARAMETERS110# For the data codes of the parameters, refer to the data code list in the appendices.REMARKSFor computer link operation, set the value

Pagina 29

PARAMETERS111<Computer programming>(1) Communication protocolData communication between the computer and inverter is performed using the follow

Pagina 30 - NA and Japanese version

PARAMETERS112Note: 1. The inverter station numbers may be set between H00 and H1F (stations 0 and 31) inhexadecimal.2. *3 indicates the control code.

Pagina 31

PARAMETERS1135) Waiting timeSpecify the waiting time between the receipt of data at the inverter from the computer and the transmissionof reply data.

Pagina 32

PARAMETERS1147) Sum check codeThe sum check code is 2-digit ASCII (hexadecimal) representing the lower 1 byte (8 bits) of the sum(binary) derived fro

Pagina 33

PARAMETERS115(5) Instructions for the program1) If the data from the computer is in error, the inverter will not accept that data. Hence, always inse

Pagina 34

PARAMETERS116<Setting items and set data>After completion of parameter setting, set the instruction codes and data and start communication from

Pagina 35

1.3 StructureOUTLINE31.3 Structure1.3.1 Appearance and structure(1) Front viewPOWER lampALARM lampOperation panel (FR-DU04)Accessory coverWiring port

Pagina 36

PARAMETERS117No. ItemInstructionCodeDescriptionNumberof DataDigits3 Run command HFAb0: b1: Forward rotation (STF)b2: Reverse rotation (STR)b3: b4: b5

Pagina 37

PARAMETERS118No. ItemInstructionCodeDescriptionNumberof DataDigitsRead H6CWhen setting the programmed operation(data code H3D to H5A, HBD to HDA)para

Pagina 38 - Low-level signal contacts

PARAMETERS119(6) Communication specifications for RS-485 communicationOperation ModeOperation Location ItemCommunicationOperation from PUConnectorExt

Pagina 39 - 2.3 Other wiring

PARAMETERS120Pr. 73 "0-5V/0-10V selection"Pr. 79 "operation mode selection"Pr. 180 to Pr. 186 (input terminal assignment)Pr

Pagina 40

PARAMETERS121(2) PID action overview1) PI actionA combination of proportional control action (P) and integral control action (I) for providing a mani

Pagina 41

PARAMETERS1224) Reverse actionIncreases the manipulated variable (output frequency) if deviation X = (set point - process value) ispositive, and decr

Pagina 42

PARAMETERS123(4) I/O signalsSignal Terminal Used Function Description RemarksX14Depending onPr. 180 to Pr. 186PID controlselectionSwitch on X14 to se

Pagina 43

PARAMETERS124(5) Parameter settingParameterNumberSetting Name Description10For heating, pressure control,etc.PID reverseaction11 For cooling, etc.Dev

Pagina 44

PARAMETERS125(7) Calibration example(A detector of 4mA at 0°C (32°F) and 20mA at 50°C (122°F) is used to adjust the room temperature to 25°C(77°F) un

Pagina 45

PARAMETERS126<Set point input calibration>1. Apply the input voltage of 0% set point setting (e.g. 0V) to across terminals 2-5.2. Make calibrat

Pagina 46

OUTLINE41.3.2 Removal and reinstallation of the front coverFR-F520-0.75K to 11K, FR-F540-0.75K to 11K• Removal1) Hold both sides of the front cover to

Pagina 47

PARAMETERS1274.2.41 Commercial power supply-inverter switch-over function(Pr. 135 to Pr. 139)Pr. 135 "commercial power supply-inverterswitch-ove

Pagina 48 - 2.3.6 Peripheral devices

PARAMETERS128(1) Wiring exampleSink logic, Pr. 185 = 7, Pr. 186 = 6, Pr. 192 = 17, Pr. 193 = 18, Pr. 194 = 19*3. The terminals used depend on the Pr.

Pagina 49

PARAMETERS129• Roles of the magnetic contactors (MC1, MC2, MC3)MagneticContactorPlace of Installation RoleMC1Between power supply andinverterNormally

Pagina 50

PARAMETERS130(2) Parameter settingParameterNumberName Setting Description0Sequence output is not provided. (Pr. 136, Pr. 137, Pr. 138 and Pr. 139 set

Pagina 51

PARAMETERS131(3) Operation procedure1) Operation procedure for runningOperation pattern! Pr. 135 = "1" (inverter's open collector outp

Pagina 52

PARAMETERS132Note: 1. This function is only activated when R1 and S1 are connected to a different power supply (powersupply which is not connected to

Pagina 53 - 2.3.9 Earthing (EC version)

PARAMETERS133Pr. 190 to Pr. 195 (output terminal function selection)Related parameters4.2.42 Zero current detection (Pr. 152, Pr. 153)Pr. 152 &qu

Pagina 54 - OPERATION/CONTROL

PARAMETERS1344.2.43 RT signal activated condition selection (Pr. 155)Pr. 155 "RT signal activated condition"#Set the condition of activatin

Pagina 55 - 3.1 Pre-Operation Information

PARAMETERS135<Setting>Refer to the following table and set the parameter as required:Stall Prevention Operation Selection$$$$...Activated####..

Pagina 56

PARAMETERS136CAUTION Always perform test operation.Stall prevention operation performed during acceleration may increase theacceleration time.Stall p

Pagina 57 - 3.1.2 Power on

OUTLINE5FR-F520-30K to 55K, FR-F540-30K to 55K• Removal1) Remove the front cover mounting screws.• Reinstallation1) Fix the front cover with the mount

Pagina 58 - 3.2 Operation Panel

PARAMETERS1374.2.46 User group selection (Pr. 160, Pr. 173 to Pr. 176)Pr. 160 "user group read selection"Pr. 173 "user group 1 registr

Pagina 59 - 3.2.4 Frequency setting

PARAMETERS138Pr. 52 "DU/PU main display data selection"Related parameterNote: 1. Pr. 77, Pr. 160 and Pr. 991 values can always be read

Pagina 60

PARAMETERS139<Setting>Refer to the following list and set the parameters:SettingSignalNameFunctions Relevant ParametersPr. 59 = 0 Low-speed ope

Pagina 61 - 3.2.7 Help mode

PARAMETERS1404.2.49 Output terminal function selection (Pr. 190 to Pr. 195)Pr. 190 "RUN terminal function selection"Pr. 191 "SU termin

Pagina 62

PARAMETERS141SettingPositivelogicNegativelogicSignalNameFunction OperationRelatedparameter17MC1Commercial power supply-inverter switch-over MC118

Pagina 63 - 3.2.8 Copy mode

PARAMETERS142Pr. 77 "parameter write disable selection"Related parameter4.2.50 User initial value setting (Pr. 199)Pr. 199 "user&

Pagina 64 - 3.3.1 Parameter checking

PARAMETERS1434.2.51 Cooling fan operation selection (Pr. 244)Pr. 244 "cooling fan operation selection"You can control the operation of the

Pagina 65 - Simple mode parameter

PARAMETERS1444.2.53 Override bias/gain (Pr. 252, Pr. 253)Pr. 252 "override bias"Pr. 253 "override gain"When you have selected ove

Pagina 66 - 3.3.2 Main parameter settings

PARAMETERS1454.2.54 Advanced PID control (Pr. 500 to Pr. 516) (NA, EC versions only)Pr. 500 "Auxiliary motor operation selection"Pr. 501 &q

Pagina 67

PARAMETERS146 (1) Pr. 501=0Q2Q1(2) Pr. 501=1(3) Pr. 501=2QmaxQ3Flow rate QMotor 1 (M1)Motor 2 (M2)Motor 3 (M3)Motor 4 (M4)Motor 1 (M1)Motor 2 (M2)Mot

Pagina 68 - 3.4 Operation

OUTLINE61.3.3 Removal and reinstallation of the operation panelTo ensure safety, remove and reinstall the operation panel after switching power off.•

Pagina 69 - CONTROL PANEL

PARAMETERS147(3) Pr. 501 "motor switch-over selection" = "2" (Direct Method)When the start signal is entered, the motor is starte

Pagina 70 - 3.4.3 PU operation mode

PARAMETERS148(2) Pr. 501 "motor switch-over selection" = 1 (Alternative Method), 2 (Direct Method)RST UVWJOGSD102514FUOLIPFSERI01R01RI02MCR

Pagina 71 - 3.4.4 Combined operation mode

PARAMETERS149#PID controlPID actions are performed as set in Pr. 128 to Pr. 134 (PID control). (Refer to page 120)In this advanced PID control, a vol

Pagina 72 - PARAMETERS

PARAMETERS150<Motor switch-over timing>(1) Pr. 501 "motor switch-over selection" = 0 (Basic method)Pr. 501 "motor switch-over se

Pagina 73 - 4.1 Parameter List

PARAMETERS151#You can set the output frequency of the inverter-operated motor at which the commercial power supplyoperation motors start. When the ou

Pagina 74

PARAMETERS152<Output stop detection>TdSTOP STARTTimeTimeMotorPr. 508: Output stop cancel levelPr. 507: Output stop levelPr. 506: Output stop de

Pagina 75

PARAMETERS153<Status transition chart>(1) Pr. 501 "motor switch-over selection" = 0 (Basic method) (For four motors)STF(STR)R03R02R04

Pagina 76

PARAMETERS154(2) Pr. 501 "motor switch-over selection" = 1 (Alternative method) (For two motors)RI01RI02R01R02M1M260Hz(EC version50Hz)Pr. 5

Pagina 77

PARAMETERS155Pr. 54 "FM terminal function selection"Pr. 55 "frequency monitoring reference"Pr. 56 "current monitoring refere

Pagina 78

PARAMETERS156<Operation procedure>• When operation panel (FR-DU04) is used8) Press the key to stop the inverter.1) Sele

Pagina 79

2 CHAPTER 2INSTALLATION AND WIRINGThis chapter gives information on the basic "installation andwiring" of this product.Always read the instr

Pagina 80

PARAMETERS1574.2.56 Frequency setting voltage (current) bias and gain(Pr. 902 to Pr. 905)Pr. 902 "frequency setting voltage bias"Pr. 903 &q

Pagina 81 - Output voltage

PARAMETERS158Pr. 903 "frequency setting voltage gain"(Pr.902, Pr. 904, Pr. 905 can also be adjusted similarly.)<Adjustment procedure>

Pagina 82

PARAMETERS1592) Set "1" (PU operation mode) in Pr. 79 "operation mode selection".Example: To change the external operation mode (

Pagina 83

PARAMETERS160(3)Read Pr. 903 and show the current setting of the gain frequency.(Pr. 902, Pr. 904 and Pr. 905 can also be adjusted similarly.)SET0 to

Pagina 84

PARAMETERS161When not adjusting the gain voltage → go to (5) -1)When adjusting any point by applying a voltage → go to (5) -2)When adjusting any poin

Pagina 85

PARAMETERS162Note: 1. If the Pr. 903 or Pr. 905 (gain adjustment) value is changed, the Pr. 20 value does not change.The input signal to terminal 1 (

Pagina 86

5 CHAPTER 5PROTECTIVE FUNCTIONSThis chapter explains the "protective functions" of thisproduct.Always read the instructions before using the

Pagina 87

5.1 Errors (Alarms)PROTECTIVE FUNCTIONS1635 PROTECTIVE FUNCTIONS5.1 Errors (Alarms)If any fault has occurred in the inverter, the corresponding protec

Pagina 88

PROTECTIVE FUNCTIONS164Operation PanelIndicationE.OC3FR-PU04OC During DecNameOvercurrent shut-off during decelerationDescriptionWhen the inverter outp

Pagina 89

PROTECTIVE FUNCTIONS165Operation PanelIndicationE.THMFR-PU04Motor OverloadNameMotor overload shut-off (electronic overcurrent protection) (Note 1)Desc

Pagina 90

2.1 InstallationINSTALLATION AND WIRING72 INSTALLATION AND WIRING2.1 Installation2.1.1 Instructions for installation1) Handle the unit carefully.The i

Pagina 91

PROTECTIVE FUNCTIONS166Operation PanelIndicationE.UVTFR-PU04Under VoltageNameUndervoltage protectionDescriptionIf the power supply voltage of the inve

Pagina 92

PROTECTIVE FUNCTIONS167Operation PanelIndicationE.OLTFR-PU04Stll Prev STP (OL shown during stallprevention operation)NameStall preventionDescriptionTh

Pagina 93

PROTECTIVE FUNCTIONS168Operation PanelIndicationE.PUEFR-PU04PU Leave OutNameParameter unit disconnectionDescriptionThis function stops the inverter ou

Pagina 94

PROTECTIVE FUNCTIONS169Operation PanelIndicationE.P24FR-PU04E. P24Name24VDC power output short circuitDescriptionWhen the 24VDC power output from the

Pagina 95

PROTECTIVE FUNCTIONS170(2) Minor faultWhen the protective function is activated, the output is not shut off. You can make parameter setting to outputt

Pagina 96

PROTECTIVE FUNCTIONS171Operation PanelIndicationoLFR-PU04oLNameStall prevention (overvoltage)DescriptionDuringdecelerationIf the regenerative energy o

Pagina 97

PROTECTIVE FUNCTIONS1725.1.2 To know the operating status at the occurrence of an alarmWhen any alarm has occurred, the display automatically switches

Pagina 98

PROTECTIVE FUNCTIONS1735.1.4 Alarm code outputBy setting Pr. 76 "alarm code output selection", an alarm definition can be output as a 4-bit

Pagina 99 - (Pr. 52 to Pr. 54, Pr. 158)

5.2 TroubleshootingPROTECTIVE FUNCTIONS1745.2 TroubleshootingPOINT: Check the corresponding areas. If the cause is still unknown, it is recommended to

Pagina 100 - With alarm

PROTECTIVE FUNCTIONS1755.2.5 Motor current is largeCheck that the load is not too heavy.Check that the torque boost (Pr. 0, Pr. 46) setting is not too

Pagina 101 - PARAMETERS

INSTALLATION AND WIRING88) For installation in an enclosureVentilation fan(Correct example)Position of Ventilation FanInverter InverterInverter(Correc

Pagina 102

5.3 Precautions for Maintenance and InspectionPROTECTIVE FUNCTIONS1765.3 Precautions for Maintenance and InspectionThe transistorized inverter is a st

Pagina 103

PROTECTIVE FUNCTIONS1775.3.4 Insulation resistance test using megger1) Before performing the insulation resistance test using a megger on the external

Pagina 104

PROTECTIVE FUNCTIONS178IntervalPeriodic*Area ofInspec-tionInspectionItemDescriptionDaily1year2yearsMethod Crlterlon InstrumentInvertermodule,Converter

Pagina 105

PROTECTIVE FUNCTIONS179•••• Checking the inverter and converter modules<Preparation>1) Disconnect the external power supply cables (R, S, T) 〈L1

Pagina 106

PROTECTIVE FUNCTIONS1805.3.7 Replacement of partsThe inverter consists of many electronic parts such as semiconductor devices.The following parts may

Pagina 107

PROTECTIVE FUNCTIONS181(2) Smoothing capacitorsA large-capacity aluminum electrolytic capacitor is used for smoothing the DC in the main circuit, and

Pagina 108

PROTECTIVE FUNCTIONS1825.3.9 Measurement of main circuit voltages, currents and powerMeasurement of voltages and currentsSince the voltages and curren

Pagina 109

PROTECTIVE FUNCTIONS183Measuring Points and InstrumentsItem Measuring Point Measuring InstrumentRemarks(Reference Measured Value) *Power supply voltag

Pagina 110 - 4.2.29 Applied motor (Pr. 71)

6 CHAPTER 6SPECIFICATIONSThis chapter provides the "specifications" of this product.Always read the instructions before using the equipment.

Pagina 111

6.1 Standard SpecificationsSPECIFICATIONS1846 SPECIFICATIONS6.1 Standard Specifications6.1.1 Model specifications####Japanese versionFR-F520-0.75K to

Pagina 112 - 4.2.31 Voltage input (Pr. 73)

A - 1Thank you for choosing this Mitsubishi transistorized Inverter.This instruction manual gives handling information and precautions for use of this

Pagina 113 - (Pr. 75)

2.2 WiringINSTALLATION AND WIRING92.2 Wiring2.2.1 Terminal connection diagramNFBRSTR1S1PCSTFSTRSTOPRHRMRLJOGRTMRSRESAUCSSD10E(+10V)10(+5V)2523114 (4 t

Pagina 114

SPECIFICATIONS185#### Japanese version, EC versionFR-F540-0.75K to 55K (-EC)#### NA versionFR-F540-11K to 55K-NAType FR-F540-""K 0.75 1.5 2.

Pagina 115

SPECIFICATIONS1866.1.2 Common specificationsControl systemSoft-PWM control/high carrier frequency PWM control (V/F control), Optimum excitationcontrol

Pagina 116

SPECIFICATIONS187OperatingstatusSelection can be made from output frequency, motor current (steady or peak value), outputvoltage, frequency setting, r

Pagina 117

SPECIFICATIONS1886.1.3 Outline drawings#### FR-F520-0.75K110 (4.33)260 (10.24)125 (4.92)95 (3.74) 6 (0.24) 5 (0.20) 245 (9.65)2-φ6 hole(Unit: mm (inch

Pagina 118

SPECIFICATIONS189#### FR-F520-5.5K, 7.5K, 11K#### FR-F540-5.5K, 7.5K, 11K220 (8.66)HD211 (8.31)195 (7.68)6 (0.24)H110.5 (0.41)2-φ6 holeD1Inverter Type

Pagina 119

SPECIFICATIONS190#### FR-F520-30K300 (11.81)450 (17.72)195 (7.68)280 (11.02)280 (11.02)430 (16.93)72.5(2.85)3.9 (0.15)10 (0.39)2-φ10 hole(Unit: mm (in

Pagina 120

SPECIFICATIONS191#### Operation panel (FR-DU04)<Outline drawing> <Panel cutting dimension drawing>19.75 (0.78)3.25 (0.13)16.5 (0.65)23.75

Pagina 121

7 CHAPTER 7OPTIONSThis chapter describes the "options" of this product.Always read the instructions before using the equipment. 7.1 Option L

Pagina 122

7.1 Option ListOPTIONS1927 OPTIONS7.1 Option List7.1.1 Stand-alone optionsName Type Application, Specifications, etc.ApplicableInverterParameter unit(

Pagina 123

OPTIONS193Name Type Application, Specifications, etc.ApplicableInverterManual controller FR-AX (Note 4)For independent operation. With frequency meter

Pagina 124

INSTALLATION AND WIRING10(1) Description of main circuit terminalsSymbol Terminal Name DescriptionR, S, T〈L1, L2, L3〉AC power inputConnect to the comm

Pagina 125

OPTIONS1947.1.2 Inboard dedicated options•••• Inboard optionsName Type Function12-bit digital input FR-A5AX• Input interface used to set the inverter

Pagina 126

8APPENDICESThis chapter provides the "appendices" for use of thisproduct.Always read the instructions before using the equipment. Appendix 1

Pagina 127

Appendix 1 Data Code ListAPPENDICES195APPENDICESAppendix 1 Data Code ListData CodesFunc-tionParameterNumberNameRead WriteLink Parameter ExtensionSetti

Pagina 128

APPENDICES196Data CodesFunc-tionParameterNumberNameRead WriteLink Parameter ExtensionSetting (Data code 7F/FF)Additionalfunction59 Remote setting func

Pagina 129

APPENDICES197Data CodesFunc-tionParameterNumberNameRead WriteLink Parameter ExtensionSetting (Data code 7F/FF)140 Backlash acceleration stopping frequ

Pagina 130

APPENDICES198Data CodesFunc-tionParameterNumberNameRead WriteLink Parameter ExtensionSetting (Data code 7F/FF)240 Soft-PWM setting 30 B0 2Subfunction2

Pagina 131 - Minute (Second)

APPENDICES199Data CodesFunc-tionParameterNumberNameRead WriteLink Parameter ExtensionSetting (Data code 7F/FF)345DeviceNet Address Startup Data(Lower

Pagina 132

REVISIONS* The manual number is given on the bottom left of the back cover.Print Data *Manual Number RevisionDec., 1998 IB(NA)-66868-A First editionMa

Pagina 133

INSTALLATION AND WIRING11Type Symbol Terminal Name Description10E10VDC, permissible loadcurrent 10mA10Frequency settingpower supply5VDC, permissible l

Pagina 134

INSTALLATION AND WIRING122.2.2 Wiring of the main circuit(1) Wiring instructions1) Crimping terminals with insulation sleeves are recommended for use

Pagina 135

INSTALLATION AND WIRING139) When rewiring after operation, make sure that the POWER lamp has gone off, and when more than 10minutes have elapsed after

Pagina 136

INSTALLATION AND WIRING14(2) Terminal block layoutIn the main circuit of the inverter, the terminals are arranged as shown below:1) 200V classFR-F520-

Pagina 137

INSTALLATION AND WIRING152) 400V classFR-F540-0.75K, 1.5K, 2.2K, 3.7KUVW PRP1PXScrew size (M4)Screw size (M4)JumperCharge lampR〈L1〉S〈L2〉T〈L3〉N〈–〉P〈+〉R

Pagina 138

INSTALLATION AND WIRING16(3) Cables, crimping terminals, etc.The following table lists the cables and crimping terminals used with the inputs (R, S, T

Pagina 139

INSTALLATION AND WIRING17(5) Connecting the control circuit to a power supply separately from the main circuitIf the magnetic contactor (MC) in the in

Pagina 140 - (Pr. 135 to Pr. 139)

INSTALLATION AND WIRING182.2.3 Wiring of the control circuit(1) Wiring instructions1) Terminals SD, SE and 5 are common to the I/O signals and isolate

Pagina 141

A - 2SAFETY INSTRUCTIONS1. Electric Shock PreventionWARNING! While power is on or when the inverter is running, do not open the front cover. You may g

Pagina 142

INSTALLATION AND WIRING19(3) Changing the control logicThe input signals are set to sink logic for the Japanese and NA version, and to source logic fo

Pagina 143

INSTALLATION AND WIRING204) Sink logic type•In this logic, a signal switches on when a current flows out of the corresponding signal input terminal.Te

Pagina 144

INSTALLATION AND WIRING215) Source logic type•In this logic, a signal switches on when a current flows into the corresponding signal input terminal.Te

Pagina 145

INSTALLATION AND WIRING222.2.4 Connection to the PU connector(1) When connecting the operation panel or parameter unit using a connection cable<Rec

Pagina 146

INSTALLATION AND WIRING232) When a computer having an RS-232C interface is used with invertersComputerTerminal resistorMax. 15mRS-232C connectorRS-485

Pagina 147

INSTALLATION AND WIRING242.2.5 Connection of stand-alone option unitsThe inverter accepts a variety of stand-alone option units as required.Incorrect

Pagina 148

INSTALLATION AND WIRING25(2) Connection of the conventional BU brake unit (option)Connect the BU brake unit correctly as shown below. Incorrect connec

Pagina 149 - OL output signal

INSTALLATION AND WIRING26Note: 1. Remove the jumpers across terminals R-R1 and S-S1 <L1-L11 and L2-L21> of the inverter andconnect the control c

Pagina 150

INSTALLATION AND WIRING272.2.6 Design information1) For commercial power supply-inverter switch-over operation, provide electrical and mechanical inte

Pagina 151 - (Pr. 170, Pr. 171)

2.3 Other wiringINSTALLATION AND WIRING282.3 Other wiring2.3.1 Power harmonicsPower harmonics may be generated from the converter section of the inver

Pagina 152

A - 34. Additional instructionsAlso note the following points to prevent an accidental failure, injury, electric shock, etc.:(1) Transportation and in

Pagina 153

INSTALLATION AND WIRING292.3.2 Japanese harmonic suppression guidelinesHarmonic currents flow from the inverter to a power receiving point via a power

Pagina 154

INSTALLATION AND WIRING30Table 3 Equivalent Capacity LimitsReceived Power Voltage Reference Capacity6.6kV 50kVA22/33kV 300kVA66kV or more 2000kVATable

Pagina 155

INSTALLATION AND WIRING314) Harmonic suppression techniquesNo. Item Description1Reactor installation(ACL, DCL)Install a reactor (ACL) in the AC side o

Pagina 156

INSTALLATION AND WIRING322.3.3 Inverter-generated noises and reduction techniquesSome noises enter the inverter causing it to misoperate and others ar

Pagina 157

INSTALLATION AND WIRING33IMIn-verterReceiverInstrumentTelephoneMotorSensor5)7)2)1)7)3)2)8)3)4)6)Sensor power supplyNoise Path Measures1) 2) 3)When dev

Pagina 158

INSTALLATION AND WIRING34•••• Data examplesBy decreasing the carrier frequency, the noiseterminal voltage* can be reduced. Use Pr. 72 to setthe carrie

Pagina 159

INSTALLATION AND WIRING35#### Example of counter measures against noiseFR-BLFFR-BIFFR-BLFInstall filter (FR-BLF,FR-BSF01) to inverter input side.Contr

Pagina 160

INSTALLATION AND WIRING36(2) Line-to-line leakage currentsHarmonics of leakage currents flowing in static capacities between the inverter output cable

Pagina 161

INSTALLATION AND WIRING372.3.6 Peripheral devices(1) Selection of peripheral devicesCheck the capacity of the motor to be used with the inverter you p

Pagina 162

INSTALLATION AND WIRING38(2) Selection the rated sensitivity current for the earth leakage circuit breakerWhen using the earth leakage circuit breaker

Pagina 163 - Pr. 502 + Pr. 503

A - 4CAUTION! The load used should be a three-phase induction motor only. Connection of any other electricalequipment to the inverter output may damag

Pagina 164

INSTALLATION AND WIRING392.3.7 Instructions for compliance with U.S. and Canadian Electrical Codes(Standard to comply: UL 508C)(1) InstallationThe abo

Pagina 165

INSTALLATION AND WIRING40(5) Motor overload protectionWhen using the electronic overcurrent protection function as motor overload protection, set the

Pagina 166

INSTALLATION AND WIRING41(2) Low Voltage Directive1) Our view of transistorized inverters for the Low Voltage DirectiveTransistorized inverters are co

Pagina 167

INSTALLATION AND WIRING422.3.9 Earthing (EC version)(1) Earthing and Earth Leakage Current(a) Purpose of EarthingElectrical equipment usually has an E

Pagina 168

3 CHAPTER 3OPERATION/CONTROLThis chapter provides the basic "operation/control" for useof this product.Always read this chapter before using

Pagina 169

3.1 Pre-Operation InformationOPERATION/CONTROL433 OPERATION/CONTROL3.1 Pre-Operation Information3.1.1 Devices and parts to be prepared for operationTh

Pagina 170 - (Pr. 902 to Pr. 905)

OPERATION/CONTROL44Preparation• Start signal ...Switch, relay, etc. (for 1)• Frequency setting signal ...0

Pagina 171

OPERATION/CONTROL453.1.2 Power onBefore switching power on, check the following:•••• Installation checkMake sure that the inverter is installed correc

Pagina 172 - MON EXT PU

3.2 Operation PanelOPERATION/CONTROL463.2 Operation PanelWith the operation panel (FR-DU04), you can set the running frequency, monitor the operation

Pagina 173

OPERATION/CONTROL473.2.3 Monitoring• Operation command indications in the monitoringEXT is lit to indicate external operation.PU is lit to indicate PU

Pagina 174

CONTENTSI1 OUTLINE 11.1 Pre-Operation Information...

Pagina 175

OPERATION/CONTROL483.2.5 Parameter setting method• A parameter value may either be set by updating its parameter number or setting the value digit-by-

Pagina 176 - PROTECTIVE FUNCTIONS

OPERATION/CONTROL493.2.6 Operation modeMODE MODEMODETo 3.2.7 Help mode#External operation#PU operation#PU jog operationFR-DU04CONTROL PANELHzMON EXT P

Pagina 177 - 5.1 Errors (Alarms)

OPERATION/CONTROL50(2) Alarm history clearClears all alarm history.SET SETSETFlickerCancelFR-DU04CONTROL PANELHzMON EXT PUAVREV FWDFR-DU04CONTROL PANE

Pagina 178

OPERATION/CONTROL513.2.8 Copy modeBy using the operation panel (FR-DU04), the parameter values can be copied to another inverter (only theFR-F500 seri

Pagina 179

3.3 Parameter Checking and SettingOPERATION/CONTROL523.3 Parameter Checking and SettingThe inverter is designed to perform simple variable-speed opera

Pagina 180

OPERATION/CONTROL53ParameterNumberName Application60 Intelligent mode selectionUsed to cause the inverter to automatically set the appropriate paramet

Pagina 181

OPERATION/CONTROL543.3.2 Main parameter settingsThe main parameter settings are given below. For more information, refer to "CHAPTER 4 PARAMETERS

Pagina 182

OPERATION/CONTROL55(5) Selection of load pattern (Pr. 14 "load pattern selection")Used to select the output characteristic (V/F characterist

Pagina 183

3.4 OperationOPERATION/CONTROL563.4 Operation3.4.1 Pre-operation checksBefore starting operation, check the following:• SafetyPerform test operation a

Pagina 184 - (3) Warnings

OPERATION/CONTROL573.4.2 External operation mode (Operation using external input signals)(1) Operation at 60HzStep Description Image1Power-on → Operat

Pagina 185

II3.3.2 Main parameter settings ...

Pagina 186

OPERATION/CONTROL583.4.3 PU operation mode(Operation using the operation panel (FR-DU04))(1) Operation at 60HzWhile the motor is running, repeat the f

Pagina 187 - 5.1.5 Resetting the inverter

OPERATION/CONTROL593.4.4 Combined operation mode(Operation using the external input signals and PU)When entering the start signal from outside the inv

Pagina 188 - 5.2 Troubleshooting

4 CHAPTER 4PARAMETERSThis chapter explains the "parameters" of this product.Always read the instructions before using the equipment. 4.1 Par

Pagina 189

4.1 Parameter List PARAMETERS604 PARAMETERS4.1 Parameter List4.1.1 Parameter listAll parameters available when the Pr. 160 "user group read selec

Pagina 190 - 5.3.3 Periodic inspection

PARAMETERS61Func-tionParameterNumberName Setting RangeMinimumSettingIncrementsFactorySetting〈〈〈〈ECVersion〉〉〉〉ReferToPage:Cust-omerSet-ting41 Up-to-fr

Pagina 191 - 5.3.5 Pressure test

PARAMETERS62Func-tionParameterNumberName Setting RangeMinimumSettingIncrementsFactorySetting〈〈〈〈ECVersion〉〉〉〉ReferToPage:Cust-omerSet-ting107 V/F4 (f

Pagina 192

PARAMETERS63Func-tionParameterNumberName Setting RangeMinimumSettingIncrementsFactorySetting〈〈〈〈ECVersion〉〉〉〉ReferToPage:Cust-omerSet-ting152 Zero cu

Pagina 193 - <Checking method>

PARAMETERS64Func-tionParameterNumberName Setting RangeMinimumSettingIncrementsFactorySetting〈〈〈〈ECVersion〉〉〉〉ReferToPage:Cust-omerSet-ting$240 Soft-P

Pagina 194 - <Example: FR-F540-5.5K>

PARAMETERS654.1.2 List of Parameters Classified by Purposes of UseSet the parameters according to the operating conditions. The following list indica

Pagina 195 - 5.3.8 Inverter replacement

4.2 Parameter Function Details PARAMETERS664.2 Parameter Function Details4.2.1 Torque boost (Pr. 0, Pr. 46)Pr. 0 "torque boost"Pr. 46 "

Pagina 196

III4.2.39 Computer link operation (Pr. 117 to Pr. 124)...

Pagina 197

PARAMETERS674.2.2 Output frequency range (Pr. 1, Pr. 2)Pr. 1 "maximum frequency"Pr. 2 "minimum frequency"Used to clamp the upper

Pagina 198 - SPECIFICATIONS

PARAMETERS684.2.3 Base frequency, base frequency voltage (Pr. 3, Pr. 19, Pr. 47)Pr. 3 "base frequency"Pr. 19 "base frequency voltage&q

Pagina 199 - 6.1 Standard Specifications

PARAMETERS694.2.4 Multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr.27)Pr. 4 "multi-speed setting (high speed)"Pr. 5 "multi-speed se

Pagina 200

PARAMETERS704.2.5 Acceleration/deceleration time(Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45)Pr. 7 "acceleration time"Pr. 8 "decelera

Pagina 201 - 6.1.2 Common specifications

PARAMETERS71Pr. 71 "applied motor"Related parameterNote: 1. In S-shaped acceleration/deceleration pattern A (refer to page 79), the set tim

Pagina 202

PARAMETERS72Pr. 13 "starting frequency"Pr. 71 "applied motor"Related parameters4.2.7 DC injection brake (Pr. 10 to Pr. 12)Pr. 10

Pagina 203 - 95 (3.74)

PARAMETERS734.2.8 Starting frequency (Pr. 13)Pr. 13 "starting frequency"You can set the starting frequency between 0 and 60Hz.# Set the sta

Pagina 204

PARAMETERS744.2.9 Load pattern selection (Pr. 14)Pr. 14 "load pattern selection"You can select the optimum output characteristic (V/F chara

Pagina 205

PARAMETERS75Pr. 20 "acceleration/decelerationreference frequency"Pr. 21 "acceleration/deceleration timeincrements"Pr. 79 "op

Pagina 206

PARAMETERS764.2.11 MRS input selection (Pr. 17)Pr. 17 "MRS input selection"Used to select the logic of the MRS signal.When the MRS signal s

Pagina 207 - CHAPTER 7

IV6 SPECIFICATIONS 1846.1 Standard Specifications...

Pagina 208 - 7.1 Option List

PARAMETERS774.2.12 Stall prevention (Pr. 22, Pr. 23, Pr. 66, Pr. 148, Pr. 149, Pr. 154)Pr. 22 "stall prevention operation level"Pr. 23 &quo

Pagina 209

PARAMETERS78<Setting>• In Pr. 22, set the stall prevention operation level. Normally set it to 120% (factory setting). Set "0" in Pr.

Pagina 210 - • Inboard options

PARAMETERS794.2.14 Acceleration/deceleration pattern (Pr. 29, Pr.140 to Pr.143)Pr. 29 "acceleration/deceleration pattern"Pr. 140 "back

Pagina 211 - APPENDICES

PARAMETERS804.2.15 Regenerative brake duty (Pr.30)Pr. 30 "regenerative function selection"#Use the optional "high power factor convert

Pagina 212 - Appendix 1 Data Code List

PARAMETERS814.2.16 Frequency jump (Pr. 31 to Pr. 36)Pr. 31 "frequency jump 1A"Pr. 32 "frequency jump 1B"Pr. 33 "frequency ju

Pagina 213

PARAMETERS824.2.17 Speed display (Pr. 37, Pr. 144)Pr. 37 "speed display"Pr. 144 "speed setting switch-over"The units of the runni

Pagina 214

PARAMETERS83Pr. 190 "RUN terminal functionselection"Pr. 191 "SU terminal function selection"Pr. 192 "IPF terminal function s

Pagina 215

PARAMETERS844.2.20 Output frequency detection (Pr. 42, Pr. 43, Pr. 50)Pr. 42 "output frequency detection"Pr. 43 "output frequency dete

Pagina 216

PARAMETERS854.2.21 Second stall prevention (Pr. 48, Pr. 49)Pr. 48 "second stall prevention operation current"Pr. 49 "second stall prev

Pagina 217 - REVISIONS

PARAMETERS864.2.22 Monitor display / FM, AM terminal function selection(Pr. 52 to Pr. 54, Pr. 158)Pr. 52 "DU/PU main display data selection"